Series IEF Insertion Electromagnetic Flow TransmitterSpecifications - Installation and Operating InstructionsBulletin F-IEF-FThe SERIES IEF Insertion Electromagnetic Flow Transmitter is an adjustable insertion flowmeter featuring electromagnetic technology that accurately and reliably measures fluid velocity in addition to providing several continuous signal outputs. This series is specifically designed to offer superior performance paired with simple installation and use. One unit is adjustable to fit pipe sizes from 4 to 36˝ (102 to 914 mm), and offers several output options including selectable BACnet MS/TP or Modbus® RTU communications protocol over 2-wire RS-485 in addition to the standard analog, frequency and alarm outputs. FEATURES/BENEFITS• Field configurable setup displays (-LCD integral option or remote accessory A-IEF-DSP) allow for ultimate flexibility by accommodating a variety of application configurations with one model through multiple display configurations i.e. pipe size, pipe material, liquid type, analog output, pulse/frequency output, alarm outputs, communication outputs, damping, and calibration factor.• High performance accuracy is maintained through changes in temperature, density or viscosity.• Setup Wizard and installation tool are simple to use allowing for quick and precise installation.• Accessory setup kit A-IEF-KIT ensures exact installation application depth with included thickness gage and measuring tape. • Long Life Cycle and minimal maintenance requirements with no moving parts to wear or break and electrodes that discourage fouling.• Isolation valve accessory options allow for installation in operational systems via hot-tap kit or easy removal without system downtime. • NIST calibration certificate included standard for Carbon Steel Schedule 40 pipes sized 4˝ (102 mm), 6˝ (150 mm), 8˝ (200 mm), and 10˝ (250 mm) with high accuracy option.APPLICATIONS• Boiler feed water • Chilled water • Open and closed loop condenser water • Irrigation system• Municipal water distribution• Process and coolant flow• Ground water remediation• Chemical processing• Pump protection• Wastewater• MiningSPECIFICATIONSService: Compatible clean or dirty non coating, conductive liquids.Range: 0 to 20 ft/s (0 to 6 m/s).*Wetted Materials: Body shaft/fitting: 316SS; Electrodes: 316SS; Electrode cap: Polymer/Polystyrene; O-ring: Silicone.Accuracy: IEF-HX-X: ±0.5% of reading at calibrated velocity; ±1% of reading from 2 to 20 ft/s (0.6 to 6 m/s) ±0.02 ft/s (±0.006 m/s) at < 2 ft/s (0.6 m/s). IEF-SX-X: ±1% FS.Temperature Limits: Ambient: -20 to 160°F (-29 to 71°C); Process: 15 to 250°F (-9 to 121°C); Storage: -40 to 185°F (-40 to 85°C).Process Connection: 1˝ NPT or BSPT with accessory full port ball valve options.Pressure Limits: 400 psi (27.6 bar) @ 100º F (37.8°C).Pressure Drop: < 0.1 psi at 12 ft/s in 4˝ (101.6 mm) and larger pipe.Outputs: (1) Analog: 4 to 20 mA, 0 to 5 V, 0 to 10 V or 2 to 10 V (display selectable); (1) Pulse/Frequency: 0 to 15 V peak pulse, 0 to 500 Hz or scalable pulse output (display selectable); (2) Alarm: (1) Empty pipe detection or minimum/maximum velocity, (display selectable); (1) Reverse flow output indication.Power Requirements: 12 to 42.4 VDC, .25 A @ 24 VDC; 12 to 36 VAC.Electrical Connection: Removable terminal blocks, model selectable 1/2˝ female NPT conduit connection, PG 16 gland or PG 16 gland with (2) 10 ft (3 m) 9 conductor 22 AWG plenum rated cables, accessory cable lengths up to 200 ft (61 m) optional.Display (-LCD option): 2˝ ( 5.08 cm) x 2˝ (5.08 cm) graphic LCD with backlight.Conductivity: >20 microsiemens.Enclosure Material: Powder coated die cast aluminum.Enclosure Ratings: NEMA 6P (IP68) (Non display models); NEMA 4X (IP66) (-LCD option).Agency Approvals: BTL, CE, NSF/ANSI 61 and 372 pending.COMMUNICATIONS (-COM OPTION)Type: BACnet MS/TP or Modbus® RTU communication protocol (default disabled, display selectable).Supported Baud Rates: 9600, 19200, 38400, 57600, 76800, or 115200 bps (display selectable).Device Load: 1/8 unit load. ADDITIONAL SPECIFICATIONSApplicable Pipe Material: Most popular plastic and metal pipes; i.e. Carbon steel, SS, copper, UPVC/PVDF, galvanized steel, mild steel, and brass.Applicable Pipe Size: IEF-HX-X: 4 to 10˝ (101 to 254 mm); IEF-SX-X: 4 to 36˝ (101 to 914 mm).Diameter Length Requirements: >10 upstream, >5 downstream.Glycol: 0 to 100% display selectable.