+8.5 to 32 VDC (Reverse Polarity Protected) | 25 mA minimum250 Ohm Load: +13.5 to 32 VDC | 500 Ohm Load: +18.5 to 32 VDC “-LCD” Loop Powered: Add +7 VDC to 250/500 Ohm Load Supply Voltage above (Terminal Voltage - 8.5 V) | 0.020 A Current: 4-20 mA (2-Wire Loop Powered) | Voltage: 1-5 VDC or 2-10 VDC (3-Wires)Temp. Spans < 500ºF (260ºC): +/- 0.2% Temp. Spans < 100ºF (38ºC): +/- 0.04%/ºF | Temp. Spans > 100ºF (38ºC): +/- 0.02%3 Point NIST: 20%, 50% & 80% of span | 5 Point NIST: 0%, 20%, 50%, 80% & 100% of span10 Minutes | +/- 0.1% Minimum Temp. Span: 50ºF (28ºC) | Maximum Temp. Span: 200ºF (93ºC) Screw Terminal Blocks | 16 AWG (1.31 mm) to 26 AWG (0.129 mm)0.37 ft-lb (0.5 N-3m ) nominalDry Contact “N/O” Contact | Minimum: 10 uA @ 1 VDC | Maximum: 50 mA @ 24 VDC +/- 10% | 4-20 mA: 4 mA (Far Left) / 20 mA Far Right (DA- Direct Acting (Default) 20 mA (Far Left / 4 mA Far Right (RA- Reverse Acting (Optional)Platinum RTD | PTC (Positive Temperature Coecient) | OneTwo | A/TTM100-R/R2: Brown/Brown | A/TTM1K-R/R2: Black/BlackA/TT100/TTM100-R/R2: 100 Ohms | A/TT1K/TTM1K-R/R2: 1000 Ohms +/- 0.06% Class A | (Tolerance Formula: +/- ºC = (0.15ºC + (0.002 * |t|)) where |t| is the absolute value of temperature above or below 0ºC in ºCDIN EN 60751 (IEC 751) | 3850 ppm / ºC+/- 0.03% after 1000 Hours @ 300ºC (572ºF)4 to 20 mA Only (2-wire Loop Powered) +/- 1.0% of Calibrated Temperature Span or +/- Whichever is GreaterºF (Fahrenheit) or ºC (Celsius) | 3 ½ Digits (-199.9 to 199.9) 50,000 Hours Minimum35 to 122ºF (1.5 to 50ºC)Non-LCD: -40 to 65ºC (-40 to 149ºF), LCD Display: -10 to 65ºC (14 to 149ºF)5 to 90% RH, non-condensing“-R2” Enclosure: ABS Plastic, White, UL94-HB“-R” Enclosure: ABS Plastic, Beige , UL94-HBNeoprene/EPDM/SBR Polymer | UL94-HBF; FMVSS-302; MIL-R-6130C4.50” (114.3 mm) x 2.78” (70.6 mm) x 1.00” (25.4 mm)“-R/RS/RO” Series: 0.17 lbs. (0.375 kg) | “-RSO” Series: 0.21 lbs. (0.46 kg)“-R2/R2S/R2O” Series: 0.19 lbs. (0.42 kg) | “-R2SO” Series: 0.23 lbs. (0.51kg)All LCD Display Units: 0.174 lbs. (0.079 kg)RoHS2, WEEEAutomation Components, Inc.TEMPERATURE | TRANSMITTERS | ROOMPRODUCT SPECIFICATIONSTEMPERATURE | ## Call: 1-888-967-5224 | Web: www.workaci.com Transmitter Supply Voltage | Supply Current:Maximum Load Resistance:Output Signals:Calibrated Transmitter Accuracy | Linearity: Temperature Drift:TTM100/TTM1K Certication Points:Warm Up Time | Warm Up Drift:Calibrated Temperature Spans:Connections | Wire Size:Terminal Block Torque Rating:Override Contact Type | Contact Ratings:Set Point Accuracy:Sensor Type | Sensor Curve | Sensing Points:Number Wires | Wire Colors (TTM Series only):Nominal Sensor Output @ 0°C (32°F):RTD Tolerance Class | Sensor Accuracy:Din Standard | Temperature Coecient:Sensor Stability:LCD Display Input Signal:LCD Display Accuracy:LCD Display Descriptor | Resolution:LCD Display Life Expectancy:Operating Temperature Range:Storage Temperature Range:Operating Humidity Range:Enclosure Specications (Material Type, ColorUL Flammability Rating):Foam Pad Material | Flammability Rating (TTM Only):Product Dimensions:Product Weight:Agency Approvals:Note: Transmitter’s calibrated at 71ºF (22ºC) nominal | Note: Temperature Drift is referenced to 71ºF nominal calibration temperature | Note: Temperature spans may go outside of the operating temperature range but the unit must be used within the operating temperature limitRR-LCDR2ROOMWall Mount Enclosures, TransmitterThe ACI Transmitter Room Series features a two-wire, 4 to 20 mA loop powered output with optional 3-Wire voltage output