Series 641 Air Velocity TransmitterSpecifications - Installation and Operating InstructionsBulletin E-66CEThe Series 641 Air Velocity Transmitter (AVT) uses a heated mass flow sensor technology. It has 8 user selectable ranges from 250 FPM to 15000 FPM with corresponding metric ranges of 1.25 MPS to 75 MPS. The Series 641 AVT provides an isolated 4 to 20 mA output proportional to the velocity. With the optional 1/2˝ 4-1/2 digitLED display, the Series 641 AVT will provide a highly visible local readout of the velocity.INSTALLATIONLocation: Select a location where the temperature will be within 32 to 140°F (0 to 60°C) to mount the enclosure. The transmitter may be located any distance from the receiver provided that the total loop resistance does not exceed 600 ohms. The probe should be located where conditions are representative of the overall environment being monitored. Avoid locations where turbulence, stagnation, or rapidly fluctuating velocities or temperatures are present as these conditions may affect the readings. The filter setting may be used to average velocity readings in turbulent conditions.Position: The transmitter is not position sensitive and may be mounted in any orientation.Mounting: An integral 1/2˝ NPT allows direct mounting to pipe fittings or a pipe flange. The Series 641 AVT may also be mounted using a 5/16˝ compression fitting. Arrows on the hex flats at the base of the probe indicate the direction of the calibrated airflow. Align these arrows in the direction of the process air. The case may be rotated independently of the probe for ease of connection.Airflow: The Series 641 AVT is intended for use with clean dry air. Particulates in the air may cause sensor damage. Dust accumulation may impair the velocity measurement and will require probe cleaningSPECIFICATIONSService: Air and compatible, non-combustible gases.Accuracy: 3% FS Process gas: 32 to 122° F (0 to 50°C); 4% FS Process gas: -40 to 32°F & 122 to 212°F (-40 to 0°C & 50 to 100°C).Response Time: Flow: 1.5 seconds to 95% of final value (Output filter set to minimum).Temperature Limits: Process: -40 to 212°F (-40 to 100°C). Ambient: 32 to 140°F (0 to 60°C).Pressure Limit: 100 psi (6.89 bar) maximum.Humidity Limit: Non-Condensing.Power Requirements: 12–35 VDC, 10–16 VAC.Output Signal: 4 to 20 mA, isolated 24 V source, 3 or 4-wire connection.Output Filter: Selectable 0.5 –15 (seconds).Loop Resistance: 600 ohms max.Current Consumption: 300 mA max.Electrical Connections: Screw terminal.Process Connections: 1/2˝ male NPT.Mounting Orientation: Unit not position sensitive. Probe must be aligned with airflow.Weight: 12.6 oz. (357.2 g).Agency Approvals: CE (See text for test standards).OPTIONAL DISPLAY VERSION:Display: 4-1/2 digit 1/2˝ Red LED.Resolution: 1 FPM, 0.01 MPS (10 FPM @ 10,000 and 15,000 FPM ranges).Weight: 13.3 oz. (377 g).4-29/64[113.11]1/2 NPT1/2-14 NPT13/16[20.64]B DIMENSIONA DIMENSION3-1/4[82.55]B DIMENSIONA DIMENSION2-23/32[29.06]4-29/64[113.11]1/2 NPT1/2-14 NPT25/32[19.84]641 AVT WITH DISPLAY OPTIONA DimensionB Dimension7-63/64 [202.80]13-63/64 [355.20]19-63/64 [507.60]26-63/64 [685.40]32-63/64 [837.80]37-63/64 [964.80]9-13/16 [249.24]15-13/16 [401.64]21-13/16 [554.04]28-13/16 [731.84]34-13/16 [884.24]39-13/16 [1011.24]641 AVT WITHOUT DISPLAY OPTIONA DimensionB Dimension7-7/16 [188.91]13-7/16 [341.31]19-7/16 [493.71]26-7/16 [671.51]29-7/16 [747.71]37-7/16 [950.91]9-9/32 [235.74]15-9/32 [388.14]21-9/32 [540.54]28-9/32 [718.34]34-9/32 [870.74]39-9/32 [997.74]®DWYER INSTRUMENTS, INC.P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.Phone: 219/879-8000Fax: 219/872-9057www.dwyer-inst.come-mail: info@dwyermail.comNote: Where conduit connections are not made, a 1/2˝ NPT cable seal should be used to prevent contaminants from entering the case. Where conduit connections are made, make sure that any possible condensation within the conduit will not flow into the transmitter housing.ELECTRICAL CONNECTIONThe Series 641 AVT has been designed for easy and flexible connection to power and loop receivers. Electrical connection is made inside the body of the device with a “Euro” style terminal block. The device features a current loop that is fully isolated from the power source. The current loop has an internal 24 V isolated supply so no external loop power is required. With full isolation, loop grounding is not a concern. The input power requirements are also