Automation Components, Inc. INTERFACE | ATL INTERFACE | ## Call: 1-888-967-5224 | Web: www.workaci.com ATL Analog Current/Voltage to 4 Adjustable SPDT Relays The ATL accepts an analog (voltage or current) input signal and controls four relays. Each relay has an adjustable trip point which is set by a multi-turn potentiometer. Each relay is activated when the input signal is equal to, or greater than, the trip point setting. Relays deactivate at trip point less the deadband (3% standard, 1% & 10% optional). Common (C), Normally Open (NO), and Normally Closed (NC) terminals are available at each relay. The ATL is eld calibratable, however, factory calibration is available upon request for an additional charge. This will speed up installation time for the end user. Applications: Level Indication, Digital Output Expansion, Alarms, Staging and Sequencing The ATL is covered by ACI's Two (2) Year Limited Warranty. The warranty can be found in the front of ACI's Sensors & Transmitters catalog, as well as on ACI's website, www.workaci.com. Supply Voltage: Supply Current: Input Voltage Signal Range (@ Impedance): Input Current Signal Range (@ Impedance): Deadband (0-12 VDC Signal): Deadband (0-24 VDC Signal): Deadband (0-20 mA Signal): Digital Output Type: Relay Contact Rating: Relay Electrical Life: Relay Mechanical Life: Connections: Wire Size: Terminal Block Torque Rating: Operating Temperature Range: Operating Humidity Range: Storage Temperature: Snaptrack Material: Snaptrack Flammability Rating: Product Dimensions: Product Weight: Agency Approvals: 24 VAC (+/- 10%), 50/60 Hz or 22-28 VDC 180 mA maximum 0 to 12 VDC @ 10M, 0 to 24 VDC @ 20,000 0-20 mA @ 500 3% Version (Standard): 0.33 VDC | 10% Version: 1.0 VDC | 1% Version: 0.1 VDC 3% Version (Standard): 0.66 VDC | 10% Version: 2.0 VDC | 1% Version: 0.2 VDC 3% Version (Standard): 0.66 mA | 10% Version: 2.0 mA | 1% Version: 0.2 mA Four SPDT Form “C” Relays 2A @ 24 VDC, 0.5A @ 240 VAC 100,000 operation @ 1A 10,000,000 operations 45° Captive screw Terminal Blocks 12 (3.31 mm) to 22 AWG (0.33 mm) 0.5 Nm (Minimum); 0.6 Nm (Maximum) 35 to 120°F (1.7 to 48.9°C) 10 to 95% non-condensing -20 to 150°F (-28.9 to 65.5°C) Polyvinyl Chloride (PVC) UL94 V-0 (L) 2.75” (W) 3.25” (H) 1.00” (69.85 x 82.55 x 25.4 mm) 0.25 lbs. (0.113 Kg) RoHS2, WEEE PRODUCT SPECIFICATIONS2.75” (69.85mm) 3.25” (82.55mm) 0.70” (17.78mm) DIMENSIONAL DRAWING Board OnlySnap TrackSnap Track Automation Components, Inc. INTERFACE | ATL INTERFACE | ## Call: 1-888-967-5224 | Web: www.workaci.com STANDARD ORDERING Model # ATL ATL-DB-1% ATL-DB-10% Item # 105978 129665 129663 Description Analog Current/Voltage to 4 Adjustable SPDT Relays Analog Current/Voltage to 4 Adjustable SPDT Relays Analog Current/Voltage to 4 Adjustable SPDT Relays Deadband 3% 1% 10% -OR-Model # Example:105978ATL ACCESSORIES Model # A/DO008 A/DRC 2.7 X 3.25 ENC1 Item # 142583 142624 102472 Description Transient Voltage Suppressor, Bi-directional, 56VAC/DC, 1500W DIN Rail Adapter Kit 20 Gauge Metal Enclosure, Designed to Hold Interfaces Products -OR-Model # Example: 142583A/DO008 3.25” (82.55mm) 2.70” (68.58mm)Next >