signals available. All transmitters include Zero and Span adjustments for eld calibration and are calibrated using NIST Certied Calibration equipment. ACI recommends the use of an 18 to 22 AWG shielded cable for all temperature transmitter installations to reduce the chances of noise being introduced onto the signal lines. The room transmitters are designed to be mounted over a standard single gang junction box or hole in the wall and includes a foam pad to reduce the eects of self-heating from the transmitter and thermal drafts from within the wall. For best accuracy, ACI recommends the use of the A/TTM Series Matched transmitters with 3 or 5 Point NIST Calibration Certicate, since they include a second calibration step in which the RTD and transmitter are calibrated together as a system. Optional Set Point, Override and Loop Powered LCD Display. Applications: Space Temperature Sensing, Oce Buildings, Schools, Gyms, Manufacturing Plants, Pharmaceutical, Hospitals, Data Centers The ACI Transmitter Room transmitters are covered by ACI's Five (5) Year Limited Warranty. The warranty can be found in the front of ACI's Sensors & Transmitters catalog, as well as on ACI's website, www.workaci.com. Automation Components, Inc.TEMPERATURE | TRANSMITTERS | ROOMTEMPERATURE | ## Call: 1-888-967-5224 | Web: www.workaci.com DIMENSIONAL DRAWING2.75” (69.85mm)2.75” (69.85mm)4.50”(114.30mm)4.50”(114.30mm)1.12” (28.55mm)1.12” (28.55mm)RR2RRR2R2Front ViewRight ViewTop ViewTT100 = 100 Ohm Platinum RTD | TT1K = 1K Ohm Platinum RTDA/R = Room | RO = Room with Override | RS = Room with Set PointRSO = Room with Set Point and Override | R2 = Room | R2O = Room with OverrideR2S = Room with Set Point | R2SO = Room with Set Point and OverrideCUSTOM ORDERING | STANDARD ACCURACYA. Sensor Series No Selection RequiredB. Model Series Select One (1)C. Conguration Select One (1)4-20 mA1. Potentiometer Select One (1)+ to - | Blue | Red | Cool | Warm | Cooler | Warmer | 10 to 30C | 18 to 28C | 55 to 85F2. Setpoint Indication Select One (1)---- = No LCD Display | LCD = With LCD DisplayE. LCD Display Select One (1)1 = 1 to 5 VDC | 2 = 2 to 10 VDC | 4 = 4 to 20 mAD. Output Signal Select One (1)1 = 1 to 5 VDC | 2 = 2 to 10 VDC | 4 = 4 to 20 mAD. Output Signal Select One (1)Setpoint Conguration Options Select Options below if RS, RSO, R2S or R2SO was selected as a Conguration (C).MODEL #A/1.F.10 to 30C2.Model # Example:R2SOC.4LCDD.A/A.TT100B.E.TTM100 = Matched 100 Platinum RTD | TTM1K = Matched 1K Platinum RTD*A/R2 = Room | R = Room CUSTOM ORDERING | HIGHER ACCURACYA. Sensor Series No Selection RequiredB. Model Series Select One (1)C. Conguration Select One (1)MODEL #A/Specify Span in ºF or ºC (Best Accuracy in 100ºF Increments)F. Calibrated SpanSpecify Span in ºF or ºC (Best Accuracy in 100ºF Increments)E. Calibrated SpanNote*: Best transmitter accuracy with spans in 100ºF Increments (ie. 0 to 100ºF or 1.5 to 40ºC5 PointF.Model # Example:RC.4D.A/A.TTM1KB.0 to 100ºFE.4-20 mA40 to 90ºFNote* = Must specify a 3 or 5 Point NIST Certicate with the TTM1K Transmitter aboveACCESSORIES ORDERINGModel #A/MOUNTING PLATE BEIGE RA/MOUNTING PLATE WHITE RA/MOUNTING PLATE WHITE R2LOCKING COVERA/ROOM-FOAM-PADItem #106821143369143369107370125690DescriptionWall Mounting Back Plate, Plastic, Beige (”R“)Wall Mounting Back Plate, Plastic, White (”R”)Wall Mounting Back Plate, Plastic, White (”R2”)Clear Thermostat Guard, Locking Cover, Low Prole 1/8” Foam Insulation Pad with Adhesive (3” x 2”, Black)-OR-Model # Example:106821A/MOUNTING PLATE BEIGE RNext >