Sensor PowerInduced from monitored conductor Insulation Class600 Vac RMS Frequency Range50/60 Hz Temperature Range-15 to 60 °C (5 to 140 °F) Humidity Range10 to 90% RH non-condensing Accuracy±2% F.S. from 10% to 100% (selected range) Response Time2 sec. Terminal Block Wire Size24 to 14 AWG (0.2 to 2.1 mm 2 ) Terminal Block Torque3.5 to 4.4 in-lbs (0.4 to 0.5 N-m) WARRANTY Limited Warranty5 years AGENCY APPROVALS Agency Approvals UL 508 open device listing, CAT III, Pollution Degree 2, basic insulation SENSED AMPS 30/60/120 A* 0 V 0 A 5 V SENSOR OUTPUT *Factory calibrated ranges selected with the amperage range switch H932 EXAMPLE LINEAR OUTPUT Scale software as shown APPLICATIONS • Load trending • Motor control • Fan/pump status SPECIFICATIONS Maximize Reliability Minimize Installed Cost TM Note: Do not use LED status indicators as evidence of applied voltage The Hawkeye 932 and 952 Series provide accurate load trending information with a proportional 0 to 5 Vdc output signal. This feature combined with an integrated command relay makes these products ideal for start/stop and status monitoring of motors. The relay is fully isolated from the current sensor, and all relay connections are externally available for maximum flexibility. Self-powered Self-powered analog current transducer with integral start/stop command relay Reduces installation One device to install for start/stop and status Saves time Reduces the number of installed components…saves time and space No external power No external power required for current sensor Retrofit Self-gripping, split-core design for fast retrofit installation…no need to remove conductor Increased flexibility Selectable factory calibrated ranges up to 120 A for increased flexibility and resolution 800.354.8556 | +1 503.598.4564 | sales@veris.com | intl@veris.com | www.veris.com TM H932 & H952 Load Trending and Control Relay in One Package Current Monitoring | Current Transducers with Relay: 0 to 5 Vdc Analog Output HQ0001767.F 0117Fan or Pump CONTROLLER Motor CONTACTOR CONTROL POWER Digital Output (Relay Coil) Analog Input (0 to 5 Vdc) MODEL AMPERAGE RANGE SENSOR OUTPUT RELAY TYPE RELAY COIL HOUSINGUL H932 0 to 30/60/120 A0 to 5 VdcSPST, N.O. 24 Vac/dc Split-core • H95212 Vdc• Removable Mounting Bracket Self-gripping Iris 1.0” (25 mm) 0.8” (21 mm) 1.1” (26 mm) 3.1”** (79 mm) 2.8” (70 mm) Ø 0.3” (8 mm) 1.4”* (36 mm) 2.5” (64 mm) 3.0” (76 mm) Bracket can be mounted on three sides for added installation flexibility. RELAY CONTACT RATINGS (N.O.) Resistive5 A @ 250 Vac, 30 Vdc 5 A @ 30 Vac, 30 Vdc Inductive2 A @ 250 Vac, 30 Vdc 2 A @ 30 Vac, 30 Vdc TYPICAL COIL PERFORMANCE VoltageACDC 24 (H932)1515 12 (H952)20 Pull In Voltage (H952 only) 12 Vdc8.4 Vdc Drop Out Voltage (H952 only) 12 Vdc3.0 Vdc H932/H952 Dimensional Drawing TRENDING & CONTROLLING MOTOR LOADS WITH THE HAWKEYE 932 Wiring Diagram ORDERING INFORMATION * Terminal block may extend up to 1/8” over the height dimensions shown. ** Slide switch may extend up to 1/4” over the height dimensions shown. 800.354.8556 | +1 503.598.4564 | sales@veris.com | intl@veris.com | www.veris.com TM Current Monitoring | H932 & H952 HQ0001767.F 0117Next >