MobileAccessPortalGatewayInstallationInstructions PartNo.24-10737-8,Rev.F SoftwareRelease4.0 IssuedApril2016 RefertotheQuickLITwebsiteforthemostup-to-dateversionofthisdocument. Applications TheMobileAccessPortal(MAP)Gatewayisanalternate localdisplaysolutionoratemporaryportable commissioningdevicethatenablesuserstoleveragethe powerofmobilityusingsmartphones,tablets,orlaptop computerstointeractwithbuildingautomationequipment controls.TheMAPGatewayservesupwebpagesthrough abuilt-inWi-FiaccesspointortetheredEthernet connection,whichallowsuserstoviewandedit equipmentcontrollerconfigurationparameters,setpoints, schedules,andalarmsthroughabrowser.Amobile applicationisnotrequiredtousetheMAPGatewaywith yourmobiledevice. TheMAPGatewaycanbeusedtoseefieldbusdevices onMetasys ® systems,FacilityExplorersystems,and SmartEquipmentrooftopunits(RTUs)withunitcontrol boards(UCBs).TheMAPGatewaysupports JohnsonControls ® brandedFieldControllers,including FEC,FAC,VMA,PCA,PCG,andPCVSeriesdevices. MAPGatewayalsosupportstheTEC3000Series Thermostats. ThewirelessconnectionontheMAPGatewayallows usersofasupportedmobiledevicetobeupto30m(100 ft,lineofsight)awayindoorsandupto91m(300ft,line ofsight)awayoutdoors.Powermaybesuppliedviathe SAB(sensor/actuatorbus),theFCB(fieldcontrollerbus), asuppliedexternalpowersupply,oramicroUSBport. TheMAPGatewaycomesintwoconfigurations:a portableconfigurationandastationaryconfiguration. Configurationischosenatpurchase,andtheaccessories shippedwiththeMAPGatewaydependonthe configurationchosen. Whenusedasaportabledevice,theMAPGatewaycan beattachedtoalanyard.Inthisconfiguration,theMAP Gatewaycanbecarriedfromsitetosite,dependingon theneedsandworkflowoffieldpersonnel. Whenusedasastationarydevice,theMAPGateway canbepermanentlymounteddirectlytoawallorDINrail usingthesuppliedMAPGatewaymountingcradle. NorthAmericanEmissions Compliance UnitedStates Thisequipmenthasbeentestedandfoundtocomply withthelimitsforaClassAdigitaldevicepursuantto Part15oftheFCCRules.Theselimitsaredesignedto providereasonableprotectionagainstharmful interferencewhenthisequipmentisoperatedina commercialenvironment.Thisequipmentgenerates, uses,andcanradiateradiofrequencyenergyand,ifnot installedandusedinaccordancewiththeinstruction manual,maycauseharmfulinterferencetoradio communications.Operationofthisequipmentina residentialareamaycauseharmfulinterference,inwhich casetheuserswillberequiredtocorrecttheinterference attheirownexpense. RFTransmitters:ComplianceStatement(Part15.19) ThisdevicecomplieswithPart15oftheFCCRules. Operationissubjecttothefollowingtwoconditions: 1.Thisdevicemaynotcauseharmfulinterference,and 2.Thisdevicemustacceptanyinterferencereceived, includinginterferencethatmaycauseundesired operation. Warning(Part15.21) Changesormodificationsnotexpresslyapprovedbythe partyresponsibleforcompliancecouldvoidtheuser’s authoritytooperatetheequipment. RFExposure(OETBulletin65) TocomplywithFCCRFexposurerequirementsfor mobiletransmittingdevices,thistransmittershouldonly beusedorinstalledatlocationswherethereisatleast 20cmseparationdistancebetweentheantennaandall persons. 