Technical Data 96726 Fluidchilled or hot water, up to 60% glycol, steam Flow characteristicmodified equal percentage Controllable flow range90° rotation Valve Size [mm]0.75” [20] Pipe connectionNPT female ends HousingBronze B584-C84400 Housing sealPTFE Ball316 stainless steel RetainerB16 Brass Stem316 stainless steel Stem sealRPTFE Spindle bearingRPTFE Lock nutstainless steel SeatRPTFE Body Pressure Rating600 psig WOG psi Maximum Inlet Pressure (Steam)35 psi [241 kPa] Max Differential Pressure (Steam)35 psi Close-off pressure ∆ps600 psi Maximum Velocity15 FPS Cv30 Weight1.32 lb [0.60 kg] Fluid Temp Range (water)-22...280°F [-30...138°C] Leakage rateANSI Class VI Flow/Mounting Details Application This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VAV Box re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed with MFT functionally which facilitates the use of various control input. Up to 35 psi steam 1/2” - 2” 600 PSIG WOG, Cold Non-Shock Federal Specification: WW-V-35C, Type II Composition: BZ Style: 3 Suitable Actuators Non-SpringSpring B219VSNMB(X), GRCB(X), GRB(X)NF Safety Notes WARNING: This product can expose you to lead which is known to the State of California to cause cancer and reproductive harm. For more information go to www.p65warnings.ca.gov B219VS Technical Data Sheet Bronze Body, Stainless Steel Ball and Stem 800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEAN Date created, 04/17/2020 - Subject to change. © Belimo Aircontrols (USA), Inc.Technical Data 317485 Power Supply100...240 VAC, ±20%, 50/60 Hz, DC, ±10% Power consumption in operation6 W Power consumption in rest position 2 W Transformer sizing11 VA (class 2 power source) Electrical Connection18 GA appliance cable, 3 ft [1 m], with 1/2” conduit connector Overload Protectionelectronic thoughout 0...90° rotation Input Impedance600 Ω Angle of rotation90°, adjustable with mechanical stop Direction of motion motorselectable with switch 0/1 Position indicationMechanically, 5...20 mm stroke Manual overrideunder cover Running Time (Motor)35 s, constant, independent of load Ambient humiditymax. 95% r.H., non-condensing Ambient temperature-22...122°F [-30...50°C] Storage temperature-40...176°F [-40...80°C] Degree of ProtectionIP66/67, NEMA 4X, UL Enclosure Type 4X Housing materialPolycarbonate Agency ListingcULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2014/30/EU and 2014/35/EU Noise level, motor45 dB(A) Servicingmaintenance-free Quality StandardISO 9001 Weight9.92 lb [4.5 kg] †Rated Impulse Voltage 2.5kV, Type of Action 1.AA, Control Pollution Degree 3. GRCX120-3 N4 Technical Data Sheet On/Off, Floating Point, Non-Spring Return, AC 100...240 V 800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEAN Date created, 02/12/2020 - Subject to change. © Belimo Aircontrols (USA), Inc.Wiring Diagrams INSTALLATION NOTES A Actuators with appliance cables are numbered. Provide overload protection and disconnect as required. Actuators may be connected in parallel. Power consumption and input impedance must be observed. Meets cULus requirements without the need of an electrical ground connection. ! WARNING! LIVE ELECTRICAL COMPONENTS! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Blu (1) Common Brn (2) Load Wht (3) Load N L Line Wht Volts Blk A 12 On/Off 100 to 240 VAC Blu (1) Common Brn (2) Load Wht (3) Load Wht N Blk L Line Volts A 1 2 Floating Point 100 to 240 VAC GRCX120-3 N4 Technical Data Sheet On/Off, Floating Point, Non-Spring Return, AC 100...240 V 800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEAN Date created, 02/12/2020 - Subject to change. © Belimo Aircontrols (USA), Inc.Next >