*For max flowrates >10 ft/s (3 m/s) order option -CC.-LCD option shownShown with A-IEF-VLV-BR accessory valve5-53/64 [148.0]4-51/64[121.8]61/64[24.2]22-1/64[559.2]5-53/64[148.0]7-3/32 [180.2]Modbus® is a registered trademark of Schneider Automation, Inc.®DWYER INSTRUMENTS, INC.P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.Phone: 219/879-8000Fax: 219/872-9057www.dwyer-inst.come-mail: info@dwyermail.comINCLUDED WITH THE FLOWMETERCarefully unpack the shipping container of your new Series IEF Insertion Electromagnetic Flow Transmitter and remove the following items: • (1) Series IEF Insertion Electromagnetic Flow Transmitter • (1) A-IEF-INGD Installation Alignment Kit: (1) Alignment Scale (2) Alignment Rods (2) Thumbscrews • (1) 3 mm Allen Wrench (not shown)RECOMMENDED TOOLS • (2) 12˝ (300 mm) adjustable wrenches • (1) 12˝ (300 mm) pipe wrenchSETUPSelecting Installation Location 1. Although the unit may be installed in any orientation, the ideal mounting position is on the side of the pipe (2 o’clock or 10 o’clock position)* as this generally minimizes possible air or sediment interference with the Series IEF. It is not reccomended to mount the unit below the pipe (6 o’clock position). Insert the IEF in a pipe via a threaded Tee, Saddle, or welded integrally reinforced branch connection outlet fitting. If a Hot-Tap option is required, use a 1-1/4˝ valve kit with proper mounting hardware available in Model A-IEF-VLV-BR or A-IEF-VLV-SS. A 1˝ (25.4 mm) hole in the pipe is required for proper installation. Safety Information OPERATING PRINCIPLE • Per Faraday’s Law of electromagnetic induction, a voltage is induced in a conductor when it passes through a magnetic field, and the induced voltage will be directly proportional to the velocity of the conductor. • The Series IEF Flow Transmitter generates pulsating magnetic fields in the probe to induce a voltage into a conductive fluid flowing through the pipe. • Electrodes located on the probe measure the induced voltage. Electronics and firmware within the enclosure convert the voltage to velocity and flow rate while using various outputs to convey the data to connected systems (i.e. display devices, data acquisition systems, or BTU meters).MODEL CHARTExampleIEF-HN-CND-LCDIEF-HN-CND-LCD SeriesIEFInsertion electromagnetic flow transmitterAccuracyHSHigh accuracy; 1% of readingStandard accuracy; 1% FS Process ConnectionNB1˝ NPT1˝ BSPTElectrical Housing ConnectorCNDPG101/2˝ female NPTPG 16 glandPG 16 gland with (2) 10´ (3 m) plenum rated cablesOptionsLCDCOMNISTFCCCIntegral LCDBACnet or Modbus® communication protocol (display selectable)Multiple point NIST traceable calibration certificateFactory calibration certificate for 0.5% of reading at single pointCustom configured for specific installation • Only qualified professionals equipped with the necessary required trade skills should install, remove or service this product in any way. Failure to follow the proper installation procedures could lead to death or permanent injury. • This product is intended to be installed in pressurized pipe applications. In this event, product will be under pressure, caution should be taken to properly vent system prior to installation or removal of the unit. Failure to do so could result in equipment damage and/or serious bodily injury. WARNING • Refer to Model Chart and Specifications