Sensor Datasheet22UTH-530Xwww.belimo.com22UTH-530X • en-us • 2018-01-08 • Subject to change1 / 4Outdoor Humidity, Temperature Sensor±2% accurate humidity and temperature sensor for outdoor applications. Temperature is available with dual active 4 to 20 mA outputs or passive only for temperature. NEMA 4X /IP65 rated enclosure standard. Field selectable output for RH, absolute humidity, dew point or enthalpy. Type OverviewTypeOutput Signal Active TemperatureOutput Signal Active Humidity22UTH-530X4...20 mA4...20 mATechnical DataElectrical DataPower Supply DC15...24 V, ±10%, 0.5 WElectrical Connectionremovable spring loaded terminal block max. 11 GA [2.5 mm²]Cable Entrycable gland PG11 Ø6 to 10 mm, with strain relief Ø6 to 8 mm, 1/2" conduit adapter includedFunctional DataMultirange4 fields selectableOutput Signal Active Notecurrent output: max. 500 Ω loadMediaairMeasuring DataMeasured Valuestemperaturerelative humiditydew pointenthalpyabsolute humidityMeasuring Range Humidity0 to 100% RH non-condensingMeasuring range temperatureActive sensor: range selectableAttention: max. measuring temperature is restricted by max. medium temperature (see Safety data)Settingrange [°C]range [°F]FactorysettingExport Media AP WebS0-40°C to 60°C-40°F to 160°FS10°C to 50°C40°F to 140°FS2-15°C to 35°C0°F to 100°FS3-20°C to 80°C0°F to 200°FMeasuring Range Absolute Humidityadjustable at the transducer:0 to 50 g/m³ (default setting)0 to 80 g/m³Measuring Range Enthalpy0 to 85 kJ/kgMeasuring Range Dew Pointadjustable at the transducer:40°F to 140°F [0°C to 50°C] (default setting)0°F to 200°F [-20°C to 80°C]Accuracy Humidity±2% between 10 to 90% RH @ 70°F [21°C]Accuracy temperature active±0.9°F @ 77°F [±0.5°C @ 25°C]Operating Condition Air Flowmax. 40 ft/s [12 m/s]Sensor Datasheet22UTH-530Xwww.belimo.com22UTH-530X • en-us • 2018-01-08 • Subject to change2 / 4MaterialsCable GlandPA6, blackHousingcover: lexan, Belimo orange NCS S0580-Y6ORbase: lexan, Belimo orange NCS S0580-Y6ORseal: 0467 NBR70, blackSafety DataAmbient Humidity85% RH non-condensingAmbient Temperature-30°F to 120°F [-35°C to 50°C]Medium Temperature-30°F to 120°F [-35°C to 50°C]Operating Condition Air Flowmax. 40 ft/s [12 m/s]Protection Class IEC/ENIII safety extra-low voltage (selv)Protection Class ULUL Class 2 SupplyEU ConformityCE MarkingCertification IEC/ENIEC/EN 60730-1 and IEC/EN 60730-2-13Certification ULcULus acc. to UL60730-1A/-2-9/-2-13, CAN/CSA E60730-1:02/-2-9, CE acc. to 2004/108/EC and 2006/95/EC, NEMA 4X, IP65, UL Enclosure Type 4XDegree of Protection IEC/ENIP65Degree of Protection NEMA/ ULNEMA 4XQuality StandardISO 9001Weight0.24 lbsAccessoriesdowelscrewscable gland nut conduit 1/2" NPTScope of DeliverySensor Datasheet22UTH-530Xwww.belimo.com22UTH-530X • en-us • 2018-01-08 • Subject to change3 / 4Wiring DiagramrHRelative humidityabsHAbsolute humidityEntHEnthalpyTPkt/DewDew point the adjustment of the measuring ranges is made by changing the bonding jumpersthe output value in the new measuring range is available after 2 secondsSettingrange [°C]range [°F]FactorysettingExport Media AP WebS0-40°C to 60°C-40°F to 160°FS10°C to 50°C40°F to 140°FS2-15°C to 35°C0°F to 100°FS3-20°C to 80°C0°F to 200°FSensor Datasheet22UTH-530Xwww.belimo.com22UTH-530X • en-us • 2018-01-08 • Subject to change4 / 4DimensionsNext >