1MobileAccessPortalGatewayInstallationInstructionsCanada IndustryCanadaStatement ThetermICbeforethecertification/registrationnumber onlysignifiesthattheIndustryCanadatechnical specificationsweremet. Leterme«IC»précédantlenuméro d'accréditation/inscriptionsignifiesimplementquele produitestconformeauxspécificationstechniques d'IndustryCanada. Installation Observethefollowingguidelines: •VerifythatallpartsshippedwiththeMAPGateway. •Keeptheunitencasedintheprotectiveshell.Ifnot protectedbytheenclosureinwhichitships,theMAP Gatewaymaybesubjecttophysicaldamage. PartsIncluded(PortableModel) •MAPGateway •Protectiveshell •6-pinRJ-12connectorcable •Lanyard •InstallationInstructions •MobileAccessPortalGatewayQuickStartGuide (PartNo.24-10737-16) PartsIncluded(StationaryModel) •MAPGateway •Fieldbusadapter •Mountingbracket(withlockingscrew) •InstallationInstructions •MobileAccessPortalGatewayQuickStartGuide (PartNo.24-10737-16) SpecialToolsNeeded TousetheMAPGateway,youneedamobiledevice (tabletorsmartphone)orcomputer(laptopordesktop) thatsupportsWi-Fi. Iftheunitispermanentlymountedtoaverticalsurface withoutaDINrail,youneedscrewstomounttheunit. Thespecificscrewtypesdependuponthesurfaceto whichtheunitismounted.ThescrewholesontheMAP GatewaycanaccommodateM3.5and#6screws. Useofthemountingbracketlockingscrewrequiresa T15Torxdriver. PortableUse Whenusedasaportableunit,theMAPGatewayshould behousedinthesuppliedshell.Duringuse,theunitcan betemporarilyhungonnearbyequipmentusingthe suppliedlanyard. RiskofPersonalInjury.DonotwearorholdtheMAP Gatewayduringuse,andonlyuseorinstalltheMAP Gatewayatlocationswherethereisatleast20cm betweenthebuilt-inantennaandallpersons.Failureto dosomayresultinminorormoderatepersonalinjury. MISEENGARDE: Risquedeblessure.Nepasporterousoutenirl'MAP Gatewaydurantsonutilisationetutiliserouinstaller l'MAPGatewayuniquementàunemplacementoffrant unedistanceminimumde20cmentrel'antenneintégrée ettoutepersonne.Lenon-respectdecetteprécaution risquedeprovoquerdesblessureslégèresoudegravité modérée. Observethefollowingguidelineswhenusingaportable MAPGateway: •DonotusetheRJ-12cabletosupporttheweightof theMAPGateway.Usethelanyardtosupportit. •KeeptheMAPGatewayintheprotectiveshellwith whichitships.ToinserttheMAPGatewayintothe shell,stretchtheshelledgesandslidetheMAP Gatewayunitintoplace(Figure1).Thisshellprotects theunitfromdropsupto1.22m(4ft). •TheMAPGatewayhasnotbeendesignedfor prolongedoutdooruse.Leavingitinoutdoor environments(suchasinsiderooftopunits)mayresult indamage. •Objects(includingductwork,cabinets,doors,and glass)canimpedethewirelesssignal.Minimizethe numberofobjectsbetweentheconnectedcomputer ormobiledeviceandtheMAPGateway.Uselineof sight,ifpossible. •Metalobjects(suchascabinetdoors,enclosures,and pipes)andconcreteobjects(suchaspillars,walls, andceilings)maylimitWi-Fiservice.To accommodatepotentialstructuralobstaclesonsite, theMAPGatewaycanbemountedflatorontheside. 2MobileAccessPortalGatewayInstallationInstructionsRiskofPropertyDamage.DonotusetheRJ-12cable oranyotherfieldbuscableorelectricalcabletosupport theweightoftheMAPGateway.HangingtheMAP Gatewayfromanythingotherthanthesuppliedlanyard mayresultindamagetotheproductorperipheral equipment. MISEENGARDE: Risquededégâtsmatériels.Nepasutiliserlecâble RJ-12outoutautrecâbledebusdeterrainoucâble électriquepoursoutenirlepoidsdel'MAPGateway.La suspensiondel'MAPGatewayàtoutautreélémentque lalongefournierisqued'endommagerleproduitoules équipementspériphériques. Figure1:PortableMAPGatewayandProtectiveShell Mounting Permanent Whenusedinastationaryconfiguration,theMAP Gatewayispermanentlymountedusingabracketwhich isprovidedwiththestationaryMAPGateway.We recommendthefollowingthreewaystomounttheunit: vertically(uprightandflush),horizontally(sidewaysand flush),orperpendicularly(perpendiculartothewall).This flexibilityallowstheunittobemountedinawaythat minimizesspacialconstraintsandmaximizesplacement optionsforoptimalwirelesssignalstrength. Theunitshouldbemountedinsuchawaythatlabels canbereadiftheyarevisible.