for the applicable options to your unit. • Ensure the unit is sufficiently grounded as stated in this bulletin. • Depressurize and vent systems without Hot-tap valve prior to installation or removal. • Confirm the Series IEF wetted material is chemically compatible with process media prior to installation and use. • Do not exceed maximum temperature and pressure specifications. • Wear appropriate personal protective equipment during installation, removal and or service of the unit. • Altering the product construction in any way may adversely affect product operation and voids warranty. • Prior to attempting to wire or service the Series IEF disconnect from power.CAUTIONFigure 1Figure 2ACCESSORIESModelDescriptionA-IEF-KITA-IEF-DSPA-IEF-CBL-50A-IEF-VLV-BRA-IEF-VLV-SSA-IEF-INGDA-IEF-PASetup kit (includes setup display, thickness gage and measuring tape)Setup displayPlenum rated cable 50 ft (15.2 m)1-1/4˝ full port isolation valve brass1-1/4˝ full port isolation valve 316SSInstallation alignment kitAC wall adapterAlignment scale (1) Rods (2)Thumbscrews (2)Series IEFRODTHUMBSCREWBODYRULER(2 PLACES) When installing a unit with an integral display select an installation location that allows for clear viewing of the display and proper earth ground.NOTICE**For Field Configurable Models 2. For field configuration, a display is required (-LCD option or accessory A-IEF- DSP) and needs to be powered via normal field wiring or with the AC wall adapter accessory A-IEF-PA ( A-IEF-DSP and A-IEF-PA are also available in the accessory setup kit A-IEF-KIT). 3. When using the AC wall adapter and the cable is supplied, connect the red (positive +) and black (common -) wires of the cable bundle marked “A” to the open terminals of the AC wall adapter. This will provide temporary power to the meter to complete the installation set up. 4. For field wiring, refer to the wiring chart tag attached to the Series IEF to identify the terminal block pins for positive (+) and common (-) connection. 5. Unscrew the four captured cover screws using the supplied 3 mm Allen wrench to remove and set aside enclosure cover. 6. Insert one connector of the ribbon cable supplied in the setup kit into the connector labeled “Display” in the middle of the unit. Be sure to orient the keying feature/tab. See Figure 5 below:For Custom Configured Models (-CC Option) 2. Locate the configuration tag attached to the Series IEF to identify the value of the alignment scale setting. Position the alignment scale such that the scale setting is lined-up with the seam of the enclosure as shown in Figure 4. Minor scale marks are in 1/20ths Securely tighten the thumbscrews. 3. Refer to Preparing the Unit for Installation section. 7. Plug the other end of the cable into the bottom of the supplied portable display being sure to orient the keying feature/tab as shown: 8. Apply power to the unit and the display will turn-on automatically. Follow the on screen directions for entering the necessary parameters to setup the unit and obtain the alignment scale setting value. 2. Select a location that will minimize flow distortion with adequate upstream and downstream pipe diameters as displayed. Ideal installation will have a minimum of 10 pipe diameters upstream relative to the instrument and a minimum distance of 5 pipe diameters downstream. INSTALLATION 1. To prepare the meter for installation, mount the provided alignment scale to the side of the meter with the two provided thumbscrews. The thumbscrews are to be inserted through the alignment scale slots and into the holes in the side of the lid as shown in Figure 4, finger tighten only. Be sure to orient the alignment scale as shown in figure below. Actual scale setting determined in next step.20x5x20x5xFLOW DIRECTIONUSE LID TOENCLOSUREGAP ASINDICATOR LINE Figure 3Figure 4Figure 5Figure 6KEYINGFEATUREKEYINGFEATURE When using measuring