very flexible. The device may be powered from either an AC or DC power source. CAUTION: Do not exceed the specified supply voltage rating. Permanent damage not covered by the warranty may result. Do not use an external power source on the current loop connection.Receiver-Transmitter Connection - The Series 641 AVT is designed as a three or four wire 4 to 20 mA device. Thevcurrent loop output is isolated from the power supply input and provides an internal 24-volt loop supply. With a DC power supply, a three or four-wire connection may be used. Do not use a three-wire connection with an AC power source. In a three-wire connection either power supply wire may be used as the common. The total loop resistance should not exceed 600 Ohms.CAUTION: Do not use a receiver with an internal power supply or use an external supply in the current loop. The current loop is powered from within the Series 641 AVT. Connecting an external supply to the current loop may destroy the transmitter. Using an external supply voids the warranty.Power Supply Connection - The power supply may be either AC or DC. The DC power may be from 12 to 35 volts. The power connection is not polarity sensitive so the positive and negative connections may be made to either power terminal. The AC connection may be from 10 to 16 VAC RMS. Do not exceed 20 VAC. When selecting a transformer please note that the specified output for transformers is at some specified current. With a load current less than the specified current transformer output may be significantly higher than the specified voltage. Transformers with secondary voltages of 10 to 16 VAC are recommended.CAUTION: Do not use transformers with a secondary voltage rating greater than 16 VAC RMS.3 or 4-Wire ConnectionInterior Label DiagramWire Type and Length - The wire selection for an installation is often overlooked or neglected and may contribute to improper or even intermittent operation. In all cases ensure that the connection meets all applicable national and local electrical codes. Although the 4 to 20 mA current loop systems are relatively immune to wire or wiring related problems, selection of the wire for some installations will be an important factor in ensuring satisfactory system operation. Twisted conductors will usually be immune to most stray electric and magnetic fields and to some extent electromagnetic fields, such as interference from RF transmitters. With twisted pair wiring the current loop and the power connections should be separate pairs. Avoid using flat or ribbon cable that has no regular conductor twist. Where interference is possible, it is recommended that shielded wire be used. The shield must not be used as one of the conductors and should be connected to ground at only one end, generally at the power supply. Similarly, if the installation uses conduit, the conduit should be connected to protective ground as specified by the applicable code and the signal wiring must not be connected to the conduit at more than one point or as specified by the code. The maximum length of wire connecting the transmitter and receiver is a function of the wire resistance and receiver resistance. The total loop resistance must not exceed 600 Ohms, including the receiver resistance and wire resistance. The power supply connection must be designed so that the worst case voltage drop due to wire resistance will not cause the power supply voltage at the transmitter to drop below the specified value. Provided the power supply voltage is maintained within the specified voltage range, the Series 641 AVT is not affected by variations in power supply voltage.TRANSMITTER SETUPThe Series 641 AVT has been designed for easy setup. It has five configuration parameters that may be adjusted by the user. These parameters are Output Filter, Range (In English or Metric), span, 4 mA set-point and 20 mA setpoint. All of these may be adjusted at any time in the field. These adjustments may also be easily returned to factory default.A set of controls and indicators are provided within the unit consisting of the select button, enter button, adjustment control, and six LED indicators. When operating normally, only the RUN LED indicator will be illuminated. During the setup operation the LED indicators will indicate the parameter selected, when it is being adjusted, and status of the adjustment process. If the unit is left in the setup