Sensor Datasheet22UTH-51..www.belimo.com22UTH-51.. • en-us • 2018-01-08 • Subject to change1 / 5Outdoor Humidity, Temperature Sensor±2% accurate humidity and temperature sensor for outdoor applications. Temperature is available with dual active 4 to 20 mA outputs or passive only for temperature. NEMA 4X /IP65 rated enclosure standard. Field selectable output for RH, absolute humidity, dew point or enthalpy. Type OverviewTypeOutput Signal Active TemperatureOutput Signal Active HumidityOutput Signal Passive Temperature22UTH-51DC 0...5 V, DC 0...10 VDC 0...5 V, DC 0...10 V-22UTH-510B-DC 0...5 V, DC 0...10 VPT100022UTH-510E-DC 0...5 V, DC 0...10 VNi1000 (JCI)22UTH-510L-DC 0...5 V, DC 0...10 VNTC10k222UTH-510M-DC 0...5 V, DC 0...10 VNTC10k322UTH-510Q-DC 0...5 V, DC 0...10 VNTC20kTechnical DataElectrical DataPower Supply DC15...24 V, ±10%, 0.3 WPower Supply AC24 V, ±10%, 0.5 VACable Entrycable gland PG11 Ø6 to 10 mm, with strain relief Ø6 to 8 mm, 1/2" conduit adapter includedFunctional DataSensor Technologypolymer capacitive sensor with stainless steel wire meshOutput Signal Passive TemperaturePT1000Ni1000 (JCI)NTC10k2NTC10k3NTC20kOutput Signal Active Noteoutput DC 0 to 5/10 V with jumper adjustablevoltage output: min. 10 kΩ loadMediaairSensor Datasheet22UTH-51..www.belimo.com22UTH-51.. • en-us • 2018-01-08 • Subject to change2 / 5Measuring DataMeasured Valuestemperaturerelative humiditydew pointenthalpyabsolute humidityMeasuring Range Humidity0 to 100% RH non-condensingMeasuring range temperaturepassive sensor: -30°F to 120°F [-35°C to 50°C]Active sensor: range selectableAttention: max. measuring temperature is restricted by max. medium temperature (see Safety data)Settingrange [°C]range [°F]FactorysettingExport Media AP WebS0-40°C to 60°C-40°F to 160°FS10°C to 50°C40°F to 140°FS2-15°C to 35°C0°F to 100°FS3-20°C to 80°C0°F to 200°FMeasuring Range Absolute Humidityadjustable at the transducer:0 to 50 g/m³ (default setting)0 to 80 g/m³Measuring Range Enthalpy0 to 85 kJ/kgMeasuring Range Dew Pointadjustable at the transducer:40°F to 140°F [0°C to 50°C] (default setting)0°F to 200°F [-20°C to 80°C]Accuracy Humidity±2% between 10 to 90% RH @ 70°F [21°C]Accuracy temperature active±0.9°F @ 77°F [±0.5°C @ 25°C]Accuracy temperature passivepassive sensors depending on used typeNi.. = ±0.7°F @ 32°F [±0.4°C @ 0°C]NTC.. = ±0.3°F @ 77°F [±0.2°C @ 25°C]MaterialsCable GlandPA6, blackHousingcover: lexan, graybase: lexan, grayseal: 0467 NBR70, blackSafety DataAmbient Temperature-30°F to 120°F [-35°C to 50°C]Medium Temperature-30°F to 120°F [-35°C to 50°C]Protection Class IEC/ENIII safety extra-low voltage (selv)Protection Class ULUL Class 2 SupplyCertification IEC/ENIEC/EN 60730-1 and IEC/EN 60730-2-13Certification ULcULus acc. to UL60730-1A/-2-9/-2-13, CAN/CSA E60730-1:02/-2-9, CE acc. to 2004/108/EC and 2006/95/EC, NEMA 4X, IP65, UL Enclosure Type 4XDegree of Protection IEC/ENIP65Degree of Protection NEMA/ ULNEMA 4XQuality StandardISO 9001Weight0.21 lbsSensor Datasheet22UTH-51..www.belimo.com22UTH-51.. • en-us • 2018-01-08 • Subject to change3 / 5Safety NotesThe installation and assembly of electrical equipment should only be performed by authorized personnel.The product should only be used for the intended application. Unauthorized modifications are prohibited! The product must not be used in relation with any equipment that in case of a failure may threaten, directly or indirectly, human health or life or result in danger to human beings, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating equipment.Please comply with • Local laws, health & safety regulations, technical standards and regulations • Condition of the device at the time of installation, to ensure safe installation • This data sheet and installation manualRemarksRefrain from touching the sensitive humidity sensor/element. Touching the sensitive surface will void warranty.For standard environmental conditions the manufacturing accuracy specified in the datasheet will be covered by the calibration warranty for two years. When exposed to harsh environmental conditions such as; high ambient temperature and/or high levels of humidity or presence of aggressive gases (i.e. chlorine, ozone, ammonia) the sensor element may be affected and readings may be outside specified accuracy. Replacement of deteriorated humidity sensor due to harsh environmental conditions are not subject of the general warranty.Accessoriesmounting platedowelscrewsRain covercable gland nut conduit 1/2" NPTApplication Notice for Humidity SensorsScope of DeliverySensor Datasheet22UTH-51..www.belimo.com22UTH-51.. • en-us • 2018-01-08 • Subject to change4 / 5Wiring DiagramrHRelative humidityabsHAbsolute humidityEntHEnthalpyTPkt/DewDew point the adjustment of the measuring ranges is made by changing the bonding jumpersthe output value in the new measuring range is available after 2 secondsSettingrange [°C]range [°F]FactorysettingExport Media AP WebS0-40°C to 60°C-40°F to 160°FS10°C to 50°C40°F to 140°FS2-15°C to 35°C0°F to 100°FS3-20°C to 80°C0°F to 200°FSensor Datasheet22UTH-51..www.belimo.com22UTH-51.. • en-us • 2018-01-08 • Subject to change5 / 5DimensionsNext >