EXT-LD14108BE1AX • en-us • 2022-04-07 • Subject to change1 / 3 • Valve size [mm]8" [200] FluidPotable water Fluid Temp Range (water)-22...250°F [-30...120°C] Body Pressure RatingANSI Class Consistent with 125, 200 psi CWP Close-off pressure ∆ ps150 psi Flow characteristicmodified equal percentage Installation positionupright to horizontal (in relation to the stem) Servicingmaintenance-free Rangeability Sv30:1 (for 30...70° range) Flow Pattern2-way Leakage rate0% Controllable flow range90° rotation Cv1579 Maximum Velocity12 FPS Lug threads3/4-10 UNC Valve bodyDuctile cast iron ASTM A536 Body finishEpoxy powder coating (black RAL 9005) Spindle416 stainless steel Spindle sealBuna-N SeatEPDM Pipe connectionfor use with ANSI class 125/150 flanges BearingRPTFE DiscAluminum Bronze Non-SpringDRB(X) DRCB(X) N4 Electrical fail-safeDKRB(X) The valve has to be exercised at least once a week, so that the quality of potable water as well as the functionality are not affected.EXT-LD14108BE1AX • en-us • 2022-04-07 • Subject to change2 / 3 The valve is adjusted by a rotary actuator. The rotary actuator is connected by an on/off signal. Open the ball valve counterclockwise and close it clockwise. 200[] Valve with DR/DK Actuator 11.3" [286]2.3" [58]22.1" [562]18.0" [457]5.4" [137]5.4" [137]8EXT-LD14108BE1AX • en-us • 2022-04-07 • Subject to change3 / 3 Valve with DR N4/DK N4 Actuator 14.1" [358]2.3" [58]25.1" [638]20.1" [511]5.4" [137]5.4" [137]8PRXUP-MFT-T • en-us • 2022-04-07 • Subject to change1 / 5 Nominal voltageAC 24...240 V / DC 24...125 V Nominal voltage frequency50/60 Hz Nominal voltage rangeAC 19.2...264 V / DC 19.2...137.5 V Power consumption in operation20 W Power consumption in rest position6 W Transformer sizingwith 24 V 20 VA / with 240 V 52 VA Auxiliary switch2 x SPDT, 3 A resistive (0.5 A inductive) @ AC 250 V, 1 x 10° / 1 x 0...90° (default setting 85°) Switching capacity auxiliary switch3 A resistive (0.5 A inductive) @ AC 250 V Electrical ConnectionTerminal blocks, (PE) Ground-Screw Overload Protectionelectronic thoughout 0...90° rotation Communicative controlBACnet MS/TP Modbus RTU MP-Bus Torque motor160 Nm Operating range Y2...10 V Operating range Y note4...20 mA Input Impedance100 kΩ for 2...10 V (0.1 mA), 500 Ω for 4...20 mA, 1500 Ω for On/Off Operating range Y variableStart point 0.5...30 V End point 2.5...32 V Operating modes optionalvariable (VDC, on/off, floating point) Position feedback U2...10 V Position feedback U noteMax. 0.5 mA Position feedback U variableVDC variable Direction of motion motorreversible with app Manual override7 mm hex crank, supplied Angle of rotation90° Running Time (Motor)35 s / 90° Running time motor variable30...120 s Noise level, motor68 dB(A) Position indicationintegral pointer Power source ULClass 2 Supply Degree of protection IEC/ENIP66/67 Degree of protection NEMA/ULNEMA 4X EnclosureUL Enclosure Type 4X Agency ListingcULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2014/30/EU and 2014/35/EU Quality StandardISO 9001PRXUP-MFT-T • en-us • 2022-04-07 • Subject to change2 / 5 Ambient temperature-22...122°F [-30...50°C] Storage temperature-40...176°F [-40...80°C] Ambient humidityMax. 100% RH Servicingmaintenance-free Weight13 lb [5.9 kg] Housing materialDie cast aluminium and plastic casing PR Series valve actuators are designed with an integrated linkage and visual position indicators. For outdoor applications, the installed valve must be mounted with the actuator at or above horizontal. For indoor applications the actuator can be in any location including directly under the valve. Gateway MP to BACnet MS/TPUK24BAC Gateway MP to Modbus RTUUK24MOD Gateway MP to LonWorksUK24LON Service Tool, with ZIP-USB function, for programmable and communicative Belimo actuators, VAV controller and HVAC performance devices ZTH US Hand crank for PR, PKR, PMZG-HND PR Connection cable 10 ft [3 m], A: RJ11 6/4 ZTH EU, B: 3-pin Weidmüller and supply connection ZK4-GEN Service Tool, with ZIP-USB function, for programmable and communicative Belimo actuators, VAV controller and HVAC performance devices ZTH US Duct/Immersion sensor Temperature 6" [150 mm] x 0.24" [6 mm] Pt100001DT-5BN Duct/Immersion sensor Temperature 2" [50 mm] x 0.24" [6 mm] Pt100001DT-5BH Duct/Immersion sensor Temperature 4" [100 mm] x 0.24" [6 mm] Pt100001DT-5BL Duct/Immersion sensor Temperature 8" [200 mm] x 0.24" [6 mm] Pt100001DT-5BP Duct/Immersion sensor Temperature 18" [450 mm] x 0.24" [6 mm] Pt1000 01DT-5BT 01DT-5EH 01DT-5EL 01DT-5EN 01DT-5EP Duct/Immersion sensor Temperature 12" [300 mm] x 0.24" [6 mm] Pt1000 01DT-5BR 01DT-5ER 01DT-5ET Meets cULus requirements without the need of an electrical ground connection. Universal Power Supply (UP) models can be supplied with 24 V up to 240 V. Disconnect power. Provide overload protection and disconnect as required. Two built-in auxiliary switches (2x SPDT), for end position indication, interlock control, fan startup, etc. Only connect common to negative (-) leg of control circuits.PRXUP-MFT-T • en-us • 2022-04-07 • Subject to change3 / 5 Actuators may be controlled in parallel. Current draw and input impedance must be observed. During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. On/Off On/Off BACnetPRXUP-MFT-T • en-us • 2022-04-07 • Subject to change4 / 5 Modulating Floating Point Temperature SensorsAuxiliary SwitchesPRXUP-MFT-T • en-us • 2022-04-07 • Subject to change5 / 5Next >