1®QUICK MOUNT VISUAL INSTRUCTION MANUALSGVL/G2/G3 Linkage with LV and SV Series Actuators4mm12!2!321AABBAABAAB121 2 436324575Nm4mm221811?For Stem Up A to AB @ Minimum Control SignalFor Stem Down A to AB @ Minimum Control SignalPush Adaption for 3 Seconds with PowerSTOPOptional Lock and Manual OverrideSignal Direction@ Minimum Control Signal71822-00001.B05/16 - Subject to change. © Belimo Aircontrols (USA), Inc.2®WIRING DIAGRAMSQUICK MOUNT VISUAL INSTRUCTION MANUALSGVL/G2/G3 Linkage with LV and SV Series ActuatorsBLKBlackNegroNoirPretoREDRedRojoRougeVermelhoWHTWhiteBlancoBlancBrancoPNKPinkRosadoRosaCor-de rosORGOrangeAnaranjadoOrangeAlaranjadoBLUBlueAzulBleuAzulBRNBrownMarronBrunMarromNon-Spring Return Actuator with -3 Non-Spring Return Actuator with -SR24 VAC TransformerBlk (1) CommonRed (2) +Wht (3) +LineVolts2318Blk (1) CommonRed (2) + Wht (3) +LineVolts24 VAC Transformer2318Blk (1) CommonRed (2) + HotWht (3) Y1 Input, 2 to 10 VOrg (5) U Output, 2 to 10 V(–)(+)LineVolts24 VAC TransformerControl SignalVDC/mA3187Ω500Ω1/4 WOn/OffFloating PointVDC / 4 to 20 mA100 to 240 VACBlu (1) CommonBrn (2) + Wht (3) +N L1H L2–LineHotA2Blk (1) CommonBrn (2) + Wht (3) +A2Line N L1Hot H L2100 to 240 VACSignalDirectionOn/OffFloating PointSelector SwitchComLineVoltsHotController24 VAC Transformer (AC only)–Blk (1) CommonRed (2) + HotWht (3) Y1 Input224 VAC Transformer (AC only)LineVoltsHotControllerCom–Blk (1) CommonRed (2) + HotWht (3) Y1 Input2Triac SinkTriac SourceNon-Spring Return Actuator with MFTBlk (1) CommonRed (2) Hot Wht (3) Y InputOrg (5) U Output LineVolts24 VAC Transformer2 to 10 VDCFeedback Signal(+)(–)318LineVolts (–) (+)24 VAC TransformerBlk (1) – CommonRed (2) + HotWht (3) Y1 InputOrg (5) U Output 2 to 10 VABABDirection of rotation switchABFeedback Signal 2 to 10 VDC2101818188912Notes:On/OffFloating PointBlk (1) CommonRed (2) + HotWht (3) Y1 Input, 2 to 10 VOrg (5) U Output, 2 to 10 V(–)(+)LineVolts24 VAC TransformerControl SignalVDC/mA3187Ω500Ω1/4 WFunctions0%50%100%Control mode acc. to YMinMidMaxNormalabc500Blk (1) CommonRed (2) + HotOrg (5)Wht (3) Y1 Input, 2 to 10 V(–)(+)LineVolts24 VAC Transformer (AC Only)BCA1/4 WVDC/mAControl Signal187ΩΩVDC / 4 to 20 mAOverride Control Min, Mid, Max PostionsMeets cULus requirements without the need of an electrical ground connectionAActuators with appliance cables are numbered.2Actuators may be connected in parallel. Power consumption and input impedance must be observed.3Actuators may also be powered by 24 VDC.5Only connect common to neg. (-) leg of control circuits.7A 500 resistor converts the 4 to 20 mA control signal to 2 to 10 VDC.8Control signal may be pulsed from either the Hot (Source) or Common (Sink) 24 VAC line.9Contact closures A & B also can be triacs. A & B should both be closed for the triac source and open for triac sink.10For triac sink the Common connection from the actuator must be connected to the Hot connection of the controller. Position feedback cannot be used with a triac sink controller. The actuator internal common reference is not compatible.1212IN4004 or IN4007 diode. (IN4007 supplied, Belimo Part number 40155)18Actuators with plenum rated cable do not have numbers on wires; use color codes instead.3®QUICK MOUNT VISUAL INSTRUCTION MANUALSGVL/G2/G3 Linkage with LVK and SVK Series