Technical Data1704Servicehigh temperature hot water/low pressure steam, up to 60% glycolFlow CharacteristicA-port equal percentageControllable Flow Range75°Size [mm]1” [25]End FittingNPT female endsBodynickel plated brass (DZR) P-CuZn35Pb2Ballstainless steelStemstainless steelStem PackingVition O-ringSeatETFESeat O-ringEPDM (lubricated)Characterized DiscETFEBody Pressure Rating [psi]600Max Inlet Pressure (Steam)15 psiMedia Temperature Range (Water)60°F to 266°F [16°C to 130°C]Media Temperature Range (Steam)250°F [120°C]Maximum Differential Pressure (Steam)15 psiMax Differential Pressure (Water)60 psi partially open ball, 116 psi full openClose-Off Pressure200 psiCv4.64 Weight2 lb [0.9 kg]Leakage0%Servicingmaintenance freeFlow PatternFlow directionApplicationThis valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include unit ventilators, VAV box re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed to fit in compact areas where on/off, floating point and modulating control is required using 24 VAC.Suitable Actuators Non-SpringSpringB225HT464LRLFDimensions (Inches [mm])DEBAFCH2H1LRB, LRXABCDEFH1H28.6” [218]5.14” [131]6.89” [175]6.36” [162]1.3” [33]1.18” [30]0.5” [15]B225HT464, 1”, High Temperature CCVStainless Steel Ball and Stem800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 09/20/2016 - Subject to change. © Belimo Aircontrols (USA), Inc.Dimensions (Inches [mm])EFBADCLFABCDEF9.47” [241]5.14” [131]7.76” [197]6.84” [174]1.89” [48]B225HT464, 1”, High Temperature CCVStainless Steel Ball and Stem800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 09/20/2016 - Subject to change. © Belimo Aircontrols (USA), Inc.Technical Data2198Power Supply120 VAC ± 10%, 50/60 HzPower Consumption Running5.5 WPower Consumption Holding3.5 WTransformer Sizing7.5 VAElectrical Connection(2) 3ft [1m], 18 GA appliance cables with 1/2” conduit connectorsOverload Protectionelectronic throughout 0° to 95° rotationOperating Range Yon/offAngle of Rotation90°Direction of Rotation (Motor)reversible with built-in switchDirection of Rotation (Fail-Safe)reversible with CW/CCW mountingPosition Indicationvisual indicator, 0° to 95° (0° is full spring return position)Running Time (Motor)<40 to 75 secRunning Time (Fail-Safe)<25 sec @ -4°F to 122°F [-20°C to 50°C], < 60 sec @ -22°F [-30°C]Ambient Temperature Range-22°F to 122°F [-30°C to 50°C]Storage Temperature Range-40°F to 176°F [-40°C to 80°C]HousingNEMA 2, IP54Agency Listings†cULus acc. To UL 873 and CAN/CSA C22.2 No. 24-93Noise Level (Motor)<50 dB (A) Noise Level (Fail-Safe)<62 dB (A) Servicingmaintenance freeQuality StandardISO 9001Auxiliary Switch1 x SPDT, 3A resistive (0.5A inductive) @ 250 VAC, adjustable 0° to 95° (double insulated)†Rated Impulse Voltage 800V, Type of action 1.AA, Control Pollution Degree 3LF120-S US, Valve ActuatorOn/Off, Spring Return, 120 VAC, Auxiliary Switch800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 08/16/2017 - Subject to change. © Belimo Aircontrols (USA), Inc.Wiring DiagramsINSTALLATION NOTESAActuators with appliance cables are numbered.Provide overload protection and disconnect as required.Actuators may be connected in parallel if not mechanically linked. Power consumption and input impedance must be observed.44One built-in auxiliary switch (1x SPDT), for end position indication, interlock control, fan startup, etc.Apply only AC line voltage or only UL-Class 2 voltage to the terminals of auxiliary switches. Mixed or combined operation of line voltage/safety extra low voltage is not allowed.Meets cULus requirements without the need of an electrical ground connection.!WARNING! LIVE ELECTRICAL COMPONENTS!During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Wht (1) NeutralBlk (2) HotWht NBlk HLine Volts111AOn/Off S1S2S3NCNO0° to 95°144Auxiliary SwitchesLF120-S US, Valve ActuatorOn/Off, Spring Return, 120 VAC, Auxiliary Switch800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 08/16/2017 - Subject to change. © Belimo Aircontrols (USA), Inc.Next >