Automation Components, Inc.TEMPERATURE | TRANSMITTERS | FREEZERPRODUCT SPECIFICATIONSTEMPERATURE | ## Call: 1-888-967-5224 | Web: www.workaci.com +13.5 to 32 VDC into 250 Ohm Load (Reverse Polarity Protected) | 25 mA minimum+18.5 to 32 VDC into 500 Ohm Load(Terminal Voltage - 8.5 V) | 0.020 A | (775 Ohms @ 24 VDC)Current: 4-20 mA (2-Wire Loop Powered) | Voltage: 1-5 VDC or 2-10 VDC (3-Wires)Temp. Spans < 500ºF (260ºC): +/- 0.2% | Temp. Spans > 500ºF (260ºC): +/- 0.5% Temp. Spans < 100ºF (38ºC): +/- 0.04%/ºF | Temp. Spans > 100ºF (38ºC): +/- 0.02%10 Minutes | +/- 0.1% -40ºF (-40ºC) to 185ºF (85ºC)0 to 90%, non-condensing Minimum Temp. Span: 50ºF (28ºC) | Maximum Temp. Span: 1000ºF (538ºC) -45 to 155ºC (-49 to 311ºF) Screw Terminal Blocks (Non-Polarity Sensitive) | 16 AWG (1.31 mm) to 26 AWG (0.129 mm)0.5 Nm nominalPlatinum RTD | Linear, PTC (Positive Temperature Coecient)Three Conductors (White and Two Red Wires); Polarity Sensitive (Red wires tied together)A/TT/TTM100-LTS Series: 100 Ohms nominal | A/TT/TTM1K-LTS Series: 1000 Ohms nominal Class B | Accuracy Formula: +/- ºC = (+/- 0.30ºC + (0.005 x |t|)) -200ºC (-328ºF): +/- 1.30ºC (+/- 2.34ºF) | 0ºC (-32ºF): +/- 0.30ºC (+/- 0.54ºF) 3850 ppm / ºC | DIN EN 60751 (IEC 751)< 0.04% @ 1000 hours @ 400ºC (752ºF)15 Seconds nominal20 PSI (1.38 Bars) maximum -200 to 200ºC (-328 to 392ºF) “-GD” Enclosure: -40 to 100ºC (-40 to 212ºF); Galvanized Steel; NEMA 1 (IP10)“-BB” Enclosure: Aluminum, -40 to 121ºC (-40 to 250ºF), Plenum Rated, NEMA 3R (IP 14) “-4X” Enclosure: -40 to 70ºC (-40 to 158ºF); Polystyrene Plastic; UL94-V2; NEMA 4X (IP 66)-40 to 80ºC (-40 to 176ºF)10 to 95% RH, non-condensingPG7 | 15 mm (0.591”) | Polyamide 6Neoprene | 0.098” (2.5 mm) to 0.256” (6.5 mm)IP 68 (NEMA 6P) | 2.5 Nm (22.127 lb. inch)316 Stainless Steel | 2” (50.8 mm) | 0.1875” (4.76 mm) nominal10’ (3.05 m) or 30’ (9.15 m) | 0.106” nominal (2.69 mm) 24 AWG (0.51 mm) | Silver Plated CopperFEP/FEP (Teon) Jacketed Cable | White A/TT/TTMxxx-LTS-BB-10’: 0.84 lbs (0.39 kg) | A/TT/TTMxxx-LTS-BB-30’: 1.04 lbs (0.48 kg)A/TT/TTMxxx-LTS-4X-10’: 0.42 lbs (0.19 kg) | A/TT/TTMxxx-LTS-4X-30’: 0.62 lbs (0.29 kg)Transmitter Supply Voltage | Current:Maximum Load Resistance:Output Signals:Calibrated Transmitter Accuracy | Linearity: Temperature Drift:Warm Up Time | Warm Up Drift:Operating | Storage Temperature Range:Operating Humidity Range:Calibrated Temperature Spans:Matched Calibrated Temperature Spans (A/TTM models) Range:Connections | Wire Size:Terminal Block Torque Rating:Sensor Type | Sensor Curve:Number Wires:Sensor Output @ 0ºC (32ºF): RTD Tolerance Class: Sensor Accuracy:Temperature Coecient | Din Standard:Stability:Response Time (63% Step Change):Pressure Test:Sensor Operating Temperature Range:Enclosure Specications (OperatingTemperature, Material, Flammability, NEMA/IP Ratings):Storage Temperature Range:Operating Humidity Range:Cable Gland (Fitting) Size | Hole Size | Material:Cable