ActuatorsAABBAABAAB154mm12!3!268M23421711Push Adaption for 3 Seconds with PowerSTOPOptional Manual Override5Nm4mm221?For Stem Up A to AB @ Minimum Control SignalFor Stem Down A to AB @ Minimum Control SignalSignal Direction@ Minimum Control Signal4®WIRING DIAGRAMSQUICK MOUNT VISUAL INSTRUCTION MANUALSGVL/G2/G3 Linkage with LVK and SVK Series ActuatorsBLKBlackNegroNoirPretoREDRedRojoRougeVermelhoWHTWhiteBlancoBlancBrancoPNKPinkRosadoRosaCor-de rosORGOrangeAnaranjadoOrangeAlaranjadoBLUBlueAzulBleuAzulBRNBrownMarronBrunMarromElectronic Fail-Safe Actuator with -3Electronic Fail-Safe Actuator with -SR24 VAC TransformerLineVolts–Blk (1) CommonRed (2) + HotWht (3) + Y1 InputPnk (4)2318Blk (1) Red (2)Wht (3) Pnk (4) Common Hot +Y1 Input Y2 Input 2LineVolts24 VAC Transformer8189Blk (1) CommonRed (2) + HotWht (3) Y1 Input, 2 to 10 VOrg (5) U Output, 2 to 10 V(–)(+)LineVolts24 VAC TransformerControl SignalVDC/mA3187Ω500Ω1/4 WOn/OffFloating PointVDC / 4 to 20 mABlu (1)Brn (2) +Wht (3) + Wht (4)100 to 240 VACN L1H L2LineHotA2ALine N L1Hot H L2100 to 240 VACBlu (1) Brn (2) + Wht (3) +Wht (4) + 250%SignalDirectionFailPostionOn/OffFloating PointSelector SwitchesComHotControllerLineVolts24 VAC TransformerBlk (1) CommonRed (2) HotWht (3) Y1 InputPnk (4) Y2 Input+51018ComHotControllerLineVolts24 VAC TransformerBlk (1) CommonRed (2) HotWht (3) Y1 InputPnk (4) Y2 Input+18Blk (1) CommonRed (2) HotWht (3) Y1 InputPnk (4) Y2 InputComHotControllerLineVolts24 VAC TransformerLineVolts24 VAC Transformer+1018Triac SinkTriac SourceTriac Sink with Separate TransformerElectronic Fail-Safe Actuator with MFTBlk (1) CommonRed (2) Hot Wht (3) Y InputOrg (5) U Output LineVolts24 VAC Transformer2 to 10 VDCFeedback Signal(+)(–)318LineVolts (–) (+)24 VAC TransformerBlk (1) – CommonRed (2) + HotWht (3) Y1 InputOrg (5) U Output 2 to 10 VABABDirection of rotation switchABFeedback Signal 2 to 10 VDC2101818188912Notes:On/OffFloating PointBlk (1) CommonRed (2) + HotWht (3) Y1 Input, 2 to 10 VOrg (5) U Output, 2 to 10 V(–)(+)LineVolts24 VAC TransformerControl SignalVDC/mA3187Ω500Ω1/4 WFunctions0%50%100%Control mode acc. to YMinMidMaxNormalabc500Blk (1) CommonRed (2) + HotOrg (5)Wht (3) Y1 Input, 2 to 10 V(–)(+)LineVolts24 VAC Transformer (AC Only)BCA1/4 WVDC/mAControl Signal187ΩΩVDC / 4 to 20 mAOverride Control Min, Mid, Max PostionsMeets cULus requirements without the need of an electrical ground connectionAActuators with appliance cables are numbered.2Actuators may be connected in parallel. Power consumption and input impedance must be observed.3Actuators may also be powered by 24 VDC.5Only connect common to neg. (-) leg of control circuits.7A 500 resistor converts the 4 to 20 mA control signal to 2 to 10 VDC.8Control signal may be pulsed from either the Hot (Source) or Common (Sink) 24 VAC line.9Contact closures A & B also can be triacs. A & B should both be closed for the triac source and open for triac sink.10For triac sink the Common connection from the actuator must be connected to the Hot connection of the controller. Position feedback cannot be used with a triac sink controller. The actuator internal common reference is not compatible.1212IN4004 or IN4007 diode. (IN4007 supplied, Belimo Part number 40155)18Actuators with plenum rated cable do not have numbers on wires; use color codes instead.Next >