(Forexample,donotmount theunitupsidedown,whichputsthelabelsupsidedown.) LocationConsiderations ObservethefollowingguidelineswhenmountingaMAP Gateway: •MounttheMAPGatewayinareasfreeofcorrosive vaporsandobservetheenvironmentallimitations listedintheTechnicalSpecificationssectionofthis document. •Objects(includingductwork,cabinets,doors,and glass)canimpedethewirelesssignal.Minimizethe numberofobjectsbetweentheconnectedcomputer ormobiledevicecomputerandtheMAPGateway. Uselineofsight,ifpossible. •Metalobjects(suchascabinetdoors,enclosures,and pipes)andconcreteobjects(suchaspillars,walls, andceilings)maylimitWi-Fiservice.To accommodatepotentialstructuralobstaclesonsite, theMAPGatewaycanbemountedflushagainstthe wallorperpendiculartoit. •TheMAPGatewayisnotratedforoutdoormounting. LockingScrew(StationaryUnitOnly) Regardlessofwhichmountingconfigurationisused,a lockingscrewcanbeusedtosecuretheunitintothe mountingbracket.Donotovertightenthelockingscrew. Figure2:StationaryMountingwithLockingScrew PermanentMountingLocations Themountingbracketcanbeattachedtoa35mm (1-1/8in.)DINrailoraflat,verticalsurface.Mountingthe unitonaceilingorinawaythatpositionsthefrontofthe unitfacingdownisnotrecommended. 3MobileAccessPortalGatewayInstallationInstructionsAlthoughthebrackethastwomountingclips,onlythe bottomclipsnapsinward.Thetopclipispermanently lockedintheoutwardposition,anditcanbeusedasan additionalholeforscrewingthebracketintoplace.Ifnot utilizedforDINrailorsurfacemounting,thetopand bottomclipsmayberemovedfromthemountingbracket. DINRailMounting TomountthebracketonaDINrail: 1.Securelymounta7.5cm(3in.)orlongersectionof 35mm(1-1/8in.)DINrailintherequiredspace. 2.Onthebracket,pullthebottommountingclipoutward totheextendedposition. Figure3:PositioningtheBracketonaDINRail 3.HangthebracketontheDINrailbythehooksatthe topoftheDINrailchannel(onthebackofthe bracket),andpositionthebracketsnuglyagainstthe DINrail. 4.Pushthebottommountingclipinwardtosecurethe mountingbracketontheDINrail. 5.PlacetheMAPGatewayunitinthebracketand secureitwiththelockingscrew. WallMounting Thebracketmaybemountedusingscrewholesonthe backofthebracket(sothattheunitisflatonitsback), usingthescrewholesonthesideofthebracket,orusing theholesintheDINrailclips.Thisorientationhelps accommodateon-siteconstraints.Screwholelocations areillustratedinFigure7 ,Figure8,andFigure9. Thescrewtypesneededtomounttheunitdependupon thesurfacetowhichtheunitismounted.Thescrewholes ontheMAPGatewaycanaccommodateM3.5and#6 screws. Forinformationonlocationconsiderationsformaximizing signalstrength,seetheMountingsection. Figure4:SamplePermanentMounting,Back-side Screws Figure5:SamplePermanentMounting,SideScrews Figure6:SamplePermanentMounting,DINRail ScrewHoles 4MobileAccessPortalGatewayInstallationInstructionsTomountthebracketonaflatsurface(suchasawall): 1.Pullthebottommountingclipoutwardtotheextended position. 