Sensor Power30 mA (max.) @ 12 to 30 Vdc Insulation Class600 Vac RMS Frequency Range50/60 Hz Temperature Range-15 to 60 °C (5 to 140 °F) Humidity Range10 to 90% RH non-condensing Accuracy±2% F.S. from 10% to 100% (selected range) Response Time2 sec. Terminal Block Wire Size24 to 14 AWG (0.2 to 2.1 mm 2 ) Terminal Block Torque3.5 to 4.4 in-lbs (0.4 to 0.5 N-m) WARRANTY Limited Warranty5 years AGENCY APPROVALS Agency Approvals UL 508 open device listing, CAT III, Pollution Degree 2, basic insulation SENSED AMPS 30/60/120 A* 0 V 0 A 5 V SENSOR OUTPUT *Factory calibrated ranges selected with the amperage range switch H931 Note: Do not use LED status indicators as evidence of applied voltage Maximize Reliability Minimize Installed Cost TM EXAMPLE LINEAR OUTPUT Scale software as shown SPECIFICATIONS APPLICATIONS • Load trending • Motor control • Positive proof of flow The Hawkeye 931 provides accurate load trending information with a proportional 4 to 20 mA output signal. These devices offer three amperage ranges for versatility, with easy slide-switch selection. The command relay is fully integrated in the device, but it is isolated from the current transducer. This combination makes these products ideal for start/stop control and status monitoring of motors, using one device instead of two. Loop-powered Loop-powered analog current transducer with integral start/stop command relay Reduces installation charges One device to install for start/stop and status Saves time Reduces the number of installed components…saves time and space Fewer wires Power the current sensor and receive the 4 to 20 mA signal with only two wires Retrofit Self-gripping, split-core design for fast retrofit installation…no need to remove conductor Factory calibrated Selectable factory calibrated ranges up to 120 A for increased flexibility and resolution 800.354.8556 | +1 503.598.4564 | sales@veris.com | intl@veris.com | www.veris.com TM H931 Load Trending and Control Relay in One Package Current Monitoring | Current Transducers with Relay: 4 to 20 mA Analog Output HQ0001766.G 0117* Terminal block may extend up to 1/8” over the height dimensions shown. ** Slide switch may extend up to 1/4” over the height dimensions shown. Fan or Pump CONTROLLER Motor CONTACTOR Analog Input (4 to 20 mA) Digital Output (Relay Coil) CONTROL POWER 12 to 30 Vdc Power Source MODEL AMPERAGE RANGE SENSOR OUTPUT RELAY TYPE RELAY COIL RELAY RELAY POWER LED UL H9310 to 30/60/120 A4 to 20 mA SPST, N.O. 24 Vac/dc••• Removable Mounting Bracket Self-gripping Iris 1.0” (25 mm) 0.8” (21 mm) 1.1” (26 mm) 3.1”** (79 mm) 2.8” (70 mm) Ø 0.3” (8 mm) 1.4”* (36 mm) 2.5” (64 mm) 3.0” (76 mm) Bracket can be mounted on three sides for added installation flexibility. RELAY CONTACT RATINGS (N.O.) Resistive5 A @ 250 Vac, 30 Vdc 5 A @ 30 Vac, 30 Vdc Inductive2 A @ 250 Vac, 30 Vdc 2 A @ 30 Vac, 30 Vdc TYPICAL COIL PERFORMANCE VoltageACDC 241515 ORDERING INFORMATION DIMENSIONAL DRAWINGTRENDING & CONTROLLING MOTOR LOADS Wiring Diagram 800.354.8556 | +1 503.598.4564 | sales@veris.com | intl@veris.com | www.veris.com TM Current Monitoring | H931 HQ0001766.G 0117Next >