D18 Building Automation Products, Inc. • 750 North Royal Avenue, Gays Mills, WI 54631 USA Tel: +1-608-735-4800 • Fax: +1-608-735-4804 • Email: sales@bapihvac.com • Web: www.bapihvac.com Zone Pressure Sensors Burst Pressure: 40” WC (10 kPa) for all pressure ranges Medium: Air, non-combustible and non-aggressive gases Operating Temperature: -4° to +185°F (-20 to +85°C) Storage Temperature: -40°F to +185°F (-40 to +85°C) Accuracy: Deviation: ≤±15%, min. ±0.04” WC (±10 Pa) • Drift: ≤±15% Diaphragm Material: Silicone, tempered at 392°F (200°C), free of gas emissions Pressure Connections: 2 plastic pipe connection pieces, external dia. 0.24” (6mm) Marked “+” to higher pressure, marked “-” to lower pressure Body and Cover Material: UV-resistant plastic Mechanical Working Life: Over 1,000,000 switching operations Electrical Rating: 0.4A Inductive, 250 VAC • 1.5A Resistive, 250 VAC 0.8A Inductive, 125 VAC • 3.0A Resistive, 125 VAC 0.4A, 30VDC • 0.1A, 24 VDC Electrical connections: 1/4” Spade Plug (AMP flat plug), 0.25” x 0.03” (6.3 x 0.8mm) in accordance with DIN 46244 or push-on screw terminals included Protection Category: IP54 or IP65 Cable Conduit - M20 threads for 0.25” to 0.375” OD cable (6.5 to 9.5mm) CE Conformity: Low Voltage Directive 2014/35/EU; RoHS Directive 2011/65/EU Beck Adjustable Pressure Switch Features & Options Specifications Beck Adjustable Pressure Switch Rev. 09/15/22 Two static pressure probes and two meters of pressure tubing are available as an accessory. Total Probes and Tubing ●Designed for Monitoring Overpressure, Vacuum and Differential Pressure of Air or Other Non-Combustible, Non-Aggressive Gases ●Ideal for Air Filter and Fan Status Monitoring, Industrial Cooling-Air Circuit Monitoring, Duct Air Flow Monitoring, Air Flow Proving for Heater Control and Frost Prevention Circuits ●Field-Adjustable Dial to Select Any Trip Value Within Each Pressure RangeD19 Building Automation Products, Inc. • 750 North Royal Avenue, Gays Mills, WI 54631 USA Tel: +1-608-735-4800 • Fax: +1-608-735-4804 • Email: sales@bapihvac.com • Web: www.bapihvac.com Zone Pressure Sensors Ordering Information Gray shaded items follow the Buy and Resale Multiplier. Beck Adjustable Pressure Switch PartPressureAccuracy/ NumberRangeRepeatability Encl. Rating BA/APSW1...............0.08 to 1.2” WC / 20 to 300 Pa ......±5% / min. ±0.02” WC (±5 Pa) ....IP54 BA/APSW2...............0.2 to 2” WC / 50 to 500 Pa ...........±2.5% / min. ±0.02” WC (±5 Pa) ..IP54 BA/APSW3...............0.8 to 4” WC / 200 to 1,000 Pa ......±1% / min. ±0.02” WC (±5 Pa) .....IP54 BA/APSW4...............0.12 to 1.6” WC / 30 to 400 Pa ......±5% / min. ±0.02” WC (±5 Pa) ....IP54 BA/APSW5...............2 to 10” WC / 500 to 2,500 Pa.......±1% ..............................................IP54 BA/APSW6...............4 to 20” WC / 1,000 to 5,000 Pa....±1% ..............................................IP54 BA/APSW1-65.........0.08 to 1.2” WC / 20 to 300 Pa ......±5% / min. ±0.02” WC (±5 Pa) ....IP65 BA/APSW2-65.........0.2 to 2” WC / 50 to 500 Pa ...........±2.5% / min. ±0.02” WC (±5 Pa) ..IP65 BA/APSW3-65.........0.8 to 4” WC / 200 to 1,000 Pa ......±1% / min. ±0.02” WC (±5 Pa) .....IP65 BA/APSW4-65.........0.12 to 1.6” WC / 30 to 400 Pa ......±5% / min. ±0.02” WC (±5 Pa) ....IP65 BA/APSW5-65.........2 to 10” WC / 500 to 2,500 Pa.......±1% ..............................................IP65 BA/APSW6-65.........4 to 20” WC / 1,000 to 5,000 Pa....±1% ..............................................IP65 BA/APSW-ACC........2 Total Pressure Tubes and 2 Meters of Pressure TubingNext >