2.Markmountingholelocationsonthewallusingthe dimensionsshowninFigure7,Figure8,orFigure9; orholdthebracketagainstthewallandmarkthehole locationsthroughthemountingclips. Note:Thepositionofthelocationholesdependson whetherthebracketismountedhorizontally orvertically. Figure7:MountingHoles,FlatMounting Note:ThescrewholesontheMAPGatewaycan accommodateM3.5and#6screws. Figure8:MountingHoles,SideMounting Note:ThescrewholesontheMAPGatewaycan accommodateM3.5and#6screws. 5MobileAccessPortalGatewayInstallationInstructionsFigure9:MountingHoles,FlatMounting,DIN RailScrews Note:ThescrewholesontheMAPGatewaycan accommodateM3.5and#6screws. 3.Drillholesinthewallbasedonthelocationsmarked intheprecedingstep,andinsertwallanchorsforeach hole(ifnecessary). 4.Holdthebracketinplace,insertthescrewsthrough themountingclipsandintothescrewholes,andthen carefullytightenallscrews. Important:Donotovertightenthemountingscrews. Overtighteningthescrewsmaydamage themountingclipsorbracket. 5.PlacetheMAPGatewayunitinthebracketand securethebracketwiththelockingscrew. Wiring WiringConsiderationandGuidelines ObservethefollowingguidelineswhenwiringtheMAP Gateway: •DonotallowtheMAPGatewaytohangfromacable connection. •ProvidesomeslackinthecablebetweentheMAP Gatewayandthecontrollerorotherdevicetowhich youareconnecting. SA/FCPort TheMAPGatewayhasoneRS-485FC/SAbusportthat connectsthroughasupplied6-pinmodularjackandcable assembly.Fordatatransmissionandvoltage specifications,seetheTechnicalSpecificationssection. DonotplugtheSA/FCconnectorintoastandardphone jack. SeetheFeaturessectionforthelocationofthe communicationsterminalontheMAPGateway. Figure10:SA/FCPortPin FieldBusCommunicationsConnections ToconnecttheMAPGatewaytotheSA/FCfieldbusfor communication,connectoneendoftheRJ-12cableto theMAPGatewayandtheotherendofthecabletoa controllerornetworksensor. Note:TheMAPGatewayhasadedicatedMS/TPbus addressof03.ThenumberofMAPGatewayunits thatcanbeconnectedsimultaneouslytoone MS/TPbusdependsonthenumberofFCandSA portsavailableandconnectedtothebus.The MS/TPbuscanaccommodateoneMAPGateway ontheFCbusandoneMAPGatewayforeach SAbusconnectedtothetrunk. PerformanceoftheMAPGatewayvariesbased onthenumberofSAbusconnectionsandamount oftraffic. 6MobileAccessPortalGatewayInstallationInstructionsUSBPort Note:USBportfunctionalityisnotavailableinthis softwarerelease. TheUSBportontheMAPGatewayisa5-pin,Micro-B peripheralserialportwhichconformstotheUSB2.0 standard.TheMAPGatewayUSBportisforconnecting toacomputerforcommissioning,downloading,and retrievingdata.WhentheMAPGatewayisconnected andpoweredfromtheUSBport,FC/SAbusfunctions arenotavailable. Note:TheUSBconnectionontheMAPGatewayisnot designedforconstantuse.TheUSBportshould beusedonlywhenneeded. Table1:USBPortPinDesignations SignalNamePinNumber (BothEnds ofCable) +5VDC1 Data-2 Data+3 NoConnection4 Ground5 EthernetPort TheEthernetportontheMAPGatewayisan8-pinRJ-45 jack.Themaximumallowablecablelengthis100m (328ft). SeetheFeaturessectionforthelocationofthe communicationsterminalontheMAPGateway. Note:IfyouusetheEthernetporttoconnecttothe MS/TPbus,powermustbesuppliedbyan externalsupplythatisnottheUSBconnectionor theSA/FCbusconnection.Externalpowersupply hardwarevariesbymarket.Forinformationon theexternalpowersupplyprovided,seethe TechnicalSpecificationssection. ExternalPowerSupplyConnections ToconnecttheMAPGatewayusingthesuppliedexternal