tape A-IEF-MSTP to measure pipe circumference use the 100ths side to measure the circumference of the pipe without insulation.NOTICEPrecise pipe measurements are required for high performance installation. The A-IEF-KIT includes setup display A-IEF-DSP, thickness gage UTG and measuring tape A-IEF-MSTP used to obtain these measurements. When the precise pipe measurement information is known select Option 2 High Performance setup in the Install Kit option of the display selectionNOTICENOT RECOMMENDEDRECOMMENDEDSensor AlignmentA depth and flow alignment installation tool is provided to ensure proper depth insertion and flow alignment. To set the insertion depth verify the alignment scale has not moved from its original setting based on the alignment scale value set previously.Loosen compression nut (4) to allow the shaft (3) freedom to travel up and down and rotate inside the process collet (5).Install Depth and Alignment Rods 1. Remove alignment rods from sides of alignment scale by sliding them out. 2. Insert the two rods into the alignment scale as shown. 3. Rotate the transmitter so the pipe alignment rod is parallel with the flow in the pipe. 4. Slide the shaft (3) down into the process collet (5) until the depth rod contacts the pipe. If pipe insulation is present press the rod through the insulation. a. Tighten the nut (4) to 15 ft.-lbs (20.3 N m) b. Remove the flow alignment rod and loosen the thumbscrews to slide the alignment tool up to allow removal of the depth alignment rod. Store both rods in the storage slots on the sides of the alignment scale. Tighten thumbscrews and leave alignment tool mounted on unit for storage.GROUNDINGMetallic PipeFor proper operation the instrument must be earth grounded. Connect a ground wire to meter housing via the ground lug on the housing collet. Connect the ground wire to a known earth ground. If the pipe is grounded, connect the ground wire to the metal pipe using suitable devices such as grounding clamps. Non-Metallic PipesConnect a ground wire to the transmitter housing per the ground lug on the housing collet. Connect the ground wire to a known earth ground. Ground the fluid to earth. POWER SUPPLYChoose a power supply with a voltage and current rating sufficient to meet the power specifications under all operating conditions.If the power supply is unregulated, make sure the output voltage remains within the required voltage range under all power line conditions.FLOW ALIGNMENT RODALIGNMENT TOOLDEPTH RODPIPE ALIGNMENT ROD MUSTBE PARALLEL WITH PIPE FLOW DIRECTIONGrounding lugGROUNDING RINGS1. Enclosure2. Cable Nut3. Probe Shaft4. Compression Fitting5. Process Collet6. Valve (optional)7. Valve Handle (optional)8. Pipe9. Sensor Probe123789456Figure 7Preparing the Unit for installation (Refer to Figure 7) 1. Apply appropriate sealant to the process collet (5) threads such as application suitable sealant tape or paste. 2. Install the process collet (5) in valve (6) then tighten by hand. 3. Tighten the process collet (5) with a wrench using the hex geometry until snug. 4. Slowly open the valve handle (7) checking for leaks. 5. If leaks occur around threaded connections, close the valve and tighten those connections.Figure 8Figure 10Figure 11Figure 9Use two wrenches, one to hold the valve and another wrench to turn the process collet.NOTICE Do not adjust housing compression nut at top of probe shaft (3).NOTICEWIRING DIAGRAMCableTerminal #Wire ColorDescriptionNoteAAABExternal121314RedBlackShieldShield-Power Supply PositivePower Supply Common--Earth/Chassis GroundConnect to +24VDC or VAC transformerConnect to 24VDC/VAC commonIf used - Application DependantIf used - Application Dependant-Analog Current OutputBB34BrownBlue(+) Analog current output(-) Analog output common4 to 20 mA process outputCurrent output commonAnalog Voltage OutputBB56GreenWhite(+) Analog voltage output(-) Analog