Advanced Application Field EquipmentController (FAC) Catalog PageLIT-1900759 2018-12-17Johnson Controlswww.johnsoncontrols.com3Advanced Application Field Equipment Controller (FAC) Catalog PageAdvanced Application Field Equipment Controller(FAC)The Advanced Application Field Equipment Controller (FAC) Series Controllers are programmablecontrollers that can communicate using BACnet/IP, MS/TP, or N2 communications protocols,depending on the model. The FAC4911 is a BACnet Advanced Application Controller (B-AAC) thatcommunicates using BACnet/IP communications protocol. All other FAC Series controllers can beswitched between MS/TP and N2 communication protocols. FAC controllers used as MS/TP devicesare B-AACs with integral RS-485 MS/TP communications.FAC Series Controllers feature an integral real-time clock. FACs support time-based tasks andmaintain time-based control, which enables these field controllers to monitor and controlschedules, calendars, alarms, and trends. FACs can continue time-based control and monitoringwhen offline for extended periods of time from a Metasys system network.FAC Series Controllers can also operate as stand-alone controllers in applications that do notrequire a networked supervisory device or for network applications where it is preferred to havethe scheduling, alarming, and/or trending performed locally in the field controllers.The FAC4911 controllers operate on BACnet/IP networks and integrate into Johnson Controls® andthird-party systems.The FAC3611 and FAC3613 models include a fast persistence feature that allows data values to beheld at a configurable value, up to once per second. Persistence refers to how often samples ofdata are stored locally. In the event of a problem, such as a loss of power, data can be retrieved upto the rate that the data is persisted, minimizing the potential loss of data. When power is restored,previously persisted data, up to the rate of persistence, remains available and accessible. Forexample, if persistence is configured for once per second, you only risk losing one second of data.Persisting data may be essential for situations that require greater data accuracy, including certainmethods of utility data collection and billing.The FAC2612 controller features line-voltage relay outputs, which makes this controller well-suitedfor use in terminal units. The FAC2612-2 model uses a line-voltage power supply, which eliminatesthe need for a 24 VAC transformer in line-voltage applications.The FAC2611, FAC2612, FAC3611, and FAC3613 controllers using the MS/TP protocol supportwireless communications using the ZFR or ZFR Pro Series accessories and the WRZ-7860 One-to-One Receiver.Important: You cannot purchase a similar third-party device and install it in a UL/cUL Listedsmoke control system. Doing so voids the UL/cUL Smoke Control Listing. Third-party devicesmust be provided and labeled by the factory as described in the UL/cUL Smoke Control Listing.Important: Only those Johnson Controls products identified for use in smoke controlapplications have been tested and listed by UL for use in a Metasys system UL 864 10th EditionUUKL/ORD-C100-13 UUKLC Smoke Control System. Installation of a product that is not UL/cULListed and labeled for this application prevents the entire system from being UL/cUL Listed forsmoke control.Advanced Application Field Equipment Controller (FAC) Catalog Page4Figure 1: Advanced Application Field Equipment Controllers (FACs)Features•Switchable Communications Protocols—Provides flexibility with a choice between BACnet MS/TP and N2 communication.•Standard BACnet Protocol—Provides interoperability with other Building Automatcion System(BAS) products that use the widely accepted BACnet standard.•Standard Hardware and Software Platform—Uses a common hardware design throughoutthe family line to support standardized wiring practices and installation workflows; also uses acommon software design to support use of a single tool for control applications, commissioning,and troubleshooting to minimize technical training.•ZFR Wireless FC or SA Bus Interface—Both the ZFR1800 Series Wireless and WNC1800/ZFR182xPro Series Wireless Field Bus (ZFR Pro) provide a wireless alternative to hard-wired Metasyssystem counterparts, offering application flexibility and mobility with minimal disruption tobuilding occupants.•Bluetooth® Wireless Commissioning—Provides an easy-to-use connection to the configurationand commissioning tool.•Auto-Tuned Control Loops—Reduce commissioning time, eliminate change-of-season re-commissioning, and reduce wear and tear on mechanical devices.•Universal Inputs and Configurable Outputs—Allows multiple signal options to provide input/output flexibility.