powersource: 1.Connectthe15VDCoutputconnectorofthepower supplytothepowersupplyportoftheMAPGateway. RiskofPropertyDamage.Donotapplypowerto thesystembeforecheckingallwiringconnections. Shortcircuitedorimproperlyconnectedwiresmay resultinpermanentdamagetotheequipment. MISEENGARDE: Risquededégâtsmatériels.Nepasmettrele systèmesoustensionavantd'avoirvérifiétousles raccordsdecâblage.Desfilsformantuncourt-circuit ouconnectésdefaçonincorrecterisquent d'endommagerirrémédiablementl'équipement. 2.Connectthepowersupplytothesuppliedpowercord. 3.Plugthepowercordintoa100-240VACoutlet. Important:Powershouldonlybeappliedandremoved byconnectinganddisconnectingthepower cordfromthe100-240VACoutlet.Applying orremovingpowerbyconnectingor disconnectingthe15VDCconnectorcan damagetheunit. RiskofElectricShock.Disconnectorisolateallpower suppliesbeforemakingelectricalconnections.Morethan onedisconnectionorisolationmayberequiredto completelyde-energizeequipment.Contactwith componentscarryinghazardousvoltagecancause electricshockandmayresultinseverepersonalinjury ordeath. AVERTISSEMENT: Risquededéchargeélectrique.Débrancherouisoler toutealimentationavantderéaliserunbranchement électrique.Plusieursisolationsetdébranchementssont peut-êtrenécessairespour-couperentièrement l'alimentationdel'équipement.Toutcontactavecdes composantsconducteursdetensionsdangereuses risqued'entraînerunedéchargeélectriqueetde provoquerdesblessuresgraves,voiremortelles. 7MobileAccessPortalGatewayInstallationInstructionsFigure11:MAPGatewaywithSampleExternalPower Supply Operation AccessingSmartEquipmentUsing theMAPGateway WhentheMAPGatewayisphysicallyconnectedtoan MS/TPnetwork,userscanhaveaccesstoSmart Equipmentdevices.TheMAPGatewaycanconnect throughtheSAbusorthroughtheFCbus. ThroughtheSensorActuator(SA)Bus IftheMAPGatewayisconnectedthroughtheSAbus (forexample,pointAonFigure12 ),itcanaccesstheSE deviceandallSEdevicesonthatdevice'sFCbuswhen theFcBusModeissettoWiredFieldBus(BACnet MSTP)intheUCBdisplaymenuoftheunitsconnected totheFCbusnetwork.YoucanconnecttheMAP GatewaythroughthelocalSABusjackontheequipment controlboard.Or,ifaNetSensorisinstalled,youcan connecttheMAPGatewaydirectlytotheRJ-12jackon theNetSensor. ThroughtheFieldController(FC)Bus IftheMAPGatewayisconnectedthroughtheFCbus (pointBintheexample),ithasaccesstoSEdeviceson thatFCbusonlywhentheFCbusprotocolisBACnet MSTP.ForindividualunitsconnectedtotheFCbus network,theFcBusModeissettoWiredFieldBus (BACnetMSTP)intheUCBdisplaymenu.TheMAP GatewaycanbeconnectedtotheFCbusthroughthe RJ-12connectorontheFieldBuscardofthesmart equipment.Or,usinganRJ-12toTerminalBlockAdapter (MP-STAFBA-0),youcanconnecttheMAPGateway directlytothefieldbus. Tointeractwithadeviceorproductonthenetwork(to viewdevices,setpoints,orviewalarms),usersselectthe deviceusingaweb-enableddevicethatisconnectedto theMAPGatewayWi-Finetwork.Tousethenetwork, usersmusthaveaweb-enableddevicethatusesa supportedInternetbrowser.Forinformationonconnecting tothenetwork,seeConnectingtotheMAPGateway Wi-FiNetwork. Figure12:AccessingSmartEquipment ConnectingtotheMAPGatewayWi-Fi Network Important:IfyouaregoingtousetheMAPGateway onEthernet,youmustplugitintoexternal powerbeforeyouattachthefieldbus adapter. 