— TECHNICAL DATA SHEET DS0122US rev 2 INTEGRA™ IT-8000 (North America) ©ABB 2021 All Rights Reserved. Subject to change without notice WWW.CYLON.COM page 1 of 6 DS0122US rev 2 DESCRIPTION Part of the INTEGRA™ family, the IT-8000 is an embedded Internet of Things (IoT), BTL-listed BACnet® Building Controller (B-BC) that connects to Cylon’s BACnet field controllers. The IT-8000 is also capable of connection to and network management of a variety of diverse devices and subsystems using various protocols including, but not limited to, Modbus™ and LonWorks™. When connected to an Ethernet or wireless LAN, the IT-8000 uses Internet connectivity and web-serving capability to provide integrated control, supervision, network management, scheduling, data logging, alarming, and rich graphical displays through a standard Web browser. APPLICATION With simple configuration, tool-less installation, enhanced integration and high-powered performance, the INTEGRA™ IT-8000 controller provides ultimate flexibility in connecting and controlling buildings worldwide. ▪ Remote connectivity allows control, monitoring, and management of field controllers ▪ Scalable hardware and software make it suitable for installation in small building to large campus applications ▪ The INTEGRA-Supervisor software can connect multiple IT-8000 controllers and their data to provide aggregated information, such as; archiving, master scheduling, real-time data, history, and alarms, to create a single, unified application. The licensing model for the INTEGRA™ IT-8000 controller is scalable and features standard drivers along with optional I/O and field bus expansion modules for ultimate flexibility and expandability. The INTEGRA™ IT-8000 controller operates with Niagara Framework® for optimum performance. TI AM3352: 1000MHz ARM® Cortex™-A8 1GB DDR3 SDRAM and 4GB flash storage using a removable micro-SD card Wi-Fi Client or Wireless Access Point • IEEE802.11n HT20 @ 2.4GHz • IEEE802.11n IEEE802.11n HT20/HT40 @ 5GHz • Configurable radio (Off, WAP, or Client) WPAPSK / WPA2PSK Ports and Connections • Two 10/100MB Ethernet ports • Two on-board isolated RS-485 ports for connecting BACnet MS/TP and Modbus RTU devices • One USB Type A Connector supports stations back-up and restore Secure boot, Battery-less, Real time clock Expansion I/O Modules • IT8-EIO-16 (8 UI, 4 DO-R, 4 AO) • IT8-EIO-34 (16UI, 10 DO-R, 8AO) Expandable Option Modules • IT8-NPB-LON – LonWorks LON FTT10A module • IT8-NPB-2X-485 – Dual port RS-485 module • IT8-NPB-232 – Single port RS-232 module INTEGRA-ProPack Service Cylon Service for quick database import that automatically creates BACnet network, devices and points without the need for discovery ©ABB 2021 All Rights Reserved. Subject to change without notice WWW.CYLON.COM page 2 of 6 DS0122US rev 2 INTEGRA-ProPack | IMPORT OF NETWORK DATA FROM CXpro ᴴᴰ TO AUTOMATICALLY CREATE BACNET NETWORK, DEVICES AND POINTS The IT-8000 uses Cylon’s INTEGRA-ProPack service to reduce deployment time when connecting to the Cylon’s BACnet field controllers. The INTEGRA-ProPack is a database import tool that automatically creates the BACnet network, devices and points in the IT-8000 . This service helps to reduce programming time when deploying a new project to the IT- 8000. The INTEGRA-ProPack quickly and easily exports network data from CXpro ᴴᴰ and imports it into the IT-8000, without the need to discover controllers and points. SPECIFICATIONS CONNECTION Note: Use Copper or Copper Clad Aluminum 70 °C conductors only. Terminals PCB mounted plug terminal connections Conductor Area Max: AWG 12 (3.31 mm 2 ) Min: AWG 22 (0.355 mm 2 ) MAXIMUM EXPANSION MODULES SUPPORTED