Automation Components, Inc.ACCESSORIES | POWER SUPPLY | PS24ACCESSORIES | ## Call: 1-888-967-5224 | Web: www.workaci.com PS24Adjustable External Power SupplyThe PS24 Series low voltage power supplies will accept a 24 VAC input voltage from a Class 2 transformer and convert it into an adjustable 1.5 to 26 VDC regulated output voltage. The PS24 is able to be congured in either Half or Full Wave mode by using the integral jumper shunt selection switches. An onboard potentiometer is available to allow for eld adjustment of the 24 VDC factory set voltage to any voltage from 1.5 to 26 VDC. The standard unit is shipped in a standard snap track mounting conguration to allow for easy mounting inside of your electrical panel or piece of equipment.In applications where a Pilot Duty or remote relay is required, the A/DO008 transorb can be placed across the coil of the relay to snub electrical spikes when the relays are de-energized. An external transorb may not be required if the relay and PS24 power supply is mounted within the same control panel.Applications: DC Power Supply, Transducer Supply, Test Bench Supply, Analog Signal Simulator, DC Power Regulation from Control TransformerThe ACI PS24 is covered by ACI's Two (2) Year Limited Warranty. The warranty can be found in the front of ACI's Sensors & Transmitters catalog, as well as on ACI's website, www.workaci.com.PRODUCT SPECIFICATIONSInput Voltage: VA Requirements:Rectication:Output Voltage:Output Current:Overload Protection:Ground Loop Protection:Status Indication:Operating Temperature Range:Operating Humidity Range:Storage Temperature Range:Storage Humidity Range:Connections | Wire Size:Terminal Block Torque Rating:Snap Track Material | Flammability Rating:Product Dimensions (L x W x H):Product Weight:Agency Approvals:22 to 26 VAC, 50/60 Hz (Class 2 Transformer w/ 24 VAC Secondary) or 30 to 36 VDC 1.5 VA minimum (No Load); Additional VA required must be determined by load sizeHalf-Wave (Default) or Full Wave (Jumper Selectable)Factory set at 24 VDC; Adjustable from +1.5 to 26 VDCSee Figure #1 graphs for Output Current vs Ambient Operating Temperature Internal Current Limiting Thermal ProtectionFused, 1.25A/250 VAC, 5 x 20 mm, fast acting (Littlefuse 02171.25 MXP or equivalent)Red LED Indicates power on status32 to 158ºF (0 to 70ºC)5 to 95%, non-condensing50 to 95ºF (10 to 35ºC)30 to 60%Screw Terminal Blocks | 14 (1.31 mm) to 22 AWG (0.129 mm)4 lb-in (0.5 Nm) maximumPolyvinyl Chloride (PVC) | UL94 V-03.10” (78.8 mm) x 2.88” (73.2 mm) x 2.05” (52.1 mm)0.14 lbs. (0.064 kg)CE, RoHS2, WEEEAutomation Components, Inc.ACCESSORIES | POWER SUPPLY | PS24ACCESSORIES | ## Call: 1-888-967-5224 | Web: www.workaci.com DIMENSIONAL DRAWINGFront ViewSide ViewsSTANDARD ORDERINGModel #A/PS24-24V-SItem #144322Description24VDC Power Supply_Snap Track -OR-Model # Example:144322A/PS24-24V-SACCESSORIES ORDERINGModel #A/DO008Item #142583DescriptionTransient Voltage Suppressor, Bi-directional, 56 VAC/DC, 1500W-OR-Model # Example:142583A/DO008FuseOutput Selection JumpersPCB BoardSnap TrackV-OUT AdjustmentPower Indicator (LED)3.10”(78.8mm)2.88”(73.2mm)0.70”(17.78mm)2.05”(52.07mm)FIGURE 1Ambient Air Temperature | 77ºF (25ºC)Ambient Air Temperature | 122ºF (50ºC)Volts (DC)Volts (DC)50.00.20.40.60.81.01012151820242750.00.20.40.60.81.010121518202427MAX0.6050.5120.275MAXMIN0.325MINNote: The output current was tested at the ambient temperature and voltages provided in Figure 1Next >