Technical data sheetEXT-LD14125BE1AX www.belimo.usEXT-LD14125BE1AX • en-us • 2021-03-03 • Subject to change1 / 3 • Potable Water Valve, 2-way, flange • For potable water applications • NSF/ANSI 372 - Lead Free • NSF/ANSI 61 - Water Quality • CRN: OC/2102CL • MSS SP67-2002a Technical data Functional dataValve Size2.5" [65] FluidPotable water Fluid Temp Range (water)-22...250°F [-30...120°C] Body Pressure RatingANSI Class Consistent with 125, 200 psi CWP Close-off pressure ∆ ps200 psi Flow characteristicmodified equal percentage Installation positionupright to horizontal (in relation to the stem) Servicingmaintenance-free Rangeability Sv30:1 (for 30...70° range) Flow Pattern2-way Leakage rate0% Controllable flow range90° rotation Cv196 ANSI ClassConsistent with 125 Maximum Velocity12 FPS Lug threads5/8-11 UNC Materials Valve bodyDuctile cast iron ASTM A536 Body finishEpoxy powder coating (black RAL 9005) Stem416 stainless steel Stem sealBuna-N SeatEPDM Pipe connectionfor use with ANSI class 125/150 flanges BearingRPTFE DiscAluminum Bronze Suitable actuators Non-SpringAMB(X) SpringAF Electronic fail-safeGRCB(X) GKRB(X) Safety notes The valve has to be exercised at least once a week, so that the quality of potable water as well as the functionality are not affected.Technical data sheetEXT-LD14125BE1AX www.belimo.usEXT-LD14125BE1AX • en-us • 2021-03-03 • Subject to change2 / 3 Mode of operation Product features Flow/Mounting details Product features The valve is adjusted by a rotary actuator. The rotary actuator is connected by an on/off signal. Open the ball valve counterclockwise and close it clockwise. Dimensions Dimensional drawings Valve with AFX Actuator ABCDEFNumber of Bolt Holes 10.1" [257]1.9" [49]16.0" [406]12.9" [328]3.5" [89]3.5" [89]4 Valve with AM Actuator ABCDEFNumber of Bolt Holes 10.1" [257]1.9" [49]16.0" [406]12.9" [328]3.5" [89]3.5" [89]4Technical data sheetEXT-LD14125BE1AX www.belimo.usEXT-LD14125BE1AX • en-us • 2021-03-03 • Subject to change3 / 3 Valve with DR N4/GR N4/GK N4 Actuator ABCDEFNumber of Bolt Holes 14.1" [358]1.9" [49]21.7" [550]18.5" [470]3.4" [86]3.4" [86]4Technical data sheetGKRX24-3 N4 www.belimo.usGKRX24-3 N4 • en-us • 2021-03-03 • Subject to change1 / 2 NEMA 4, On/Off, Floating Point, Electronic Fail- Safe, 24 V Technical data Electrical dataNominal voltageAC 24 V Nominal voltage frequency50/60 Hz Power consumption in operation12 W Power consumption in rest position3 W Transformer sizing21 VA (class 2 power source) / heater 21 VA Electrical Connection18 GA plenum cable, 3 ft [1 m], with 1/2" conduit connector Overload Protectionelectronic thoughout 0...90° rotation Functional data Input Impedance100 kΩ Bridging time2 s delay before fail-safe activates Pre-charging time5...20 s Direction of motion motorselectable with switch 0/1 Direction of motion fail-safereversible with switch Manual overrideunder cover Angle of rotationMax. 95°, adjustable with mechanical stop Angle of rotation noteadjustable with mechanical stop Running Time (Motor)150 s constant, independent of load Running time motor noteconstant, independent of load Running time fail-safe<35 s Noise level, motor52 dB(A) Noise level, fail-safe61 dB(A) Position indicationMechanically, 30...65 mm stroke Safety data Degree of protection IEC/ENIP66/67 Degree of protection NEMA/ULNEMA 4X UL Enclosure Type 4X Agency ListingcULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1, CSA C22.2 No 24-93, CE acc. to 89/336/EC Quality StandardISO 9001 Ambient temperature-22...122°F [-30...50°C] Storage temperature-40...176°F [-40...80°C] Ambient humiditymax. 95% r.H., non-condensing Servicingmaintenance-free Weight Weight3.2 lb [4.1 kg] Materials Housing materialPolycarbonate Electrical installation INSTALLATION NOTES Provide overload protection and disconnect as required.Technical data sheetGKRX24-3 N4 www.belimo.usGKRX24-3 N4 • en-us • 2021-03-03 • Subject to change2 / 2 Actuators may be connected in parallel. Power consumption and input impedance must be observed. Actuators may also be powered by 24 VDC. Actuators may be connected in parallel if not mechanically linked. Power consumption and input impedance must be observed. Actuators are provided with a numbered screw terminal strip instead of a cable. Meets cULus requirements without the need of an electrical ground connection. Warning! Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. On/Off Floating Point NEMA 4 HeaterNext >