output commonMay be configured; 0 to 10 V, 0 to 5 V, 2 to 10 V, etc.Voltage output commonFrequency OutputBB87VioletGrey(+) Frequency output(-) Analog output common0 to 500 Hz output (@ 0/15 VDC output level)Frequency output commonRS-485 Communication (optional)BB11,129,10OrangeYellowRS-485 (+)RS-485 (-)On board short for daisy chain connectionOn board short for daisy chain connectionReverse FlowAA1516BrownBlueIsolated solid state output N.O.Isolated solid state output N.O.50 V AC/VDC @ 100 mA maximum50 V AC/VDC @ 100 mA maximumAlarmA A1718GreenWhiteIsolated solid state output N.O.Isolated solid state output N.O.50 V AC/VDC @ 100 mA maximum50 V AC/VDC @ 100 mA maximumPulseAA1920OrangeYellowIsolated solid state output N.O.Isolated solid state output N.O.50 V AC/VDC @ 100 mA maximum50 V AC/VDC @ 100 mA maximumNo ConnectionBBAA----RedBlackVioletGreyDo not connectDo not connectDo not connectDo not connect----The Cable column identifying cable A and B is reflective of units that include factory installed cabling.Wiring PCBA shown in Figure 12 with terminal block numbers as listed in above wiring diagram chart.Figure 12Follow the on screen directions for entering the circumference and wall thickness dimensions. See the Electronic Control Data Setup section of this manual for more information. Determining probe insertion depth for models without a displayFor models without a display the following formulas allow for calculating the alignment scale value for setting the depth of the probe into the pipe. Also included are wall thickness charts for various pipe materials and sizes. Pipes < 11 in (< 279 mm) diameter: 7.1625-1/2*DWhere D represents the pipe outer diameter and WT represents the pipe wall thickness, both in inches. Measurement of the outside diameter and wall thickness can be accomplished as described in the previous section, Determining probe insertion depth for models with a display, or similar method. Precise pipe measurements are required for a high performance installation.Position the alignment scale such that the alignment scale setting is lined-up with the seam of the enclosure as shown in Figure 13. Minor scale marks are in 1/20ths Securely tighten the thumbscrews. Determining probe insertion depth for models with a displayThe Series IEF transmitter will calculate the probe insertion depth used with -LCD display option or A-IEF-DSP display when the steps below are followed. 1. To measure the pipe circumference remove any existing insulation at the location where the transmitter will be installed. Wrap the tape measure around the pipe to measure the circumference at the selected location using the 100ths side of the tape. Record this measurement for entering into the unit when the circumference measurement is requested. 2. To measure the wall thickness of the pipe use the thickness gage UTG. Following the separate directions provided with the UTG gage and record the thickness. This measurement will be needed to enter into the unit after the circumference data is entered.It is recommended to use the A-IEF-KIT which includes a setup display A-IEF-DSP, thickness gage UTG and measuring tape A-IEF-MSTP to obtain these measurements. When the precise pipe measurement information is known, select option 2 (High Performance Setup) under the Install Kit Menu when prompted by the display as shown below. Precise pipe measurements are required for a high performance installation. NOTICEUSE LID TOENCLOSUREGAP ASINDICATOR LINE Figure 13WALL THICKNESSCarbon SteelPipe Diameter (in)DN (mm)SCH5 (in) SCH5 (mm)SCH10 (in)SCH10 (mm)SCH40 (in)SCH40 (mm)SCH80 (in)SCH80 (mm)4.55.5636.6258.62510.7512.7514161820243236114.30141.30168.28219.08273.05323.85355.60406.40457.20508.00609.60813.00914.400.0830.1090.1090.1090.1340.1560.1560.1650.1650.1880.2180.2500.2502.1102.7702.7702.7703.4003.9603.9604.1904.1904.7805.5406.3506.3500.1200.1340.1340.1480.1650.1800.2500.2500.2500.2500.2500.3120.3123.0503.4003.4003.7604.1904.5706.3506.3506.3506.3506.3507.9207.9200.2370.2580.2800.3220.3650.4060.4370.5000.5620.5930.6880.6880.7506.0206.5507.1108.1809.27010.31011.13012.70014.27015.09017.48017.48019.0500.3370.3750.4320.5000.5930.6870.7500.8430.9371.0311.2181.2181.2188.5609.53010.97012.70015.09017.48019.05021.44023.83026.19030.96030.96030.960WALL THICKNESSStainless SteelPipe Diameter (in)DN (mm)SCH5 (in) SCH5 (mm)SCH10 (in)SCH10 (mm)SCH40 (in)SCH40 (mm)SCH80 (in)SCH80 (mm)4.55.5636.6258.62510.7512.7514161820243236114.30141.30168.28219.08273.05323.85355.60406.40457.20508.00609.60813.00914.400.0830.1090.1090.1090.1340.1560.1560.1650.1650.1880.2180.2500.2502.1102.7702.7702.7703.4003.9603.9604.1904.1904.7805.5406.3506.3500.1200.1340.1340.1480.1650.1800.1880.1880.1880.2180.2500.3120.3123.0503.4003.4003.7604.1904.5704.7804.7804.7805.5406.3507.9207.9200.2370.2580.2800.3220.3650.3750.3750.3750.3750.3750.3750.3750.3756.0206.5507.1108.1809.2709.5259.5259.5259.5259.5259.5259.5259.5250.3370.3750.4320.5000.5000.5000.5000.5000.5000.5000.5000.5000.5008.5609.52510.97012.70012.70012.70012.70012.70012.70012.70012.70012.70012.700WALL THICKNESSCopperPipe Diameter (in)DN (mm)Type KType LType Minmminmminmm4.1255.1256.1258.12510.2512.2514161820243236104.78130.18155.58206.38257.18307.98355.60406.40457.20508.00609.60813.00914.400.1340.1600.1920.2710.3410.4110.4710.4710.5410.6100.6800.8181.0963.4004.0644.8766.8838.66110.43911.96311.96313.74115.49417.27220.77727.8380.1140.1250.1400.2000.3560.4110.4590.4590.5130.5680.6230.7320.9502.8953.1753.5565.0809.04210.43911.65811.65813.03014.42715.82418.59324.1300.0950.1090.1220.1700.3080.3560.3980.3980.4450.4930.5410.6360.8262.4132.7683.0984.3187.8239.04210.10910.10911.30312.52213.74116.15420.980WALL THICKNESSPVCPipe Diameter (in)DN (mm)SCH40SCH80inmminmm4.55.5636.6258.62510.7512.7514161820243236114.00141.00168.00219.00273.00324.00356.00406.00457.20508.00609.60813.00914.400.2370.2580.2800.3220.3650.4060.4370.5000.5620.5930.6870.8740.9686.0206.5507.1108.1809.27010.30011.10012.70014.27415.06217.45022.20024.5870.3370.3750.4320.5000.5930.6870.7500.8430.9371.0311.2181.5721.7548.5609.52011.00012.70015.10017.40019.00021.40023.80026.18730.93739.92944.552Printing out configuration valuesAfter installation is complete a table of configuration values can be gathered from the transmitter to print out and insert into one of the hanging plastic envelopes for future reference. The housing cover/display needs to be removed for access to the display port to retrieve the table of configuration values. To do so: 1. Unscrew the four captured cover screws using the supplied 3 mm Allen wrench to remove the enclosure cover. Leave the display cable connected to the main unit. 2. Insert a customer supplied mini-USB cable into the USB connector on the bottom side of the display PCB. 3. Connect the other end into a standard USB port in a laptop. 4. The Series IEF transmitter will appear as a standard USB drive on the laptop. 5. The file name with the configuration values is in the format of: serial number.txt. The serial number can be found on the product label on the side of the transmitter. 6. Print out the configuration values and insert into one of the hanging plastic envelopes for future reference 7. Re-attach the housing cover/display by reinserting the four 3 mm screws.Removing Series IEF Transmitter 1. To remove the transmitter from an installation without a valve depressurize the pipe and skip to step 4. If installed with a valve loosen compression fitting (4) and withdraw the transmitter shaft fully through the valve until it stops. 2. Tighten compression fitting (4) snug. 3. Close valve (6) via valve handle (7). 