Important. All wiring must conform to local building codes, regulations and laws. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. INSTALLATION INSTRUCTIONS 6000 GAS MONITOR Belimo Sensors Inc - Gas monitors 697 Meloche St. Dorval, Qc. H9P 2S4 Canada 514.556.3013 www.belimo.com Notes: 1) Do not obstruct the monitor 2) Do not ground the 24 Vac 3) When using multiple monitors: a) Maintain the same polarity (24 Vac) for all devices b) CAN bus connection: i) Maintain the same polarity (CAN bus) for all devices ii) Use 22 to 24 AWG Twisted & Shielded cable iii) Monitors must be connected in series iv) Switch end of line (EOL) jumpers (for first and last units) ac Supply Independent Circuit 120 Vac To magnetic starter coil or control relay coil for ventilation Transformer 24 Vac To Other units BACnet MSTP network Binary input to limit switch End of line jumper CAN bus Down = Off unit on cable EOL BACnet 5 VA for each unit NOCOM Relay 1 NCNOCOM Relay 2 NC – + Shield (no connect) Sensor A Sensor B Mounting Holes ½" Conduit 18-20 AWG (24Vac Power) 22 to 24 AWG shielded (CAN bus) 2 Dry contact relays EOL EOL 50 feet (15m) radius for air quality 30 feet (10m) radius for leak detection For gases lighter than air, install at 1 to 3 feet (0.3 to 0.9 meters) from the ceiling: H 2 , CH 4 , NH 3 For gases heavier than air, install 1 to 2 feet (0.3 to 0.5 meters) from oor: HFCs, HCFCs, C 3 H 8 , CL 2 , most organic vapors For gases with similar density to air: 1.H 2 S, O 2 , CO 2 : Install from 3 feet (1 meter) off the oor to one half of the ceiling height 2.CO: Install at 3 to 7 feet (1 to 2 meters) from the oor (recommended: 5 feet / 1.5 meters) 3.NO 2 : Exhaust under vehicle: same as CO Exhaust over vehicle: Install at half the ceiling height Refer to Operation Manual section 3.3 for installation and section 4 for operation and parameters 6000-B 6000-C 6000-A ac Supply Independent Circuit 120 Vac To magnetic starter coil or control relay coil for ventilation Transformer 24 Vac To Other units BACnet MSTP network CAN network Binary input to limit switch End of line jumper CAN bus Down = Off unit on cable Up for rst and last Up Position 4-20mA or Down Position 2-10V EOL BACnet 5 VA for each unit NOCOM Relay 1 NC ANA1G Analogue Output ANA2 – + SHIELD (no connect) High (H) Low (L) Shield (on 1st unit only) to other units 1 Dry contact relays Transformer 24 Vac To Other Detectors Independent Circuit 120 Vac 3VA for each unit Network end-of-line jumper Up for rst and last CAN network High (H) Low (L) Shield (on 1st unit only) to other units CAN network High (H) Low (L) Shield (on 1st unit only) to other units Path for wires 60XXINST_V2.021 OPERA INC. IS NOW BELIMO SENSORS INC.Next >