1 QUICK MOUNT VISUAL INSTRUCTION MANUAL CQK... Actuators with ZoneTight Zone Valves 71775-00001.L 1 2 2 1 1. PIQCV 1 2 2 1 1. QCV SizeValve Model V'max End Stop PositionsV'nom 123-344+55+6NNo end stop 1/2"Z2050Q(S)-F 0.1 0.20.40.60.81.21.4 1/2"Z2050Q(S)-J 0.50.71.21.72.434.85.9 3/4"Z2075Q(S)-K 0.51.01.52.33.34.66.69.8 1"Z2100Q(S)-K 0.50.91.52.23.14.368.2 Runtime (seconds) 3037414349515558626875 QCV/PIQCV Actuator Removal Valve Model (1/2") Clip Position for Flow Adjustment (GPM) 11+2-22+3-33+4-44+5-55+6-66+N-NNo Clip Z2050QPT-B 0.10.20.30.40.50.60.70.80.9 Z2050QPT-D 0.20.30.40.50.60.70.80.91.01.21.31.51.61.82.0 Z2050QPT-F 0.60.70.80.91.01.31.51.71.92.22.52.83.13.33.64.3 Valve Model 3/4" Z2075QPT-G 1.61.8 2.1 2.42.73.03.33.74.04.44.95.35.86.36.77.27.79.0 Runtime 3033353739414345474951535558606264666875 Pull Straight Up. Do not Twist to Remove. Subject to change. © Belimo Aircontrols (USA), Inc.2 kg >122°F PIQCV kg QCV 71775-00001.L QUICK MOUNT VISUAL INSTRUCTION MANUAL CQK... Actuators with ZoneTight Zone Valves3 WIRING DIAGRAMS BLK Black Negro Noir Preto RED Red Rojo Rouge Vermelho WHT White Blanco Blanc Branco ORG Orange Anaranjado Orange Alaranjado CQK..24V, CQKB24 (-RR) (-LL), CQKB24-S (-LL) (-RR), CQKB24-SR (-LL) (-RR) (-LR) (-RL), CQKBUP (-RR) (-LL) Blk Common Red Hot + Line Volts A 2318 FunctionsA 0% 100% 0%Fail PositionClose Blk Common Red Hot + Line Volts A 2318 FunctionsA 0% 100% 100%Fail PositionOpen Blk Common Red + Hot Line Volts A 2318 FunctionsA 100% 0% 0%Fail PositionClose On/Off, CQKB24-RR, CQKBUP-RROn/Off, CQKB24-LL, CQKBUP-LLOn/Off, CQKB24-S-RR Blk Common Red + Hot Line Volts A FunctionsA 0% 100% 23 18 100%Fail PositionOpen On/Off, CQKB24-S-LLProportional, CQKB24-SR-LLProportional, CQKB24-SR-LR Notes: Proportional, CQKB24-SR-RLProportional, CQKB24-SR-RR Blu (1) Neutral Brn (2) Load Blu N Brn L Line Volts 1 2 A 100 to 240 VAC FunctionsA 0% 100% 0%Fail PositionClose On/Off, CQKBUP-RROn/Off, CQKBUP-LL Actuators with appliance cables are numbered. Meets cULus requirements without the need of an electrical ground connection Apply only AC line voltage or only UL-Class 2 voltage to the terminals of auxiliary switches. Mixed or combined operation of line voltage/safety extra low voltage is not allowed. 1 Provide overload protection and disconnect as required. 2 Actuators may be connected in parallel. Power consumption and input impedance must be observed. 3 Actuators may also be powered by 24 VDC. 5 Only connect common to neg. (-) leg of control circuits. 7 A 500 Ω (ZG-R01) converts the 4 to 20 mA control signal to 2 to 10 VDC. 18 Actuators with plenum rated cable do not have numbers on wires; use color codes instead. 100 One built-in auxiliary switch, 1x SPST 1A @ 24 VAC/DC (resistive load), for end position indication, interlock control, fan startup, etc. S1 S2 NO 1100 S1 S2 NO 1 100 (–) (+) Line Volts 500 1/4 watt Control Signal VDC / mA 7 Blk (1) Red (2) Wht (3) Org (5) Common + Hot Y Input U Output Feedback Signal (+) 100%Fail Position 2 VDCOpen 10 VDCClose Open 23185 QUICK MOUNT VISUAL INSTRUCTION MANUAL CQK... Actuators with ZoneTight Zone Valves 71775-00001.L Blu (1) Neutral Brn (2) Load Blu N Brn L Line Volts 1 2 A 100 to 240 VAC FunctionsA 0% 100% 100%Fail PositionOpen (–) (+) Line Volts 500 1/4 watt Control Signal VDC / mA 7 Blk (1) Red (2) Wht (3) Org (5) Common + Hot Y Input U Output Feedback Signal (+) 23185 0%Fail Position 2 VDC Open 10 VDCClose Close (–) (+) Line Volts 500 1/4 watt Control Signal VDC / mA 7 Blk (1) Red (2) Wht (3) Org (5) Common + Hot Y Input U Output Feedback Signal (+) 23185 100%Fail Position 2 VDCClose 10 VDCOpen Open (–) (+) Line Volts 500 1/4 watt Control Signal VDC / mA 7 Blk (1) Red (2) Wht (3) Org (5) Common + Hot Y Input U Output Feedback Signal (+) 23185 0%Fail Position 2 VDCClose 10 VDCOpen Close ANext >