IT8-NPB-LON 4 IT8-NPB-232 4 IT8-NPB-2X-485 2 I/O CONFIGURATION IT-8000 Maximum Combinations EXPANSION EXPANSION EXPANSION EXPANSION RS-232 or LONRS-232 or LONRS-232 or LON RS-232 or LON (2) RS-485 RS-232 or LONRS-232 or LON RS-232 or LON (2) RS-485 (2) RS-485 RS-232 or LON (2) RS-485 (2) RS-485 Expansion I/O Units IT8-EIO-16 • 8 Universal inputs: Type 3 (10k) thermistors, 0 … 100K ohm, 0 … 10 V DC, 0 … 20 mA with external resistor • 4 Relay outputs (Form A contacts, 24 V AC @ .5 amp rated) • 4 Analog outputs (0 … 10 V DC) • Powered from IT8-EIO-34 IT8-EIO-34 • 16 Universal inputs: Type 3 (10k) thermistors, 0 .. 100K ohm, 0 … 10 V DC, 0 … 20 mA with external resistor • 10 Relay outputs (Form A contacts, 24VAC @ .5 amp rated) • 8 Analog outputs (0 … 10 V DC) • Powered from a 24 V AC/DC source • Can power up to 4 IT8-EIO-16 modules Maximum Expansion • 16 x IT8-EIO-16 or • 8 x IT8-EIO-34 COMMON EXPANSION I/O CONFIGURATIONS 2 Panels 4 Panels 8 Panels ENVIRONMENT Note: This equipment is intended for field installation within an enclosure. Operating Temperature -4 F … 140 F [-20 C … 60 C] Storage Temperature -40 F … 185 F [-40 C … 85 C] Ambient Humidity 5% … 95% RH non-condensing Shipping & Vibration ASTM D4169, Assurance Level II MTTF 10 years + AGENCY CERTIFICATIONS UL 916 CE EN 61326-1 FCC Part 15 Subpart B, Class B | FCC Part 15 Subpart C C-UL Listed to Canadian Standards Association (CSA)C22.2 No. 205- M1983 “Signal Equipment” 1999/5/EC R&TTE Directive CCC | SRRC | RSS | RoHS 1 2 3 4©ABB 2021 All Rights Reserved. Subject to change without notice WWW.CYLON.COM page 3 of 6 DS0122US rev 2 DIMENSIONS AND WIRING Note: Compatible with (DIN43880) enclosures Suitable for mounting to a panel or to an EN50022 standard 35mm rail IT-8000 IT-8000 controller. Allow at least 1.5” (38mm) clearance around all sides and minimum 3” (76mm) at bottom for Wi-Fi antenna Expansion module. Up to four (4) may be used. See “Expansion Modules” and “I/O Configuration” Distances between center tabs from one unit to another unit IT8-EIO-16 IT8-EIO-34 1 2 3 1 2 3 ©ABB 2021 All Rights Reserved. Subject to change without notice WWW.CYLON.COM page 4 of 6 DS0122US rev 2 SYSTEM ARCHITECTURE ©ABB 2021 All Rights Reserved. Subject to change without notice WWW.CYLON.COM page 5 of 6 DS0122US rev 2 ORDERING INFORMATION IT-8000 US WLAN Wi-Fi BUNDLES IT-8005-USWIFI Includes core license for 5 devices or 250 points. Made up of IT-8000-WIFI + IT8-005-COR + IT8-005-SM0. IT-8010-USWIFI Includes core license for 10 devices or 500 points. Made up of IT-8000-WIFI + IT8-010-COR + IT8-010-SM0. IT-8025-USWIFI Includes core license for 25 devices or 1250 points. Made up of IT-8000-WIFI + IT8-025-COR + IT8-025-SM0. IT-8100-USWIFI Includes core license for 100 devices or 5000 points. Made up of IT-8000-WIFI + IT8-100-COR + IT8-100-SM0. IT-8200-USWIFI Includes core license for 200 devices or 10000 points. Made up of IT-8000-WIFI + IT8-200-COR + IT8-200-SM0. IT-8000 WW (Worldwide) WLAN Wi-Fi BUNDLES IT-8005-WWWIFI Includes core license for 5 devices or 250 points. Made up of IT-8000-WIFI + IT8-005-COR + IT8-005-SM0. IT-8010-WWWIFI Includes core license for 10 devices or 500 points. Made up of IT-8000-WIFI + IT8-010-COR + IT8-010-SM0. IT-8025-WWWIFI Includes core license for 25 devices or 1250 points. Made up of IT-8000-WIFI + IT8-025-COR + IT8-025-SM0. IT-8100-WWWIFI Includes core license for 100 devices or 5000 points. Made up of IT-8000-WIFI + IT8-100-COR + IT8-100-SM0. IT-8200-WWWIFI Includes core license for 200 devices or 10000 points. Made up of IT-8000-WIFI + IT8-200-COR + IT8-200-SM0. IT-8000 UNBUNDLED IT-8000-USWIFI 2 isolated RS-485 ports, configurable for 9.6 to 115.2 