Technical Data2519Power Supply100...240 VAC, -15% / +10%, 50/60 HzPower Consumption Running4 WPower Consumption Holding1 WTransformer Sizing7.5 VA (class 2 power source)Electrical Connection18 GA applicance rated cable with 1/2” conduit connector protected NEMA 2 (IP54) 3ft [1m] 10ft [3m] and 16ft [5m]Overload Protectionelectronic thoughout 0° to 90° rotationOperating Range Y2 to 10 VDC, 4 to 20 mA w/ ZG-R01 (500 Ω, 1/4 W resistor)Input Impedance100 k Ω for 2 to 10 VDC (0.1 mA), 500 Ω for 4 to 20 mAFeedback Output U2 to 10 VDCAngle of Rotation90°Direction of Rotation (Motor)reversible with built-in switchPosition Indicationintegrated into handleManual Overrideexternal push buttonRunning Time (Motor)90 secAmbient Temperature Range-22°F to 122°F [-30°C to 50°C]Storage Temperature Range-40°F to 176°F [-40°C to 80°C]HousingNEMA 2, IP54Agency Listings†cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2004/108/EC and 2006/95/ECNoise Level (Motor)<45 dB (A) Servicingmaintenance freeQuality StandardISO 9001†Rated Impulse Voltage 4kV, Type of action 1, Control Pollution Degree 3.ARX120-SRModulating, Non-Spring Return, 100 to 240 VAC, for 2 to 10 VDC or 4 to 20 mA800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 11/30/2017 - Subject to change. © Belimo Aircontrols (USA), Inc.Wiring DiagramsINSTALLATION NOTESAActuators with appliance cables are numbered.Provide overload protection and disconnect as required.Actuators may be connected in parallel. Power consumption and input impedance must be observed.Only connect common to negative (-) leg of control circuits.A 500 Ω resistor (ZG-R01) converts the 4 to 20 mA control signal to 2 to 10 VDC.Meets cULus requirements without the need of an electrical ground connection.!WARNING! LIVE ELECTRICAL COMPONENTS!During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Wht N3 Y Input, 2 to 10 V2 LoadBlk LSG...24Control SignalVDC/mA2 to 10 VDCFeedback Signal2A171 Neutral1 Common5 U Output2 VCC52 to 10 VDC / 4 to 20 mA Control 100 to 240 VACARX120-SRModulating, Non-Spring Return, 100 to 240 VAC, for 2 to 10 VDC or 4 to 20 mA800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 11/30/2017 - Subject to change. © Belimo Aircontrols (USA), Inc.Next >