Gland Sleeve Material | Wire Clamping Size:Cable Gland IP Rating | Torque Rating:Probe Material | Length | Diameter:Lead Length | Cable Diameter:Conductor Size | Conductor Material:Lead Wire Insulation | Jacket Color:Product Weights:Agency Approvals:Note: Transmitter’s calibrated at 71ºF (22ºC) nominal | Note: Where t is the Absolute Value of temperature in Centigrade above or below 0ºCFREEZERRemote Freezer TransmittersThe ACI RTD Freezer Series features a 3/16” diameter stainless steel probe with a 10 Foot or 30 Foot, 3 Conductor, 24 AWG Plenum rated jacketed Teon cable. The sensor is designed to be used in Pharmaceutical, Liquid Nitrogen, Freezers, Refrigerators and Hydronic applications where a remote sensor is required. Optional “-GD” galvanized, “-BB” Aluminum, or “-4x” NEMA 4X weather proof plastic enclosures are available as well as NIST Certicates as referenced on the back of the product data sheet. A/TT Series transmitter accuracies must be calculated using both the calibration accuracy of the transmitter and the sensor accuracy over your applications operating temperature range. For higher accuracies, the A/TTM Series includes a secondary calibration process designed to eliminate most of the sensor error from the overall system accuracy. Any Freezer Transmitter can be used with the Single or Triple Point Glycol Kits when a Thermal Buer (slower) response time is desired. Applications: Pharmaceutical, Liquid Nitrogen, Refrigerators, Freezers, Hydronic Heating, Remote Sensor ApplicationsThe ACI Transmitter Freezer Series is covered by ACI's Five (5) Year Limited Warranty. The warranty can be found in the front of ACI's Sensors & Transmitters catalog, as well as on ACI's website, www.workaci.com.4XBBGDAutomation Components, Inc.TEMPERATURE | TRANSMITTERS | FREEZERTEMPERATURE | ## Call: 1-888-967-5224 | Web: www.workaci.com TT100 = 100 Ohm RTD | TTM100 = Matched 100 Ohm RTD (Specify 3 or 5 Point NIST)TT1K = 1K Ohm RTD | TTM1K = Matched 100 Ohm RTD (Specify 3 or 5 Point NIST)A/LTS = Freezer SensorGD = Galvanized Enclosure | BB = NEMA 3R Enclosure | 4X = NEMA 4X Enclosure1 = 1 to 5 VDC (3-Wire) | 2 = 2 to 10 VDC (3-Wire) | 4 = 4 to 20 mA (2-Wire Loop Powered)OPTIONAL SENSOR ORDERINGA. Sensor Series No Selection RequiredB. Model Series Select One (1)C. Conguration No Selection RequiredD. Output Signal Select One (1)E. Enclosure Select One (1)10’ = 10 Feet Leads (3.05 m) | 30’ = 30 Feet (9.15m) F. Lead Length Select One (1)Specify Span in ºF or ºC (Best Accuracy in 100ºF Increments)G. Calibrated Span MODEL #A/LTSModel # Example:A/A.TT100B.LTSC.1D.GDE.G.DIMENSIONAL DRAWINGRight ViewFront ViewTop ViewNEMA 4X Enclosure [4X]Galvanized Enclosure [GD]Bell Box Enclosure [BB]3.70”(93.98mm)3.11”(78.994mm)2.21"(56.13mm) 1.96” (49.78mm) 0.86"(21.84mm) 2.55” (64.77mm)1.62”(41.14mm)4.20”(106.68mm)2.33”(59.18mm)3.50” (88.90mm)3.18”(80.77mm).199”(5.05mm)2.82”(71.62mm)2.00”(50.80mm)4.56”(115.82mm)10’F.Next >