mode for several minutes without any activity it will return to the normal operating mode.POWER SUPPLYAC OR DCRECEIVER4-WIRE3-WIRERECEIVER NEGATIVECOMMONRECEIVERDC SUPPLYONLY(EITHERPOLARITY)3-WIRERECEIVER POSITIVECOMMONRECEIVERDC SUPPLYONLY(EITHERPOLARITY)Two buttons and a potentiometer control the setup process.The SELECT button is used to scroll between the setup parameters.The ENTER button allows access to each parameter for adjustment.The ADJUST potentiometer is used to change the value of the parameters.Holding the ENTER button for 2.5 seconds saves the new parameter value.Making AdjustmentsThe adjustment process has three steps: select the parameter, adjust the parameter, save the new value. These are described in the following steps: 1. Select the parameter: Each time the SELECT button is pressed the LED indicator will advance to the next parameter. When the last parameter, SPAN, is selected, the next time the SELECT is pressed the unit will return to RUN mode. Press the SELECT button until the LED indicator illuminates the desired parameter. Press ENTER. The selected indicator will begin to blink, showing the parameter may now be adjusted. If the unit is left in the setup mode, after several minutes it will reset to the operate mode. 2. Adjust the parameter: Turn the ADJUST potentiometer until the desired setting is made. This may be adjusted using a small screwdriver or similar tool. Be careful not to force the control past its stops or damage will result. 3. Save the Parameter: To save the new parameter press and hold the ENTER button. The LED indicator will begin to flash at a faster rate. After about 2.5 seconds all of the LED indicators will flash when the parameter is saved. If you do not want to save the parameter press the SELECT button without entering the parameter. The adjusted value will be discarded and next LED indicator will be illuminated.Adjusting the Output FilterThe output filter may be adjusted to smooth the readings when measuring turbulent flow. The time constant may be adjusted from 0.5 seconds to 15 seconds. To adjust the filter time constant, select the FILTER indicator. Press ENTER to enable adjustment. Turn the ADJUST until the desired amount of damping is achieved. To save the value press and hold the ENTER button until the LED indicators all flash, indicating the value was saved. To discard the adjustment press SELECT before pressing the ENTER button.OUTPUT FILTER RESPONSE (values in seconds)% of Full VelocityFilter Setting on Adjust DialMin.Mid.Max.63%90%95%99%0.51.11.52.37.517.322.534.51534.544.969.0Range SelectionThe range selection allows you to select one of eight ranges in either feet per minute (FPM) or meters per second (MPS).Ranges:FPM: 250, 500, 1000, 2000, 3000, 5000, 10000, 15000MPS: 1.25, 2.5, 5, 10, 15, 25, 50, 75Select the RANGE indicator by pressing ENTER when the RANGE LED indicator is illuminated. The A,B,C LED indicators will display which range setting is currently active. Press ENTER to enable adjustment. Turn the ADJUST until the desired range indication is achieved. If you want to discard the adjustment press SELECT. If you want to save the range press and hold ENTER. The RANGE LED will blink at a faster rate for about 2.5 seconds then all of the LEDs will flash indicating the value was saved.The range setting is displayed with the LED indicators. The function of these indicators is summarized on the control label inside the unit. The following table summarizes the indicator status for each range setting.OUTPUT FILTER RESPONSE (values in seconds)Range/UnitsRunFilterRangeSpan4 mA20 mAABC250 FPM500 FPM1000 FPM2000 FPM3000 FPM5000 FPM10000 FPM15000 FPM1.25 MPS2.5 MPS5 MPS10 MPS15 MPS25 MPS50 MPS75 MPS1111111100000000000000001111111111111111111111110000111100001111001100110011001101010101010101011: Indicator on; 0: Indicator off.Printed in U.S.A. 12/18FR# 443205-10 Rev. 2©Copyright 2018 Dwyer Instruments, Inc.DWYER INSTRUMENTS, INC.P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.Phone: 219/879-8000Fax: 219/872-9057www.dwyer-inst.come-mail: info@dwyermail.comSpan SettingThe Series 641 AVT has been calibrated for standard sea level conditions. As a mass flow device it will always read the air velocity for standard conditions. Density changes due to barometric or absolute pressure are not corrected automatically. The span setting allows correction for altitude or other static