•BACnet Testing Laboratories (BTL) Listed and Certified—Ensures interoperability with otherBTL-listed devices. BTL is a third-party agency, which validates that BAS vendor products meetthe BACnet industry-standard protocol.•32-bit Microprocessor—Ensures optimum performance and meets industry specifications.•BACnet Automatic Discovery—Supports easy controller integration into a Metasys BAS.•End-of-Line (EOL) Switch in MS/TP Field Controllers —Enables field controllers to beterminating devices on the communications bus.•Pluggable Communications Bus and Supply Power Terminal Blocks—Expedites installationand troubleshooting.•Writable Flash Memory—Allows standard or customized applications to be downloaded from5Advanced Application Field Equipment Controller (FAC) Catalog Pagethe CCT and enables persistent application data.•DIS17 Remote Display and the MAP Gateway Support—Enable monitoring and commandingof I/O and configuration parametersApplication DocumentationRefer to the Metasys System Field Equipment Controllers and Related Products Product Bulletin(LIT-12011042) for product application details.If the product fails to operate within its specifications, replace the product. For a replacementproduct, contact the nearest Johnson Controls®representative.FAC Series Model Information (Including Point Type Counts)Note: The FAC2513 is only available in certain regions. Contact your local Johnson Controlsrepresentative for more information.Table 1: FAC Series Model Information (Including Point Type Counts)FAC2513FAC2611FAC2612FAC3611FAC3613FAC4911Communication ProtocolBACnetMS/TPBACnet MS/TP, N2BACnet/IPEngines SupportedAll Model types. Some NIE models support MS/TPand N2 devices. Refer to the Network Engines ProductBulletin (LIT-12012138) for details.NAE55,NAE85,ODS atR9.0 orlater6-pin SA Bus Modular Port supports one communicatingsensor. Or you can wire up to four communicating sensors tothe SA Bus Terminal Block. They cannot be used at the sametime.Modular Jacks6-pin FC Bus for tool supportPoint TypesSignals AcceptedUniversalInput (UI)Analog Input,Voltage Mode, 0–10 VDCAnalog Input,Current Mode, 4–20 mAAnalog Input,Resistive Mode, 0–2k ohm, RTD (1k NI[Johnson Controls],1k PT, A99B SI),NTC (10k Type L,2.252k Type 2)Binary Input, DryContact MaintainedMode4CurrentMode notsupported658810Advanced Application Field Equipment Controller (FAC) Catalog Page6Table 1: FAC Series Model Information (Including Point Type Counts)FAC2513FAC2611FAC2612FAC3611FAC3613FAC4911Binary Input(BI)Dry ContactMaintained ModePulse Counter/Accumulator Mode(High Speed), 100Hz624666AnalogOutput (AO)Analog Output,Voltage Mode, 0–10 VDCAnalog CurrentMode, 4–20 mA2CurrentMode notsupported2664BinaryOutput (BO)24 VAC Triac2ExternalPoweronly3664Configurable Output(CO)Analog Output,Voltage Mode, 0–10 VDCBinary OutputMode, 24 VAC Triac2444RelayOutput (RO)RO: Single-Pole,Double-Throw(SPDT)RO: Single-Pole,Single-Throw(SPST)2 - SPDTand 3 -SPST line-voltagerelays,1/4 hp120 VAC,1/2 hp240 VACFAC Series Ordering InformationTable 2: FAC Series Ordering InformationProduct CodeNumberDescriptionMS-FAC2513-016-Point Advanced Application Field Equipment Controller with 4 UI, 6 BI, 2CO, 2 BO, and 2 AO; 24 VAC; SA Bus; FC Bus; Integral Real-time ClockNote: This model is only available in certain regions. Contact your localJohnson Controls representative for more information.7Advanced Application Field Equipment Controller (FAC) Catalog PageTable 2: FAC Series Ordering InformationProduct CodeNumberDescriptionMS-FAC2611-017-Point Advanced Application Field Equipment Controller with 6 UI, 2 BI, 4CO, 3 BO, and 2 AO; 24 VAC; SA Bus; FC Bus; Integral Real-time ClockMS-FAC2612-118-Point Advanced Application Field Equipment Controller with 5 UI, 4 BI, 4CO, 2 SPDT and 3 SPST Line-Voltage ROs 1/4 hp 120 VAC, 1/2 hp 240 VAC; 24VAC; SA Bus; FC Bus; Integral Real-time Clock;MS-FAC2612-218-Point Advanced Application Field Equipment Controller with 5 UI, 4 BI, 4CO, 2 SPDT and 3 SPST Line-Voltage ROs, 1/4 hp 120 VAC, 1/2 hp 240 VAC;100–240 VAC; SA Bus; FC Bus; Integral Real-time ClockMS-FAC3611-026-Point Advanced Application Field Equipment Controller with 8 UI, 6BI, 6 BO, and 6 AO; 24 VAC; SA Bus; FC Bus; Integral Real-time Clock; FastPersistenceMS-FAC3613-026-Point Advanced Application Field Equipment Controller with 8 UI, 6BI, 6 BO, and 6 AO; 24 VAC; SA Bus; FC Bus; Integral Real-time Clock; FastPersistenceMS-FAC4911-028-Point Advanced Application Field Equipment Controller with 10 UI, 6 BI,4 BO, 4 AO, and 4 CO; 24 VAC; SA Sensor Port; Integral Real-time Clock; 2Ethernet Ports for BACnet/IP CommunicationsFAC Series Smoke Control Ordering InformationTable 3: FAC Series for Smoke