1.ConnecttheFC/SAportoftheMAPGatewaytothe sensorbusorfieldbusportoftheequipment controllerusingthesuppliedRJ-12cable(portable model)orfieldbusadapter(stationarymodel) (Figure 13).TheMAPGateway'sLEDsflash,indicatingthat thedeviceisinitializing.WhentheFaultLEDturns 8MobileAccessPortalGatewayInstallationInstructionsoffandtheWi-FiLEDsflashinsuccession,theMAP Gatewayisreadytouse. Figure13:ConnectingthePortableMAP GatewaytoYourEquipment 2.IntheWi-Fisettingsofyourdeviceorlaptop,connect totheMAPGatewayWi-Finetworkusingyourdefault credentials.Thesecredentialsareincludedona stickerintheQuickStartGuide(PartNo. 24-10737-16)thatcamewithyourdevice. 3.Directyourbrowsertowww.mapgwy.comtoopen theMAPGatewaybrowserinterface. 4.Note:MAPGatewayshipswithaprivate mapgwy.comSSLcertificateinstalledto ensuresecurecommunicationwiththeMAP Gateway.However,thiscertificatedoesnot indicatethatitistrustedinabrowser.Ifyou wishtoinstallyourowncertificate,referto AddingaPrivateKeyandCertificatetoMAP GatewayintheMobileAccessPortalGateway NetworkandITGuidanceTechnicalBulletin (LIT-12012015). 5.ReadandaccepttheMAPGatewaylicense agreement. 6.ThefirsttimeyoulogintotheMAPGateway,the ChangePasswordandPassphrasewebpage appears.YoumustchangetheAdminpasswordand Wi-Fipassphrase. Important:AfteryouchangetheWi-Fipassphrase orSSID,thewebserverrestartsandyou mustrejointheMAPGatewayWi-Fi networkusingthenewpassphrase.On somemobiledevices,youmustselect andforgettheoriginalMAPGateway Wi-Finetworkbeforerejoiningthe networkwiththenewpassphrase. ReplacethedefaultpasswordintheNewAdmin Passwordfield.Confirmthechangebyenteringthe newpasswordintheVerifyNewAdminPassword field ReplacetheWi-FiPassphraseintheNewWi-Fi PassphrasefieldandclickSave. OncetheMAPGatewayisphysicallyconnectedtothe MS/TPnetwork,alldevicesonthenetworkthathavean equipmentnumberareavailable. Tointeractwithadeviceorproductonthenetwork(to viewdevices,setpoints,orviewalarms),selectadevice usingthemobiledevicethatisconnectedtotheMAP Gateway. ResetButtonOperationand Descriptions Ifyouloseyourpasswordorifyouwanttorestorethe unittofactorydefaults,theMAPGatewayofferstworeset functions:aNetworkResetfunctionthatresetsWi-Fiand Ethernetsettings,andaResettoFactoryDefaults functionthatresetsallunitsettings(includinguser profiles).ResettoFactoryDefaultsalsoresetsyourSSL certificatetotheJohnsonControls ® self-signedcertificate thatisinthedevicewhenitcomesfromthefactory. TheNetworkResetfunctionisintendedforindividuals whoforgettheirWi-Ficonnectioninformation,andthe ResettoFactoryDefaultsfunctionisforuseby administratorswhomaywanttoclearalluserprofiles fromadevice.Forinformationonresettingtheunit,see Table2. Important:Touseaunitthatisresettofactorydefaults, youmusthavethedefaultlogininformation suppliedintheQuickStartGuidethat shippedwiththeunit.TheResettoFactory Defaultsfunctiondoesnotchangethe versionoftheapplication.Ifyoudida softwareupgrade,theMAPGateway remainsattheupgradedversionratherthan resettingtotheversionthatitwasrunning whenitleftthefactory. Theresetbuttonisonthebackofthedevice,anditis embeddedintotheMAPGatewayhousingsothatit cannotbeactivatedbyaccident.Toreachthereset button,useasmallscrewdriverorsimilartool. •Ifyouareconnectedtothenetworkwhenyouuse theresetbutton,youaredisconnected. •Ifyoupresstheresetbuttonformorethan9seconds, theresetoperationiscancelled. •Ifafaultconditionalreadyexists,theresetbuttonis disabled. 9MobileAccessPortalGatewayInstallationInstructionsNext >