kbps. Support for 2 RS-485 protocols (BACnet MS/TP, LON, Modbus RTU). Two RJ-45 10/100 MB Ethernet with TCP/IP support for FOX, BACnet/IP, and Modbus TCP. Wi-Fi connectivity 802.11 a/b/g/n (US WLAN Country Code). Web Interface, embedded Workbench, integrated power supply and USB backup and restore. IT-8000-WWWIFI 2 isolated RS-485 ports, configurable for 9.6 to 115.2 kbps. Support for 2 RS-485 protocols (BACnet MS/TP, LON, Modbus RTU). Two RJ-45 10/100 MB Ethernet with TCP/IP support for FOX, BACnet/IP, and Modbus TCP. Wi-Fi connectivity 802.11 a/b/g/n (Worldwide WLAN Code). Web Interface, embedded Workbench, integrated power supply and USB backup and restore. IT-8000-NOWIFI 2 isolated RS-485 ports, configurable for 9.6 to 115.2 kbps. Support for 2 RS-485 protocols (BACnet MS/TP, LON, Modbus RTU). Two RJ-45 10/100 MB Ethernet with TCP/IP support for FOX, BACnet/IP, and Modbus TCP. NO Wi-Fi CONNECTIVITY. Web Interface, embedded Workbench, integrated power supply and USB backup and restore. Allow a minimum of two weeks for shipment. IT-8000 EXPANSION I/O IT8-EIO-16 IT-8000 16 Point Expansion IO Module. Powered by IT8-RIO-34 or external 15VDC power supply. Features 8UI, 4DO and 4AO. Requires IT-8000 and Niagara4 version 4.3 or higher. IT8-EIO-34 IT-8000 34 Point Expansion IO Module. Powered by an external 24VAC/DC power supply. Features 16UI, 10DO and 8AO. Requires IT-8000 and Niagara4 version 4.3 or higher. IT-8000 ACCESSORIES IT8-NPB-2X-485 IT-8000 add-on dual port RS-485 module IT8-NPB-232 IT-8000 add-on single port RS-232 module IT8-NPB-LON IT-8000 add-on single port LON FTT10A module IT8-WPM IT-8000 wall plug module. 100-240 VAC, 50/60 Hz. Connect to the 2.5 mm barrel plug, 24 V input to the IT-8000 and includes, US, EU, UK and AU plugs IT8-WIFI-EXT IT-8000 extension cable and bracket for WLAN antenna IT-8000 CORE SOFTWARE LICENSE FILE IT8-005-COR Adds support for up to 5 devices or 250 points. Requires IT-8000 & IT8-005-SM0 IT8-010-COR Adds support for up to 10 devices or 500 points. Requires IT-8000 & IT8-010-SM0 IT8-025-COR Adds support for up to 25 devices or 1,250 points. Requires IT-8000 & IT8-025-SM0 IT8-100-COR Adds support for up to 100 devices or 5,000 points. Requires IT-8000 & IT8-100-SM0 IT8-200-COR Adds support for up to 200 devices or 10,000 points. Requires IT-8000 & IT8-200-SM0 IT-8000 INITIAL DEVICE CAPACITY PACK IT8-010-DCP Adds support for an additional 10 devices or 500 points to the core (IT8-XXX-COR). Purchased at time of initial order with core software. IT8-025-DCP Adds support for an additional 25 devices or 1,250 points to the core (IT8-XXX-COR). Purchased at time of initial order with core software. IT8-050-DCP Adds support for an additional 50 devices or 2,500 points to the core (IT8-XXX-COR). Purchased at time of initial order with core software. ©ABB 2021 All Rights Reserved. Subject to change without notice WWW.CYLON.COM page 6 of 6 DS0122US rev 2 IT-8000 FIELD UPGRADE FOR DEVICE CAPACITY PACK IT8-010-DCU Adds support for an additional 10 devices or 500 points to the core (IT8-XXX-COR). Purchased any time after initial core software purchase. IT8-025-DCU Adds support for an additional 25 devices or 1,250 points to the core (IT8-XXX-COR). Purchased any time after initial core software purchase. IT8-050-DCU Adds support for an additional 50 devices or 2,500 points to the core (IT8-XXX-COR). Purchased any time after initial core software purchase. IT-8000 SERVICE AND MAINTENANCE AGREEMENTS IT8-005-SM0 18-month software maintenance agreement. IT8-005-SM1 1-year software maintenance agreement for core software IT8-005-COR. IT8-005-SM3 3-year software maintenance agreement for core software