Automation Components, Inc.WIRELESS | MOD9200LONWIRELESS | ## Call: 1-888-967-5224 | Web: www.workaci.com PRODUCT SPECIFICATIONSSupply Voltage: Supply Current:Connections:Wire Size:Terminal Block Torque Rating:Operating Temperature Range:Operating Humidity Range:Storage Temperature Range:Data Protocol:RF Characteristics:Transmission Distance:LonWorks® Protocols :Physical Network Connection:Communication Wire:Termination:Conguration Software:System Requirements:Enclosure Material | Flammability Rating:Product Dimensions:Product Weight:24 VAC, 60Hz (Full wave rectied)0.5A NominalScrew Terminal Blocks16 AWG (1.31mm) to 26 AWG (0.129mm) 0.37 ft-lb (0.5 Nm) Nominal32 to 122ºF (0 to 50ºC)30 to 50% RH, Noncondensing-4 to 176ºF (-20 to 80ºC)IEEE 802.15.4-2003/2006900 MHz, Operating Frequency 10 channels between 902 – 928 MHzTransmitter Power: 11 dBm | Receiver Sensitivity: -11 dBm 200 – 300 ft horizontally depending on building type and constructions, and typically one oorabove and below the transceiver verticallyTemperature: SNVT_temp_p | Override Push Button: SNVT_occupancySetpoint Adjustment: SNVT_temp_p | Humidity: SNVT_lev_percentSensor Status/Alarms: SNVT_count PPM: SNVT_ppmThe MOD9200LON Transceiver is pre-dened with xed congurationsFTT-10 (Free Topology Twisted Pair)Eschelon approved 22 AWG wireNot provided by ACIIncluded; Data registers need to be congured prior to use•PC (Notebook or Laptop) with Windows 98, XP, Vista, Windows 7, or Windows 10, Ethernet port, and 10 GB of hard drive memory, direct connection from PC to MOD9200LON: RJ45 Crossover Cable (not provided by ACI)•IP Address of PC must have static address of 192.168.0.2 or aboveABS Plastic | UL94-5VA(L) 8.78” (223.01 mm) x (W) 4.72” (119.89 mm) x (H) 2.36“ (59.94 mm) 2.20 lbs (1.00 kg)MOD9200LON LonWorks® Network TransceiverThe MOD9200LON network transceiver uses the 900 MHz spread spectrum technology and is compatible with any Building Automation System or front end using LonWorks® protocol and FTT-10 interface. The MOD9200LON works with any ACI wireless sensor, input concentrator, or output module. The MOD9200LON can be programmed with inputs for a maximum of 50 physical wireless sensors, or 100 data points (analog & digital), and 100 output points (50 analog and 50 digital) maximum, with the data in the form of SNVTs (Standard Network Variable Types). The sensors are programmed to the transceiver using the conguration software (included), a laptop and a crossover cable. The MOD9200LON can be ordered in six dierent congurable XIF les depending on sensor types. Transmission distance in a typical building is 200-300 feet horizontal depending on the layout and construction of the building, and one oor above and one oor below the transceiver. Sensor distance and reliability can be increased with the addition of a RR2552B(s) repeater.ACI oers pre-programming of wireless systems for ease of installation, saving time and cost of eld setup. Prior to purchase, it is recommended to contact ACI’s Technical Service Department for product selection and system design/layout.Applications: Museums, Churches, Historical Buildings & New ConstructionThe MOD9200LON is covered by ACI's Two (2) Year Limited Warranty. The warranty can be found in the front of ACI's Sensors & Transmitters catalog, as well as on ACI's website, www.workaci.com.Note : Please refer to ordering grid or download user manual for details of dierent transceiver modelsAutomation Components, Inc.WIRELESS | MOD9200LONWIRELESS | ## Call: 1-888-967-5224 | Web: www.workaci.com STANDARD ORDERINGModel #MOD9200LON-AMOD9200LON-BMOD9200LON-CMOD9200LON-DMOD9200LON-EMOD9200LON-FItem #131048131049131050131051131052----DescriptionUp to 30 Wireless Temperature, 6 RH Sensors & 50 Wireless Digital & Analog OutputsUp to 50 Wireless Temperature Sensors (50 Wall/Duct/Immersion) & 50 Wireless Digital & Analog OutputsUp to 50 Wireless Sensors (50 Temperature & RH Points) & 50 Wireless & Analog OutputsUp to 50 Wireless Devices (40 0-10 VDC Point Types & Discrete Inputs, 10 Temperature & RH Points) & 50 Wireless Digital & Analog OutputsUp to 50 Wireless Sensors/Transmitters (26 Setpoint Adjustments, 26 Pushbutton Override Switches, 12 CO2 PPM Inputs, 6 RH Points & 4 Digital Status Inputs) & 50 Wireless Digital & Analog OutputsUp to 50 Wireless Sensors (40 Temperature Points, 20 RH Points and 40 Discrete Inputs) & 50 Wireless Digital & Analog Outputs-OR-Model # Example:131048MOD9200LON-AADDITIONAL ORDERINGModel #RR2552BRR2552BEWIRELESS SETUP FEEItem #130662130694132618DescriptionTwo Way Repeater, Standard EnclosureTwo Way Repeater, NEMA 4X EnclosurePre-programming Wireless System-OR-Model # Example:130694RR2552BE4.72” (119.89mm)8.26”(209.80mm)7.62”(193.55mm)8.78”(223.01mm)2.36”(59.94mm)DIMENSIONAL DRAWINGFront ViewRight ViewTop ViewNext >