EXT-6002-250-14-.. • en-us • 2022-02-09 • Subject to change1 / 7 CO, NO₂12x 2...10 V, 2x 4...20 mA CAN bus, BACnet MS/TP CO, NO₂2-CAN bus, BACnet MS/TP CO, NO₂0-CAN bus Nominal voltageAC/DC 24 V Nominal voltage frequency50/60 Hz Nominal voltage rangeAC 17...28 V / DC 17...28 V Power consumption AC5 VA Power consumption DC5 W Cable entry2 top, 2 bottom, 1 rear – 1/2" EMT Cable specification1 pair twisted shielded 24...18AWG FuseThermal PTC, auto-reset Applicationair CommunicationCAN bus BACnet MS/TP Output signal active note2...10 V or 4...20 mA output, selectable with jumper Output signal relay note1 x SPDT, max. 1.5 A (0.4 A inductive), AC 250 V Mounting1.3 m [4 ft] above the floor Max. altitude6562 ft [2000 m] above sea level Coverage areaRadius: 15 m [50 ft] Area: 700 m² [7500 ft²] There can be no obstructions such as walls, stairs, elevators, shelving with solid fill, tool chests, etc. DisplayLCD, with backlight, Gas concentration, system status Response time<30 s (T90) AlarmAudible alarm, 85 db @ 1 m [3.3 ft] Measured valuesCO NO₂ Measuring range gasCO: 0...250 ppm NO₂: 0...10 ppmEXT-6002-250-14-.. • en-us • 2022-02-09 • Subject to change2 / 7 Long-term stability<5% per year <2% per month Measurement Repeatability<+3% CO equivalent <+2% NO₂ equivalent HousingFlame resistant polycarbonate ABS UL-94-V0 and UL-94-5VA for indoor use Ambient humidityMax. 80% RH, non-condensing Ambient temperature-20...40°C [-4...104°F] Protection class IEC/ENII, reinforced insulation Protection class ULII, reinforced insulation Certification ULCAN/CSA 205-2017, CAN/CSA 22.2 No. 152, BTL Pollution degree2 Replacement sensor module NO₂ (Nitrogen Dioxide), 0...10 ppm, Electro- chemical EXT-OP-5514 Replacement sensor module CO (Carbon Monoxide), 0...250 ppm, Electro- chemical EXT-OP-5502-250 Communication module, CAN bus, BACnet MS/TP, 1 x SPDT, max. 1.5 A (0.4 A inductive), AC 250 V EXT-OP-6000-A Communication module, CAN bus, BACnet MS/TP, 2 x SPDT, max. 1.5 A (0.4 A inductive), AC 250 V EXT-OP-6000-B Communication module, CAN busEXT-OP-6000-C Communication module, Ventilated cover, CAN bus, BACnet MS/TP, 2 x SPDT, max. 1.5 A (0.4 A inductive), AC 250 V EXT-OP-6000-BVC Calibration gas bottle, 103 LEXT-OP-Gas-N2 Calibration gas bottle NO₂ (Nitrogen Dioxide), 0...5 ppm, 58 LEXT-OP-Gas-NO2 Calibration gas bottle CO (Carbon Monoxide), 0...100 ppm, 103 LEXT-OP-Gas- CO-100 Alarm hornEXT-OP-5000-AL Splash guard, Wall mountEXT-OP-6000-BT Splash guard, Duct mountEXT-OP-6000-GNEXT-6002-250-14-.. • en-us • 2022-02-09 • Subject to change3 / 7EXT-6002-250-14-.. • en-us • 2022-02-09 • Subject to change4 / 7EXT-6002-250-14-.. • en-us • 2022-02-09 • Subject to change5 / 7EXT-6002-250-14-.. • en-us • 2022-02-09 • Subject to change6 / 7 CAN busEXT-6002-250-14-.. • en-us • 2022-02-09 • Subject to change7 / 7 0.99 lb [0.45 kg] 0.99 lb [0.45 kg] 0.99 lb [0.45 kg]Next >