Technical Data2132Servicechilled, hot water, up to 60% glycolFlow Characteristicequal percentageControllable Flow Range75°Size [mm]3” [80]End Fittingpattern to mate with ANSI 125 flangeBodycast iron - GG25Ballstainless steelStemstainless steelStem PackingEPDM (lubricated)SeatTeflon® PTFESeat O-ringEPDM (lubricated)Characterized Discstainless steelBody Pressure Rating [psi]ANSI 125, standard class BNumber of Bolt Holes4Media Temperature Range (Water)0°F to 250°F [-18°C to 120°C]Max Differential Pressure (Water)50 psi (345 kPa)Close-Off Pressure100 psiCv110 Weight32 lb [14.5 kg]Leakage0% for A to ABServicingmaintenance freeFlow PatternApplicationThis valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant flow.Suitable Actuators Non-SpringSpringB6300S-110ARB(X)AFRB(X)Dimensions (Inches [mm])GIEFCDBAARB, ARXABCDEFGI9.61” [244]6.61” [168]12.01” [309]7.79” [198]3.94” [100]6” [152]0.75” [19]B6300S-110, 2-Way, Characterized Control ValveStainless Steel Ball and Stem800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 11/01/2016 - Subject to change. © Belimo Aircontrols (USA), Inc.Dimensions (Inches [mm])DBACEFGIAFRB, AFRXABCDEFGI9.61” [244]6.61” [168]12.79” [325]9.37” [238]3.94” [100]6” [152]0.75” [19]Dimensions (Inches [mm])EFGIDCBAARXABCDEFGI13.25” [337]6.61” [168]15.00” [381]10.47” [266]3.94” [100]6” [152]0.75” [19]Dimensions (Inches [mm])EFGIDCBAAFRXABCDEFGI16” [406]6.61” [168]16.61” [421.9]11.94” [302.23]3.94” [100]6” [152]0.75” [19]B6300S-110, 2-Way, Characterized Control ValveStainless Steel Ball and Stem800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 11/01/2016 - Subject to change. © Belimo Aircontrols (USA), Inc.Technical Data2513Power Supply24 VAC ± 20%, 50/60 Hz, 24 VDC ± 10%Power Consumption Running2.5 WPower Consumption Holding0.5 W Transformer Sizing5.5 VA (class 2 power source)Electrical Connectionterminal blockOverload Protectionelectronic thoughout 0° to 90° rotationInput Impedance600 ΩAngle of Rotation90°Direction of Rotation (Motor)reversible with built-in switchPosition IndicationpointerManual Overrideunder coverRunning Time (Motor)90 sec (default), Optional (90 or 150 sec)Ambient Temperature Range-22°F to 122°F [-30°C to 50°C]Storage Temperature Range-40°F to 176°F [-40°C to 80°C]HousingNEMA 4X, IP66/67, UL enclosure type 4Agency Listings†cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2004/108/EC and 2006/95/ECNoise Level (Motor)<45 dB (A) Servicingmaintenance freeQuality StandardISO 9001†Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 4.ARX24-3-T N4NEMA 4X, On/Off, Floating Point Control, Non-Spring Return, 24 V800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 06/27/2017 - Subject to change. © Belimo Aircontrols (USA), Inc.Wiring DiagramsINSTALLATION NOTESProvide overload protection and disconnect as required.Actuators may be connected in parallel. Power consumption and input impedance must be observed.Actuators may also be powered by 24 VDC.Actuators Hot wire must be connected to the control board common. Only connect common to neg. (-) leg of control circuits. Terminal models (-T) have no-feedback.16Actuators are provided with a numbered screw terminal strip instead of a cable.Meets cULus requirements without the need of an electrical ground connection.!WARNING! LIVE ELECTRICAL COMPONENTS!During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. 24 VAC TransformerLineVolts12316 (1) Common (2) + Hot (3) + InputOn/Off (1) Common (2) + Hot (3) + InputLineVolts1231624 VAC TransformerFloating Point ComHot2316Blk (1) CommonRed (2) + HotWht (3) Y InputLineVolts24 VAC Transformer1Floating Point - Triac Source 216Blk (1) CommonRed (2) + HotWht (3) Y InputLineVolts24 VAC TransformerComHot61Floating Point - Triac SinkARX24-3-T N4NEMA 4X, On/Off, Floating Point Control, Non-Spring Return, 24 V800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 06/27/2017 - Subject to change. © Belimo Aircontrols (USA), Inc.Next >