Technical Data2266Power Supply24 VAC, ±20%, 50/60 Hz, 24 VDC, ±10%Power Consumption Running3.5 WPower Consumption Holding1.3 WTransformer Sizing6 VA (class 2 power source)Electrical Connection18 GA plenum rated cable with 1/2” conduit connector protected NEMA 2 (IP54) 3ft [1m] 10ft [3m] and 16ft [5m]Overload Protectionelectronic thoughout 0° to 90° rotationOperating Range Y2 to 10 VDC, 4 to 20 mA w/ ZG-R01 (500 Ω, 1/4 W resistor), variable (VDC, floating point, on/off)Input Impedance100 k Ω for 2 to 10 VDC (0.1 mA), 500 Ω for 4 to 20 mA, 1500 Ω for PWM, floating point and On/OffFeedback Output U2 to 10 VDC, 0.5 mA max, VDC variableAngle of Rotation90°Direction of Rotation (Motor)reversible with built-in switchPosition Indicationintegrated into handleManual Overrideexternal push buttonRunning Time (Motor)150 secAmbient Temperature Range-22°F to 122°F [-30°C to 50°C]Storage Temperature Range-40°F to 176°F [-40°C to 80°C]HousingNEMA 2, IP42, UL Enclosure Type 2Agency Listings†cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2004/108/ECNoise Level (Motor)<45 dB (A) Servicingmaintenance freeQuality StandardISO 9001†Rated Impulse Voltage 800V, Type action 1, Control Pollution Degree 3.ARX24-MFTModulating, Non-Spring Return, 24 V, Multi-Function Technology®800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 11/30/2017 - Subject to change. © Belimo Aircontrols (USA), Inc.Wiring DiagramsINSTALLATION NOTESProvide overload protection and disconnect as required.Actuators may be connected in parallel. Power consumption and input impedance must be observed.Actuators may also be powered by 24 VDC.Only connect common to negative (-) leg of control circuits.A 500 Ω resistor (ZG-R01) converts the 4 to 20 mA control signal to 2 to 10 VDC.Control signal may be pulsed from either the Hot (Source) or Common (Sink) 24 VAC line.For triac sink the Common connection from the actuator must be connected to the Hot connection of the controller. Position feedback cannot be used with a triac sink controller; the actuator internal common reference is not compatible.IN4004 or IN4007 diode. (IN4007 supplied, Belimo part number 40155).Actuators with plenum cable do not have numbers; use color codes instead.Meets cULus requirements without the need of an electrical ground connection.!WARNING! LIVE ELECTRICAL COMPONENTS!During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Blk (1)Red (2)Pnk (4)Wht (3)Org (5)LineVoltsPositionFeedback VDC(+)(–)1318CommonHot +Y2 Input Y1 InputU Output 24 VAC Transformer2On/Off LineVolts(–)(+)Position Feedback VDC11810Blk (1)Red (2)Pnk (4)Wht (3)Org (5)CommonHot +Y2 Input Y1 InputU Output 24 VAC Transformer (AC Only)2Floating Point (–)(+)LineVoltsΩ500 Ω1/4 wattControl Signal VDC / mA135187Blk (1)Red (2)Pnk (4)Wht (3)Org (5)CommonHot +Y2 Input Y1 InputU Output 24 VAC Transformer2VDC/mA Control LineVolts (–) (+) PositionFeedback VDC1188Blk (1)Red (2)Pnk (4)Wht (3)Org (5)CommonHot +Y2 Input Y1 InputU Output 24 VAC Transformer (AC Only)2PWM ControlARX24-MFTModulating, Non-Spring Return, 24 V, Multi-Function Technology®800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 11/30/2017 - Subject to change. © Belimo Aircontrols (USA), Inc. Functions0%50%100%Control mode acc. to Y1MinMidMaxNormalabcOrg (5) 24 VAC Transformer (AC Only) U Output15Blk (1) CommonRed (2) + Hot Pnk (4) Wht (3) (–)(+)LineVoltsBCAVDC / mAControl Signal Y2 Input Y1 Input127182Override ControlARX24-MFTModulating, Non-Spring Return, 24 V, Multi-Function Technology®800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 11/30/2017 - Subject to change. © Belimo Aircontrols (USA), Inc.Next >