4. Remove transmitter by unscrewing process collet (5) from value (6). Network Termination Jumper On the terminal block PCBA there is a jumper, J1 (see Figure 15), that enables or disables a network termination resistor as defined below:When the network jumper is placed in the ON position there is a 120 ohm termination resistor in place. When the network jumper is placed in the OFF position there is no termination resistor in place.Default: OFFCONFIGURATION DATA PRINT OUT EXAMPLE[Device Information]MeterTag=Series IEFSerialNumber=Andrew2ModelNumber=IEF-XX-COM-LCDDateCode=20180101[Setup Information]CalibratedBy=Date=Units=EnglishVelocityUnit=ft/sFlowUnit=ft³/sVolumeUnit=gal[Pipe Configuration]LiquidType=WaterPipeMaterial=Carbon SteelPipeCircumference=27.096 inPipeWallThickness=0.322 inAlignmentScaleValue=1.85[Analog Output]AnalogOutputType=Current 4-20mAAnalogOutputVariable=Velocity ft/sAnalogOutputHigh=20.00AnalogOutputLow=0.00[Pulse/Freq. Output Setup]Pulse/Freq. Output=Disabled[Alarm Output Setup]AlarmOutput=Empty Pipe Alarm[Communication]CommunicationProtocol=Disabled1. Enclosure2. Cable Nut3. Probe Shaft4. Compression Fitting5. Process Collet6. Valve7. Valve Handle8. Pipe9. Sensor Probe123789456NETWORK TERMINATION JUMPERFigure 15Figure 14Be sure to support the housing end of the transmitter to prevent it from flipping while unscrewing process collet (5) as damage may occur to the probe fins.CAUTIONCommunication OverviewThe Insertion Magmeter supports BACnet MS/TP and Modbus® RTU over 2-wire RS-485. Selection of protocol and configuration of serial parameters require the use of the display. BACNETBACnet Object OverviewSupported BACnet ObjectsBACnet Objects: Device ObjectThe default object identifier is 607xxx, where xxx is replaced by the MS/TP MAC address set in the Network Address menu. The object identifier value will change as the MS/TP MAC address changes. However, if a specific object identifier is written via BACnet, then that value is stored and changes to the MS/TP MAC address will no longer affect the object identifier. Similarly, the default object name includes 607xxx. The object name will reflect the current object identifier. If a specific object name is written via BACnet, then that value is stored and changes to the object identifier will no longer affect the object name.APDU Timeout values are rounded to the nearest second (1000ms). Values less than 500 will be rounded to 0 and Number of APDU Retries will be set to 0.Object TypeDynamically CreatableDynamically CreatableObject IdentifierObject NameDeviceAnalog InputAnalog ValueBinary ValueBitString ValueNoNo NoNoNoNoNo NoNoNo607xxxAV1AV1AV2BV1BV2BV3BSV1Series IEF 607xxxVelocityFlowTotal FlowReverse FlowEmpty PipeReset Total FlowStatus FlagsProperty Default ValueProperty Data TypeAccessObject IdentifierObject NameObjectTypeSystem StatusVendor NameVendor IdentifierModel NameFirmware RevisionApplication Software VersionLocationDescriptionProtocol VersionProtocol RevisionProtocol Services SupportedProtocol Object Types SupportedObject ListActive COV SubscriptionsMaximum APDU Length AcceptedMaximum APDU Length AcceptedAPDU TimeoutNumber of APDU RetriesMax MasterMax Info FramesDevice Address BindingDatabase RevisionProperty ListSerial Number607xxx“Series IEF 607xxx”DEVICE(8)Operational(0)“Dwyer Instruments, Inc.”607“IEF-HN-10-COM”“x.x.x”“x.x”“ ”“ ”114See BACnet Services belowSee Table AboveSee Table Above480NO_SEGMENTATION (3)600031271Empty1“xxxxxxxx” BACnetObjectIdentifierCharacterString(40)BACnetObjectTypeBACnetDeviceStatusCharacterStringUnsignedCharacterStringCharacterStringCharacterStringCharacterString(32)CharacterString(32)UnsignedUnsignedBACnetServicesSupportedBACnetObjectTypesSupportedBACnetArrayList of BACnetCOVSubscriptionUnsignedBACnetSegmentationUnsignedUnsignedUnsignedUnsignedBACnetAddressBinding UnsignedBACnetARRAY[N] of BACnetPropertyIdentifierCharacterStringRead/WriteRead/WriteReadReadReadReadReadReadReadRead/WriteRead/WriteReadReadReadReadReadReadReadReadRead/WriteRead/WriteRead/WriteReadReadReadReadNext >