Control Ordering InformationProduct CodeNumberDescriptionMS-FAC2611-0U17-Point Advanced Application Field Equipment Controller with 6 UI, 2 BI, 3BO, 2 AO, and 4 CO; 24 VAC, MS/TP (FC) Bus, SA Bus, integral real-time clockMS-FAC2612-1U18-Point Advanced Application Field Equipment Controller with 5 UI, 4 BI, 4CO, 2 SPDR RO, and 3 SPST RO; 24 VAC, MS/TP (FC) Bus, SA Bus, integral real-time clockNote: These devices are UL/ULC 864 Listed, File S4977, 10th Edition UUKL/ORD-C100-13 UUKLCSmoke Control System. These devices must be ordered in a Smoke Control UUKL listing.Note: You cannot purchase a similar third-party device and install it in a UL/cUL Listed smokecontrol system. Doing so voids the UL/cUL Smoke Control Listing. Third-party devices must beprovided and labeled by the factory as described in the UL/cUL Smoke Control Listing.Advanced Application Field Equipment Controller (FAC) Catalog Page8AccessoriesNote: The accessories marked with an asterisk (*) in the table are not qualified for use with aUL 864 UUKL/UUKLC 10th Edition Listed Smoke Control system.Table 4: FAC AccessoriesProduct CodeNumberDescriptionIOM SeriesRefer to the Metasys® System Field Equipment Controllers and Related ProductsProduct Bulletin (LIT-12011042) for a complete list of available IOM SeriesControllers.TL-CCT-0Metasys Controller Configuration Tool (CCT) softwareMS-FCP-0Metasys Field Controller Firmware Package Files for CCTMobile AccessPortal (MAP)Gateway*Refer to the Mobile Access Portal Gateway Catalog Page (LIT-1900869) toidentify the appropriate product for your region.Note: The MAP Gateway serves as a replacement for the the BTCVT,which is no longer available for purchase, but continues to besupported.NS Series NetworkSensorsRefer to the NS Series Network Sensors Product Bulletin (LIT-12011574) forspecific sensor model descriptions.WRZ SeriesWireless RoomSensors*Refer to the WRZ Series Wireless Room Sensors Product Bulletin (LIT-12011653)for specific sensor model descriptions.MS-DIS1710-0Local Controller Display: Refer to Local Controller Display Product Bulletin(LIT-12011273) for more information.WRZ-7860-0*Receiver for One-to-One Wireless Room Sensing Systems - functions withWRZ Series Sensors room sensorsWRZ-SST-120*Wireless System Survey ToolZFR1800 SeriesWireless Field BusSystem*This system is used for installations that only support BACnet MS/TP. Referto the WNC1800/ZFR182x Pro Series Wireless Field Bus System Product Bulletin(LIT-12012320) for a list of available products.ZFR-USBHA-0*USB Dongle with ZFR Driver provides a wireless connection through CCT toallow wireless commissioning of the wirelessly enabled FEC, FAC, IOM, andVMA16 controllers. Also allows use of the ZFR Checkout Tool (ZCT) in CCT.Note: The ZFR-USBHA-0 replaces the IA OEM DAUBI_2400 ZFR USBdongle. For additional information about the ZFR-USBHA-0 ZFR dongle,refer to the ZFR1800 Series Wireless Field Bus System Technical Bulletin(LIT-12011295) or ZFR1800 Series Wireless Field Bus System Quick ReferenceGuide (LIT-12011630).Y64T15-0*Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 92 VA, FootMount, 30 in. Primary Leads and 30 in. Secondary Leads, Class 2Y65A13-0*Transformer, 120 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount(Y65AS), 8 in. Primary Leads and 30 in. Secondary Leads, Class 2Y65T42-0*Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, HubMount (Y65SP+), 8 in. Primary Leads and Secondary Screw Terminals, Class 2Y65T31-0*Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, FootMount (Y65AR+), 8 in. Primary Leads and Secondary Screw Terminals, Class 29Advanced Application Field Equipment Controller (FAC) Catalog PageTable 4: FAC AccessoriesProduct CodeNumberDescriptionAP-TBK4SA-0Replacement MS/TP SA Bus Terminal, 4-Position Connector, Brown (Bulk Packof 10)AP-TBK4FC-0Replacement MS/TP FC Bus Terminal, 4-Position Connector (Bulk Pack of 10)AP-TBK3PW-0Replacement Power Terminal, 3-Position Connector, Gray (Bulk Pack of 10)AS-CBLTSTAT-0Cable adapter for connection to 8-pin TE-6700 Series sensorsMS-TBKLV03-0Terminal Block Kit - FAC Line Voltage AC Power - 3 PiecesMS-TBKRO02-0Terminal Block Kit - FAC 2-Position Relay Output - 9 PiecesMS-TBKRO03-0Terminal Block Kit - FAC 3-Position Relay Output - 6 PiecesMS-TBKCO04-0Terminal Block Kit - FAC 4-Position Configurable Output - 6 PiecesMS-TBKUI04-0Terminal Block Kit - FAC 4-Position Universal Input - 3 PiecesMS-TBKUI05-0Terminal Block Kit - FAC 5-Position Universal Input - 3 PiecesTL-BRTRP-0*Portable BACnet/IP to MS/TP RouterRepair InformationIf the product fails to operate within its specifications, replace the product. For a replacementproduct, contact the nearest Johnson Controls® representative.Next >