Automation Components, Inc.WIRELESS | DT2630WIRELESS | ## Call: 1-888-967-5224 | Web: www.workaci.com PRODUCT SPECIFICATIONSInput Voltage:Battery Life:Operating Temperature Range:Operating Humidity Range:Storage Temperature Range:Sensor Temperature Range:Accuracy:Probe Material:Probe Diameter:Probe Lengths:Fitting / Flammability Rating:Data Protocol:RF Characteristics:Sensor Data Transmission Time:Transmission Distance:Enclosure Material | Flammability Rating:Product Dimensions:Product Weight:Battery; 1 (Duracell DL123A), Lithium 3V 1400mAh 45 mA maximum 2-3 years typical14 to 140ºF (-10 to 60ºC)5 to 65%, Non-condensingTemperature: 0 to 176ºF (-17 to 80ºC) | Humidity: 5 to 65%, Non-condensing-40 to 200ºF (-40 to 93ºC)+/- 1ºF (+/- 0.555ºC) 12 bit resolution304 Stainless Steel0.25” (6.35 mm)4”, 6”, 8”, 12” & 18”ST801A Polyamide 66 Plastic (PA66) toughened “Zytel”, UL94-HBIEEE 802.15.4-2003/2006900 MHz, Operating Frequency 10 channels between 902 – 928 MHzTransmitter Power: 11 dBm | Receiver Sensitivity: -11 dBm 75 seconds (default) | 300 seconds (optional)200 – 300 ft horizontally depending on building type and construction, and typically one oorabove and below the transceiver verticallyStandard: ABS Plastic | UL94NEMA 4X: Polycarbonate Plastic | UL94-HBStandard: (L) 5.77” (146.56 mm) x (W) 3.19” (81.03 mm) x (H) 1.88” (47.75 mm)NEMA 4X: (L) 4.52” (114.81 mm) x (W) 3.54” (89.92 mm) x (H) 2.16” (54.86 mm) DT2630A-04: 0.99 lbs (0.45 kg)DT2630A-06: 1.00 lbs (0.45 kg)DT2630A-08: 1.01 lbs (0.46 kg)DT2630A-12: 1.03 lbs (0.47 kg)DT2630A-18: 1.05 lbs (0.48 kg)DT2630Duct TemperatureThe DT2630 is a battery operated wireless duct sensor that gives the exibility and ease of installation for monitoring duct temperatures wirelessly using 900MHz spread spectrum technology rather than costly hardwire installations. The single point probe is 0.25” O.D., made of 304 stainless steel, and is available in 4”, 6”, 8”, 12”, and 18” lengths to t most applications. The DT2630 can be ordered with the standard enclosure or NEMA 4X enclosure depending on the specications required. The DT2630 will send the temperature wirelessly to the RM2432D receiver that converts the wireless signal to voltage input for use with a DDC controller, or to a transceiver which will send the data to a BAS using BACnet, Modbus, or Lonworks protocol. Transmission distance in a typical building is 200-300 feet horizontal depending on the layout and construction of the building, and one oor above and one oor below the transceiver. Sensor distance and reliability can be increased with the addition of a RR2552B(s) repeater. Applications: Museums, Churches, Historical Buildings & New ConstructionThe DT2630 is covered by ACI's Two (2) Year Limited Warranty. The warranty can be found in the front of ACI's Sensors & Transmitters catalog, as well as on ACI's website, www.workaci.com.StandardNEMA 4XDT2630AE-04: 2.82 lbs (1.28 kg)DT2630AE-06: 2.83 lbs (1.28 kg)DT2630AE-08: 2.84 lbs (1.29 kg)DT2630AE-12: 2.86 lbs (1.30 kg)DT2630AE-18: 2.88 lbs (1.31 kg)Automation Components, Inc.WIRELESS | DT2630WIRELESS | ## Call: 1-888-967-5224 | Web: www.workaci.com STANDARD ORDERINGModel #DT2630A-04DT2630A-04-300DT2630A-06DT2630A-08DT2630AE-04DT2630AE-18Item #131022141063131023131024131027131031DescriptionWireless Duct Temperature Sensor (4”), Standard Enclosure Wireless Duct Temperature Sensor (4”), Standard Enclosure, 300 Second IntervalWireless Duct Temperature Sensor (6”), Standard Enclosure Wireless Duct Temperature Sensor (8”), Standard Enclosure Wireless Duct Temperature Sensor (4”), NEMA 4X Enclosure Wireless Duct Temperature Sensor (18”), NEMA 4X Enclosure -OR-Model # Example:131022DT2630A-045.77” (146.56mm)3.19”(81.03mm)3.54”(89.92mm)4.52”(114.81mm)DIMENSIONAL DRAWINGFront ViewRight ViewTop ViewStandardNEMA 4XA = Standard Enclosure (Default) | AE = NEMA 4X EnclosureDT263004 = 4” Probe | 06 = 6” Probe | 08 = 8” Probe | 12 = 12” Probe | 18 = 18” ProbeCUSTOM ORDERINGA. Sensor Series No Selection RequiredB. Enclosure Select One (1)C. Probe Length Select One (1)---- = Every 75 Seconds (Default) | 300 = Every 300 SecondsD. Transmission Interval Select One (1)MODEL #DT2630Model # Example:DT2630A.AB.04C.300D.3.19” (81.03mm)1.88” (47.75mm)Ø.25”(6.35mm)Probe Available in 4”, 6”, 8”, 12” or 18” Lengths2.16” (54.86mm)Ø.25”(6.35mm)Probe Available in 4”, 6”, 8”, 12” or 18” LengthsNext >