1QUICK MOUNT VISUAL INSTRUCTION MANUALCQK... Actuatorswith ZoneTight Zone Valves71775-00001.G12211. PIQCV12211. QCVSizeValve ModelV'max End Stop PositionsV'nom123-344+55+6NNo end stop1/2"Z2050Q(S)-F0.1 0.20.40.60.81.21.41/2"Z2050Q(S)-J0.50.71.21.72.434.85.93/4"Z2075Q(S)-K0.51.01.52.33.34.66.69.8Runtime (seconds)3037414349515558626875QCV/PIQCVActuator RemovalValve Model (1/2")Clip Position for Flow Adjustment (GPM)11+2-22+3-33+4-44+5-55+6-66+N-NNo ClipZ2050QPT-B0.10.20.30.40.50.60.70.80.9Z2050QPT-D0.20.30.40.50.60.70.80.91.01.21.31.51.61.82.0Z2050QPT-F0.60.70.80.91.01.31.51.71.92.22.52.83.13.33.64.3Valve Model 3/4"Z2075QPT-G1.61.82.12.42.73.03.33.74.04.44.95.35.86.36.77.27.79.0Runtime3033353739414345474951535558606264666875Subject to change. © Belimo Aircontrols (USA), Inc.2WIRING DIAGRAMSBLKBlackNegroNoirPretoREDRedRojoRougeVermelhoWHTWhiteBlancoBlancBrancoCQK..24V, CQKB24 (-LL) (-RR), CQKB24-S (-LL) (-RR), CQKB24-SR (-LL) (-RR) (-LR) (-RL)Blk CommonRed Hot + Line VoltsA2318FunctionsA0%100%0%Fail PositionCloseBlk CommonRed Hot + Line VoltsA2318FunctionsA0%100%100%Fail PositionOpenBlk CommonRed + HotLine VoltsA2318FunctionsA100%0%0%Fail PositionCloseOn/Off, CQKB24-RROn/Off, CQKB24-LLOn/Off, CQKB24-S-RRBlk CommonRed + HotLine VoltsAFunctionsA0%100%2318100%Fail PositionOpenLine VoltsControl SignalVDC/mABlk CommonRed + HotWht Y1 Input, 2 to 10V500231857100%Fail Position2 VDC CloseOpen10 VDC OpenCloseOpenLine VoltsControl SignalVDC/mABlk CommonRed + HotWht Y1 Input, 2 to 10V5002318570%Fail Position2 VDC Open10 VDCCloseCloseOn/Off, CQKB24-S-LLProportional, CQKB24-SR-LLProportional, CQKB24-SR-LRLine VoltsControl SignalVDC/mABlk CommonRed + HotWht Y1 Input, 2 to 10V500231857100%Fail Position2 VDC CloseClose10 VDC OpenOpenOpenLine VoltsControl SignalVDC/mABlk CommonRed + HotWht Y1 Input, 2 to 10V5002318570%Fail Position2 VDC CloseClose10 VDC OpenOpenCloseNotes:Proportional, CQKB24-SR-RLProportional, CQKB24-SR-RRMeets cULus requirements without the need of an electrical ground connectionApply only AC line voltage or only UL-Class 2 voltage to the terminals of auxiliary switches. Mixed or combined operation of line voltage/safety extra low voltage is not allowed.1Provide overload protection and disconnect as required.2Actuators may be connected in parallel. Power consumption and input impedance must be observed.3Actuators may also be powered by 24 VDC.5Only connect common to neg. (-) leg of control circuits.7A 500 Ω (ZG-R01) converts the 4 to 20 mA control signal to 2 to 10 VDC.18Actuators with plenum rated cable do not have numbers on wires; use color codes instead.100One built-in auxiliary switch, 1x SPST 1A @ 24 VAC/DC (resistive load), for end position indication, interlock control, fan startup, etc.S1S2NO1100S1S2NO1100kg>122°FPIQCV!kgQCVNext >