IT8-005-COR. IT8-005-SM5 5-year software maintenance agreement for core software IT8-005-COR. IT8-010-SM0 18-month software maintenance agreement. Must be purchased in conjunction with initial core software IT8-010-COR. Optional 3 or 5-year maintenance may be substituted. IT8-010-SM1 1-year software maintenance agreement for core software IT8-010-COR. IT8-010-SM3 3-year software maintenance agreement for core software IT8-010-COR. IT8-010-SM5 5-year software maintenance agreement for core software IT8-010-COR. IT8-025-SM0 18-month software maintenance agreement. Must be purchased in conjunction with initial core software IT8-025-COR. Optional 3 or 5-year maintenance may be substituted. IT8-025-SM1 1-year software maintenance agreement for core software IT8-025-COR. IT8-025-SM3 3-year software maintenance agreement for core software IT8-025-COR. IT8-025-SM5 5-year software maintenance agreement for core software IT8-025-COR. IT8-100-SM0 18-month software maintenance agreement. Must be purchased in conjunction with initial core software IT8-100-COR. Optional 3 or 5-year maintenance may be substituted. IT8-100-SM1 1-year software maintenance agreement for core software IT8-100-COR. IT8-100-SM3 3-year software maintenance agreement for core software IT8-100-COR. IT8-100-SM5 5-year software maintenance agreement for core software IT8-100-COR. IT8-200-SM0 18-month software maintenance agreement. Must be purchased in conjunction with initial core software IT8-200-COR. Optional 3 or 5-year maintenance may be substituted. IT8-200-SM1 1-year software maintenance agreement for core software IT8-200-COR. IT8-200-SM3 3-year software maintenance agreement for core software IT8-200-COR. IT8-200-SM5 5-year software maintenance agreement for core software IT8-200-COR. IT-8000 MISCELLANEOUS IT8-FIPS Provides FIPS 140-2 Level 1 conformance using the integrated FIPS certified BouncyCastle module for IT-8000. Requires IT-8000 version 4.6 and later. IT8-OS-AX Enables IT-8000 to run Niagara AX operating system instead of N4. IT-8000 DRIVERS IT8-DR-AC Andover Controls AC256 over RS-232 or RS-485. (Beta version only) IT8-DR-AINF Andover Controls Infinity. IT8-DR-APHP American Auto-Matrix PHP over RS-232 or RS-485. Manufactured by 3rd party. Limited support. IT8-DR-APUP American Auto-Matrix PUP over RS-232 or RS-485. Manufactured by 3rd party. Limited support. IT8-DR-CCN Carrier Comfort Network. IT8-DR-FLEX Flex over RS-232 or RS-485. IT8-DR-GLOB IR controlled AV equipment via an RS-232 connection to a Global Cache FC module. Requires IT8-OS-AX. Supported in AX version 3.8U1 only. IT8-DR-HELV Helvar Lighting Control. Requires IT8-OS-AX. Supported in AX version 3.8U1 only. IT8-DR-HORT European Hortsmann meters. Requires IT8-OS-AX. Supported in AX version 3.8U1 only. IT8-DR-JOS Josam Grease Trap Sensor. Requires IT8-OS-AX. Supported in AX version 3.8U1 only. IT8-DR-LANGOVN Lang Oven over RS-232 or RS-485. Requires IT8-OS-AX. Supported in AX version 3.8U1 only. IT8-DR-MCQUAY McQuay to OPM driver. IT8-DR-MFID Micros Fidelio IP driver. IT8-DR-VDRT Veeder-Root over RS-232 or RS-485. Requires IT8-OS-AX. Supported in AX version 3.8U1 only. Cylon, UniPuts, Auto-Matrix, ASPECT, ASPECT-Enterprise, ASPECT-Studio, Auto-Flow, INTEGRA, Smart building solutions, flexible building solutions, Solution Integrator and V-STAT are either trademarks or registered trademarks of are registered trademarks of ABB Cylon Controls. BACnet is a registered trademark of ASHRAE; BTL is a registered trademark of the BACnet Manufacturers Association; Niagara AX Framework is a registered trademark of Tridium, Inc.; All other trademarks are property of their respective owners. Next >