pressure conditions that affect the density of the process air. This parameter allows for a ±50% adjustment inthe span value.To make the span adjustment you will need to know either the absolute static pressure or the corrected velocity of the process air. Set the air velocity to a known value, ideally about 3/4 of the full-scale range value. Press SELECT until the SPAN LED indicator is illuminated then press ENTER. The SPAN LED will begin to blink. Adjust the control for the desired velocity then press and hold the ENTER button until all of the LED’s flash, indicating the new value was saved. If you know the absolute static pressure you can compute the corrected velocity using the following equation:Vcor = VrdgWhere:P0 is the standard pressure of 29.9 in. Hg. or 760 mm Hg.PA is the absolute pressure readingVrdg is the indicated velocityVcor is the corrected velocity4 mA SettingTo make this setting you will need a milliammeter connected in the current loop. It is not required to use a known air flow velocity to make this calibration setting. The calibration settings of the velocity and the mA outputs are independent of each other. Press SELECT until the 4 mA LED indicator is illuminated then press ENTER. The milliammeter will now read approximately 4.0 mA. Adjust the control for a 4.0 mA reading on the milliammeter. Press and hold ENTER to save the new setting. Pressing SELECT before pressing ENTER will restore the previous calibration value.20 mA SettingIt is not required to use a known air flow velocity to make this calibration setting. The calibration settings of the velocity and the mA outputs are independent of each other. Press SELECT until the 20-mA LED indicator is illuminated. Press ENTER to begin adjustment of the 20-mA set point. The 20 mA LED will now be blinking. Adjust the control until the milliammeter reads 20.0 mA. Press and hold ENTER to save the new setting. Pressing SELECT before pressing ENTER will restore the previous calibration value.Restoring Factory Default SettingsThe 4 mA, 20 mA, and Range settings override factory default values. To restore these to the factory default settings, start with the unit in the RUN mode. Press and hold the ENTER button. The RUN LED indicator will begin to blink. After about 2.5 seconds all LED indicators will flash indicating the factory settings have been restored. Range and Filter settings are not affected by this operation. If you are unsure whether any have been altered, press the SELECT button six times to sequence through all settings. When you return to the RUN mode, the RUN LED indicator will blink several times if either the 4 mA, 20 mA, or span settings have been changed. The RUN LED will otherwise remain on.MAINTENANCEIn general the Series 641 AVT should require very little maintenance. In some installations dust may accumulate on the sensor over time. This can be removed by carefully brushing the probe with a small camel hairbrush. If too much force is applied during cleaning, the sensor of the Series 641 AVT may be damaged. Therefore, a trained technician should perform the cleaning operation. A jet of air may also dislodge the accumulated buildup however, again, the sensor is delicate and this operation should be done carefully with clean regulated air. Using a shop air supply may exert enough force to damage the sensor. Most air supplies of this sort will also contain water or oil that could damage the sensor. Technical grade denatured or isopropyl alcohol may be used where the dust accumulation does not respond to brushing. Do not use water. Always disconnect the power when performing a cleaning operation.Aside from field calibrations for span, 4 mA and 20 mA setting as described above, the Series 641 cannot be fully factory calibrated in the field. Because of specialized computer instrumentation required, these units must be returned to Dwyer Instruments for factory calibration. Contact customer service to receive a return goods authorization number before shipping.CEThe following standards were used for CE approval:IEC 61000-4-2: 2001IEC 61000-4-3: 2002IEC 61000-4-4: 1995IEC 61000-4-5: 2001IEC 61000-4-6: 2003IEC 55011: 1998IEC 61326: 200289/336/EEC EMC DirectiveThis symbol indicates waste electrical products should not be disposed of with household waste. Please recycle where facilities exist. Check with your Local Authority or retailer for recycling advice.POPANext >